15A NCAC 18A .2500 — Rules Governing Public Swimming Pools

15A NCAC 18A .2508-.2545Eff. 1991-05-01; Amended eff. 2024-11-01529 inspection points
.2508

Definitions

The following definitions apply throughout this Section:
(1) "Department" means North Carolina Department of Health and Human Services.
(2) "Equipment replacement" means replacement of individual components of the hydraulic and disinfection systems such as pumps, filters, and automatic chemical feeders.
(3) "Public swimming pool" means public swimming pool as defined in G.S. 130A-280. Public swimming pools are divided into five types:
(a) "Swimming pools" are public swimming pools used primarily for swimming.
(b) "Spas" are public swimming pools designed for recreational and therapeutic use that are not drained, cleaned, or refilled after each individual use. Spas may include units designed for hydrojet circulation, hot water, cold water mineral bath, air induction bubbles, or any combination thereof. Common terminology for spas includes "therapeutic pool," "hydrotherapy pool," "whirlpool," "hot spa," and "hot tub."
(c) "Wading pools" are public swimming pools designed for use by children, including wading pools for toddlers and children's activity pools designed for casual water play ranging from splashing activity to the use of interactive water features placed in the pool.
(d) "Water recreation attractions" are pools designed for special purposes that differentiate them from swimming pools, wading pools, and spas. They include:
(i) water slide plunge pools and run out lanes, which transfer the kinetic energy of the users' velocity through friction to the slide;
(ii) wave pools;
(iii) rapid rides;
(iv) lazy rivers;
(v) interactive play attractions that incorporate devices using sprayed, jetted, or other water sources contacting the users and that do not incorporate standing or captured water as part of the user activity area;
(vi) training pools deeper than a 24 inch deep wading pool and shallower than a 36 inch deep swimming pool; and
(vii) artificial swimming lagoons as defined in G.S. 130A-280.
(e) "Special purpose and therapy pools" are pools designed and used for therapeutic treatments or physical training and fitness outside of a licensed medical facility or practice of a licensed physical therapist. They include:
(i) float tanks used for float therapy in a salt brine solution;
(ii) swim spa training pools which use jetted water for stationary swimming against a water current;
(iii) exercise therapy and treadmill pools equipped for water resistance exercise therapy; and
(iv) scuba pools designed and used for training swimmers to use self-contained underwater breathing apparatus.
(f) "Display spa at a temporary event" or "DSTE" is a portable, above ground spa that contains water but is not used for body immersion and is displayed at a temporary event.
(4) "Registered Design Professional" means an individual who is registered or licensed to practice engineering as defined by G.S. 89C or architecture as defined by G.S. 83A.
(5) "Remodeled" means renovated in a manner requiring disruption of the majority of the pool shell or deck, changes in the pool profile, or redesign of the pool hydraulic system.
(6) "Repair" means returning existing equipment to working order, replastering or repainting of the pool interior, replacement of tiles or coping, and similar maintenance activities. This term includes replacement of pool decks where the Department has determined that no changes are needed to underlying pipes or other pool structures.
(7) "Safety vacuum release system" means a system or device capable of providing vacuum release at a suction outlet caused by a high vacuum occurrence due to suction outlet flow blockage.
(8) "Splash zone" means the area of an interactive play attraction that sheds water to a surge tank or container to be recirculated.
(9) "Temporary event" means a non-permanent fair, carnival, circus, festival, or public exhibition.
(10) "Unblockable drain" means a drain of any size and shape that a human body cannot sufficiently block to create a suction entrapment hazard.
(11) "Water feature" means any component within a public swimming pool that pumps, jets, or sprays water above the waterline.
History Note: Authority G.S. 130A-280; 130A-282;
Eff. May 1, 1991;
Temporary Amendment Eff. June 1, 1994 for a period of 180 days or until the permanent rule becomes
effective, whichever is sooner;
Amended Eff. April, 1, 2013; May 1, 2010; March 1, 2004; April 1, 1999; January 1, 1996; October 1, 1994;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019;
Temporary Amendment Eff. December 3, 2019;
Amended Eff. July 1, 2022; October 1, 2020.
.2509

Plan Review and Approval

(a) Public swimming pools plans and specifications shall be prepared by a registered design professional if required by G.S. 89C Engineering or G.S. 83A Architecture, and shall be approved by the Department prior to construction. If required by G.S. 87-1 General Contractors, public swimming pools shall be constructed by swimming pool contractors licensed by the North Carolina Licensing Board for General Contractors.

What we inspect

Plans prepared by registered design professional when required

We check that your pool's construction plans were prepared by a licensed engineer or architect when the law requires one.

Must be: When required, the pool's plans must be created by a state-licensed design professional and approved by health officials before building begins.

If it fails: If plans were never sealed by a licensed professional, have one review and certify the existing pool design.

.2509(a)

What we inspect

Construction by licensed swimming pool contractor when required

We check that your pool was built by a properly licensed pool contractor when licensing is required.

Must be: When required, the pool must be built by a contractor licensed by the North Carolina Licensing Board for General Contractors.

.2509(a)

(b) The owner shall submit a minimum of two complete sets of plans to the local Health Department for review. Plans shall be drawn to scale and accompanied by specifications so as to permit a clear, comprehensive review by the local health department. All prints of drawings shall be a minimum of 18 x 24 inches and a maximum size of 36 x 42 inches. These plans shall include:

What we inspect

Minimum two complete plan sets submitted, scaled, sized 18x24-36x42 in

We check that at least two complete, properly sized sets of plans were submitted to the health department for review.

Must be: At least two full sets of scaled plans, each between 18x24 and 36x42 inches, must have been submitted for review.

.2509(b)

(1) Plan and sectional view dimensions of both the pool and the area enclosed by the barrier fences to include the bathhouse and the equipment room and pool accessories;

What we inspect

Plans include dimensions of pool and barrier-enclosed area

We check that the submitted plans show full dimensions of the pool and the fenced-in pool area.

Must be: Plans must include dimensioned drawings of the pool and the barrier-enclosed area, including the bathhouse and equipment room.

.2509(b)(1)

(2) Specifications of all treatment equipment used and their layout in the equipment room;

What we inspect

Plans include treatment equipment specifications and layout

We check that the plans list the pool's treatment equipment and show how it's laid out in the equipment room.

Must be: Plans must include specifications for all treatment equipment and their layout in the equipment room.

.2509(b)(2)

(3) A piping schematic showing piping, pipe size, inlets, main drains, skimmers, gutter outlets, vacuum fittings and all other appurtenances connected to the pool-piping system;

What we inspect

Plans include a complete piping schematic

We check that the plans include a complete diagram of the pool's piping system.

Must be: Plans must show a full piping schematic, including pipe sizes, inlets, main drains, skimmers, and other connected fittings.

.2509(b)(3)

(4) Layout of the chemical storage room; and

What we inspect

Plans include chemical storage room layout

We check that the plans show the layout of the chemical storage room.

Must be: Plans must include a layout of the chemical storage room.

.2509(b)(4)

(5) Specifications for the water supply and wastewater disposal systems that include aspects such as well location and backwash water disposal where applicable.

What we inspect

Plans include water supply and wastewater disposal specifications

We check that the plans document how the pool gets its water and where wastewater goes.

Must be: Plans must specify the water supply and wastewater disposal systems, including well location and backwash disposal where relevant.

.2509(b)(5)

(c) The Department shall approve, disapprove, or provide written comments on plans and specifications for public swimming pools within 30 days of their receipt. If such action is not taken within 30 days, the plans and specifications shall be deemed approved.

What we inspect

Department acts on plans within 30 days or they are deemed approved

We check that the health department responded to the plan submission on time.

Must be: The health department must approve, reject, or comment on submitted plans within 30 days, or the plans are automatically approved.

.2509(c)

(d) If construction is not initiated within one year from the date of approval, the approval is void.

What we inspect

Plan approval void if construction not started within one year

We check that construction began within the approval window after plans were approved.

Must be: Construction must start within one year of plan approval, or the approval becomes void.

If it fails: If more than a year passed without construction starting, resubmit the plans for a fresh approval.

.2509(d)

(e) The swimming pool contractor shall contact the local health department when pool pipes are in place and visible so that the local health department may conduct an open-pipe inspection of the pool piping.

What we inspect

Contractor arranges open-pipe inspection before pipes are covered

We check that the contractor had the health department inspect the piping before it was covered up.

Must be: The contractor must contact the health department to inspect the pool piping while it's still visible, before it's buried or covered.

.2509(e)

(f) Prior to issuance of the operation permit, the owner shall submit to the local health department a statement signed by a registered design professional stating that construction is complete and in accordance with approved plans and specifications and approved modifications. Observation of construction and a final inspection for design compliance by the certifying registered design professional or his representative are required for this statement.

What we inspect

Registered design professional certifies construction matches approved plans

We check that a licensed design professional signed off confirming the pool was built to the approved plans.

Must be: Before an operating permit is issued, a licensed design professional must certify, after inspecting the finished pool, that it matches the approved plans.

.2509(f)

(g) Upon completion of construction, the contractor shall notify the local health department and the owner. The contractor shall provide the owner with a complete set of drawings, which show as built, the location of all pipes and the connections of all equipment and written operating instructions for all equipment.

What we inspect

Contractor provides owner as-built drawings and operating instructions

We check that the contractor gave the owner as-built drawings and equipment operating instructions after construction.

Must be: The contractor must hand over drawings showing the actual pipe and equipment layout, plus written instructions for operating all equipment.

If it fails: If these documents were never provided, ask the original contractor for as-built drawings and equipment manuals.

.2509(g)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; July 1, 1992;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2510

Public Swimming Pool Operation Permits

(a) No public swimming pool shall commence or continue operation unless the owner or operator has an operation permit issued by the Department for each public swimming pool. Unless suspended or revoked, the operation permit shall be valid for the period of operation specified in the application but in no event shall it be valid for more than 12 months. For public swimming pools which are constructed or remodeled, plans and specifications shall have been approved by the Department in accordance with Rule .2509. Compliance with the design and construction requirements in Rules .2514 through .2534 and approval of plans and specifications shall not be required for public swimming pools constructed or remodeled prior to May 1, 1993. No public swimming pool shall commence or continue operation after May 1, 2010 unless documentation of compliance with pool drain safety requirements of Rule .2539 of this Section has been submitted to the local health department.

What we inspect

Valid operation permit required to open or continue operating

We check that the pool has a current, valid operating permit.

Must be: The pool must have a valid operating permit issued by the health department before it opens or continues operating.

If it fails: Contact the local health department to apply for or renew the pool's operating permit.

.2510(a)

What we inspect

Operation permit valid for no more than 12 months

We check that the pool's operating permit hasn't expired.

Must be: The operating permit is valid for no more than 12 months and must be renewed after that.

If it fails: Renew the operating permit with the health department before it expires.

.2510(a)

What we inspect

Pools built or remodeled before May 1, 1993 exempt from design/construction rules

We check whether your pool was built or remodeled before May 1, 1993, which exempts it from the current design and construction rules.

Must be: Pools built or remodeled before May 1, 1993 don't have to meet today's design and construction standards, though all other rules still apply.

.2510(a)

What we inspect

Drain-safety compliance documentation required to operate since May 1, 2010

We check that the pool has documentation on file showing it meets drain safety requirements.

Must be: Since May 1, 2010, every pool must have drain safety compliance documentation submitted to the health department to keep operating.

If it fails: Have a licensed pool professional evaluate the drain covers and submit compliance documentation to the health department.

.2510(a)

(b) Equipment replacement shall comply with Rules .2514 through .2534 and shall be approved by the Department prior to installation. However, for existing swimming pools with recirculation systems unable to meet the pool volume turnover rates specified in the rules of this Section, pump replacement shall match the flow capabilities of the system. Repairs do not require prior approval by the Department.

What we inspect

Equipment replacement must comply with design rules and be pre-approved

We check that any replaced equipment meets current design standards and was approved before installation.

Must be: Replacement equipment must meet the pool's design and construction standards and be approved by the health department before it's installed.

.2510(b)

What we inspect

Pump replacement on flow-limited existing systems may match existing flow capability

We check that a replacement pump matches what the pool's existing plumbing can actually handle.

Must be: If the pool's existing pipes can't support today's flow standards, a replacement pump only needs to match the system's existing flow capacity.

.2510(b)

What we inspect

Repairs do not require prior Department approval

We check whether the work done was a simple repair, which doesn't need prior approval, versus a replacement or remodel, which does.

Must be: Simple repairs don't need health department approval beforehand, but equipment replacements and remodels do.

.2510(b)

(c) A separate application for an operation permit must be submitted for each public swimming pool. The owner or operator shall apply annually to the Department for an operator's permit. The application form shall be obtained from the Department and shall include the following information:

What we inspect

Separate annual operation permit application required for each pool

We check that the pool has its own separate, current annual operating permit application on file.

Must be: Each pool needs its own annual permit application listing the owner, operator, address, pool type, construction date, operating dates, and disinfection type.

.2510(c)

(1) the owner's name, address, and phone number;
(2) the operator's name, address, and phone number;
(3) street address of the public swimming pool;
(4) the physical location of the public swimming pool;
(5) type of public swimming pool;
(6) construction date;
(7) proposed operating dates;
(8) type of disinfection; and
(9) signature of owner or designated representative.
History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; January 1, 1996;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2511

Inspections

(a) Each public swimming pool shall be inspected by the Department to determine compliance with the rules of this Section. Where an operation permit is issued prior to inspection of a public swimming pool, an inspection shall be completed within 60 days following issuance of the permit. Pools that open on or after April 1 and close on or before October 31 shall be inspected at least once during the period of operation. All other pools shall be inspected at least twice a year.

What we inspect

Inspection completed within 60 days when permit issued before inspection

We check that the pool received its required inspection within 60 days of the permit being issued.

Must be: If a permit was issued before the pool was inspected, the inspection must happen within 60 days of that permit.

.2511(a)

What we inspect

Seasonal pools inspected at least once during the operating period

We check that a seasonal pool was inspected at least once during its operating season.

Must be: Pools that operate only between April 1 and October 31 must be inspected at least once during that season.

.2511(a)

What we inspect

Year-round pools inspected at least twice a year

We check that a year-round pool was inspected at least twice during the year.

Must be: Pools that operate outside the April-to-October season must be inspected at least twice a year.

.2511(a)

(b) Inspections of public swimming pools shall be conducted by Environmental Health Specialists authorized by the Department to enforce the rules of this Section. Inspections shall be documented on Inspection of Swimming Pool Form DENR 3960. Items on the grade sheet shall be divided into two, four and six-demerit items. Six-demerit items are failures to maintain minimum water quality or safety standards and warrant immediate suspension of an operation permit under G.S. 130A-23(d). Four-demerit items are rule violations which warrant denial of an operation permit or notification of an intent to suspend an operation permit. Two-demerit items are rule violations that do not warrant permit action unless such violation causes an imminent hazard, a failure to meet water quality or safety standard, or a suction hazard. Demerits shall be assessed for each item found not to be in compliance with the rules of this Section. Demerits shall be assessed as follows:

What we inspect

Inspections documented on Form DENR/EHS 3960 with 2/4/6 demerit classification

We check that past inspections were properly documented and any violations were classified correctly.

Must be: Inspections must be recorded on the official state inspection form, with each violation weighted by how serious a safety or water-quality risk it poses.

.2511(b)

(1) Violation of Rule .2535(2) of this Section regarding water clarity shall be assessed six demerits.
(2) Violation of Rule .2531(a)(10), .2531(b)(3), .2535(3), (4), (5), (7), (8), or (9), or .2543(d)(7) or (e)(2) of this Section regarding disinfectant residuals shall be assessed six demerits.
(3) Violation of Rule .2535(1) of this Section regarding pool water pH shall be assessed six demerits.
(4) Violation of Rule .2535(12) of this Section or regarding control of water temperature in heated pools shall be assessed six demerits.
(5) Violation of Rule .2535(10), (11), or (13), .2537(c), or .2540 of this Section regarding pool operator training, water quality records and test kits shall be assessed four demerits.
(6) Violation of Rule .2518(j), .2537(b)(7) or (16), or .2539 of this Section regarding pool drains and suction hazards shall be assessed six demerits.
(7) Violation of Rule .2537(b)(3), (8), (9) or (14) of this Section regarding maintenance of pool walls and floor shall be assessed four demerits.
(8) Violation of Rule .2518(k) or (l), .2531(4), .2532(4)(b) or .2537(b)(14) of this Section regarding water surface skimmers shall be assessed four demerits.
(9) Violation of Rule .2523 or .2537(b)(6) of this Section regarding depth markers and no diving markers shall be assessed four demerits.
(10) Violation of Rule .2515(d) or (f), .2523(e) or .2537(b)(12) of this Section regarding floating safety ropes and contrasting color bands at breakpoints shall be assessed two demerits.
(11) Violation of Rule .2517, .2521, .2527, .2537(b)(10), .2527, or .2542 of this Section regarding diving equipment, slides, ladders, steps, handrails and in-pool exercise equipment shall be assessed two demerits.
(12) Violation of Rule .2518(i) or .2537(b)(8) of this Section regarding inlets and other fittings shall be assessed four demerits.
(13) Violation of Rule .2516(b), .2521(b)(4), .2532(13) or .2537(b)(12) of this Section regarding contrasting color bands on seats or benches shall be assessed four demerits.
(14) Violation of Rule .2532(7) or .2537(b)(11) of this Section regarding spa timers shall be assessed four demerits.
(15) Violation of Rule .2530(a), or (b), or .2537(b)(1) of this Section regarding lifesaving equipment shall be assessed six demerits.
(16) Violation of Rule .2528, .2531(a)(7) or .2537(b)(5) of this Section regarding fences, barriers and gates shall be assessed four demerits.
(17) Violation of Rule .2522 or .2537(b)(2) of this Section regarding decks shall be assessed four demerits.
(18) Violation of Rule .2530(c) of this Section regarding No Lifeguard warning signs shall be assessed four demerits.
(19) Violation of Rule .2530(d) or .2543(d)(13) of this Section regarding pet and glass container signs shall be assessed four demerits.
(20) Violation of Rule .2532(15) through (17), or .2537(b)(13) of this Section regarding caution signs at hot water spas shall be assessed four demerits.
(21) Violation of Rule .2524, or .2537(b)(4) of this Section regarding pool and deck lighting and ventilation shall be assessed four demerits.
(22) Violation of Rule .2530(f) of this Section regarding emergency telephones shall be assessed six demerits.
(23) Violation of Rule .2535(6) of this Section regarding automatic chlorine or bromine feeders shall be assessed four demerits.
(24) Violation of Rule .2518 .2519, .2525, .2531(a)(1) through (3), .2532(1) through (6), or .2543(b), (d)(1) through (6) or (e)(1) of this Section regarding pool filter and circulation systems shall be assessed four demerits.
(25) Violation of Rule .2533, .2534 or .2537(b)(15) of this Section regarding equipment rooms and chemical storage rooms shall be assessed two demerits.
(26) Violation of Rule .2518(d) of this Section regarding identification of valves and pipes shall be assessed two demerits.
(27) Violation of Rule .2513(b) of this Section regarding air gaps for filter backwash shall be assessed two demerits.
(28) Violation of Rule .2526 or .2543(d)(11) of this Section regarding accessible dressing and sanitary facilities shall be assessed two demerits.
(29) Violation of Rule .2526 of this Section regarding maintenance and cleaning of dressing and sanitary facilities and fixtures shall be assessed two demerits.
(30) Violation of Rule .2512 of this Section regarding water supplies shall be assessed two demerits.
(31) Violation of Rule .2513(a) of this Section regarding sewage disposal shall be assessed two demerits.
(32) Violation of Rule .2526(c) of this Section regarding floors in dressing and sanitary facilities shall be assessed two demerits.
(33) Violation of Rule .2526(c), or (d) of this Section regarding hose bibs and floor drains in dressing and sanitary facilities shall be assessed two demerits.
History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; March 1, 2004; January 1, 1996;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2512

Water Supply

(a) The water supply serving the swimming pool and all plumbing fixtures including drinking fountains, lavatories, toilets, and showers, shall meet all requirements in 15A NCAC 18A .1700 or be an approved public water supply in accordance with 15A NCAC 18C. However, the Department may approve the use of water from natural sources, including the use of saline water, for the swimming pool.

What we inspect

Water supply must meet potable water rules or be an approved public supply

We check that the pool's water supply and connected fixtures, like fountains, sinks, toilets, and showers, meet safe drinking-water standards.

Must be: The water supply must meet state potable water rules or come from an approved public water system.

If it fails: Have the water supply tested and, if needed, connect it to an approved public water source.

.2512(a)

(b) The water distribution system serving the swimming pool and auxiliary facilities shall be protected against backflow. Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap (American National Standards Institute A112.1.2-1979), a pipe-applied atmospheric vacuum breaker (ANSI/American Society of Sanitary Engineering No. 1001-1971), a pressure type anti-siphon vacuum breaker (ANSI/ASSE No. 1020-1976), or a reduced-pressure principle backflow preventer (ASSE No. 1013-1979, American Water Works Association No. C506-1978), which are hereby adopted by reference in accordance with G.S. 150B-14(c) or equivalent.

What we inspect

Water distribution system must be protected against backflow

We check that the water filling the pool can't be siphoned back into the drinking water supply.

Must be: Water entering the pool must pass through an approved backflow-prevention device, such as an air gap or vacuum breaker.

If it fails: Install an approved backflow preventer, such as an air gap or vacuum breaker, on the fill line.

.2512(b)

(c) Whenever an over-the-rim spout is used to introduce water into the swimming pool, it shall be shielded so as not to create a hazard. The open end of the spout shall have no sharp edges, shall not protrude more than two inches (5.1 cm) beyond the edge of the pool and shall be at least two pipe diameters above the deck or pool overflow level. The over-the-rim spout shall be located under the diving board or within six inches of a ladder or handrail.

What we inspect

Over-the-rim spout must be shielded with no sharp edges

We check that any over-the-rim fill spout is shielded and has no sharp edges.

Must be: An over-the-rim spout must be shielded so it isn't a hazard, and its open end must have no sharp edges.

If it fails: Add a protective shield or smooth cap over the spout opening.

.2512(c)

What we inspect

Over-the-rim spout must not protrude more than 2 inches beyond pool edge

We measure how far the over-the-rim spout sticks out past the pool's edge.

Must be: The spout must not extend more than 2 inches beyond the edge of the pool.

If it fails: Trim or replace the spout so it extends no more than 2 inches past the pool edge.

.2512(c)

What we inspect

Over-the-rim spout must be at least two pipe diameters above deck/overflow level

We check the clearance between the over-the-rim spout and the deck or water line.

Must be: The spout must sit at least two pipe-widths above the deck or the pool's overflow level.

If it fails: Raise the spout so it clears the deck or overflow level by at least two pipe diameters.

.2512(c)

What we inspect

Over-the-rim spout must be under the diving board or within 6 inches of a ladder/handrail

We check where the over-the-rim spout is positioned relative to the diving board and ladder.

Must be: The spout must be located under the diving board or within 6 inches of a ladder or handrail.

If it fails: Relocate the spout so it sits under the diving board or within 6 inches of a ladder or handrail.

.2512(c)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2513

Sewage Systems and Other Wastewater Disposal

(a) Sewage shall be disposed of in a public sewer system or, in the absence of a public sewer system, by an approved, properly operating sanitary sewage system.

What we inspect

Sewage must be disposed via public sewer or approved sanitary system

We check that the pool facility's sewage is properly disposed of through a public sewer or approved septic system.

Must be: Sewage must go to a public sewer system, or, if none is available, an approved septic system.

.2513(a)

(b) There shall be no direct physical connection between the sewer system and any drain from the swimming pool or circulation system. Overflow from the swimming pool, and discharges from the circulation system, when discharged to the sewer system, storm drain or other approved natural drainage course, shall be discharged through a suitable air gap so as to preclude the possibility of back flow of sewage or other waste water into the swimming pool or the swimming pool piping system. Deck drainage shall be discharged through an indirect drain.

What we inspect

No direct physical connection permitted between sewer system and pool drains

We check that the pool's drains aren't directly connected to the sewer system.

Must be: There must be no direct pipe connection between the sewer system and any pool or circulation drain.

If it fails: Have a licensed plumber disconnect any direct link and route drainage through an approved air gap.

.2513(b)

What we inspect

Pool overflow/circulation discharge to sewer must pass through an air gap

We check that pool overflow and filter discharge water passes through an air gap before reaching the sewer or storm drain.

Must be: Water draining from the pool to a sewer, storm drain, or drainage course must pass through an air gap so sewage can't flow back into the pool.

.2513(b)

What we inspect

Deck drainage must discharge through an indirect drain

We check that water draining off the pool deck goes through an indirect drain rather than a direct connection.

Must be: Deck drainage must be discharged through an indirect drain.

.2513(b)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. April 1, 1999; July 1, 1992;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2514

Materials of Construction

(a) Pools and appurtenances shall be constructed of materials which are inert, non-toxic to man, impervious and permanent, which can withstand design stresses and which can provide a water-tight tank with a smooth and cleanable surface. Use of vinyl liners is prohibited; however, liners no less than 60 mil thick may be used provided the underlying pool shell is of approved construction. If this material is used for repairs, the existing pool shall be remodeled in accordance with this Rule.

What we inspect

Pool materials must be inert, watertight and smooth; vinyl liners prohibited

We check that the pool shell is built from durable, watertight, easy-to-clean material rather than a thin vinyl liner.

Must be: The pool must be built of sturdy, non-toxic, watertight material with a smooth surface; standard vinyl liners aren't allowed.

.2514(a)

What we inspect

Non-vinyl liners must be at least 60 mil thick over an approved shell

We check the thickness of any liner used and confirm it sits over an approved pool shell.

Must be: A liner must be at least 60 mil thick and installed over a properly built pool shell.

If it fails: Replace a thinner liner with one at least 60 mil thick, installed over a sound shell.

.2514(a)

What we inspect

Liner repairs require remodeling the pool under this rule

We check that any liner repair was treated as a full pool remodel under the rules, not a simple patch.

Must be: If liner material is used to repair the pool, the whole pool must be brought up to current remodeling standards.

.2514(a)

(b) Sand or earth bottoms are prohibited in swimming pool construction.

What we inspect

Sand or earth pool bottoms are prohibited

We check that the pool bottom is a solid built surface rather than sand or bare earth.

Must be: The pool bottom must not be sand or earth.

If it fails: Have the pool bottom rebuilt with an approved solid material.

.2514(b)

(c) Pool finish, including bottom and sides, shall be of white or light colored material determined visually to contrast least with a value of gray whiter than 50 percent black on an artists gray scale, or shown by reflectance testing to reflect more than 50 percent of visible light.

What we inspect

Pool finish must be white/light colored, reflecting more than 50% of visible light

We check that the pool's interior finish is light-colored enough to see clearly through the water.

Must be: The pool finish must be white or light-colored, reflecting more than half of visible light.

If it fails: Resurface or repaint the pool interior with a white or light-colored finish.

.2514(c)

(d) Pool surfaces in areas which are intended to provide footing for bathers including steps, ramps, and pool bottoms in areas with water less than three feet deep, shall be designed to provide a slip-resistant surface.

What we inspect

Footing surfaces (steps, ramps, shallow bottoms) must be slip-resistant

We check that steps, ramps, and shallow areas have a slip-resistant surface underfoot.

Must be: Steps, ramps, and the pool floor in water under 3 feet deep must have a slip-resistant surface.

If it fails: Apply a slip-resistant coating or texture to smooth steps, ramps, or shallow areas.

.2514(d)

History Note: Authority G.S. 130A-82;
Eff. May 1, 1991;
Amended Eff. May 1, 2010;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2515

Design Details

(a) Pools shall be designed and constructed to withstand all loadings for both full and empty conditions.

What we inspect

Pools designed to withstand loadings both full and empty

We check that the pool structure is built to handle the stress of being both full and empty.

Must be: The pool must be engineered to safely withstand the loads of being full of water and being empty.

.2515(a)

(b) A hydrostatic relief valve shall be provided for in-ground swimming pools which extend more than two feet below the grade of surrounding land surface unless a gravity drainage system is provided.

What we inspect

Hydrostatic relief valve required for in-ground pools extending more than 2 ft below grade

We check for a hydrostatic relief valve, or equivalent drainage system, on in-ground pools built well below grade.

Must be: In-ground pools that sit more than 2 feet below the surrounding ground must have a hydrostatic relief valve or a gravity drainage system.

If it fails: Have a licensed contractor install a hydrostatic relief valve or gravity drainage system.

.2515(b)

(c) Provisions shall be made for complete, continuous circulation of water through all areas of the swimming pool. Swimming pools shall have a circulation system with approved treatment, disinfection, and filtration equipment as required in the rules of this Section.

What we inspect

Complete continuous circulation required through all pool areas

We check that water circulates fully through every part of the pool, with no dead spots.

Must be: The pool must have a working circulation system that continuously moves water through all areas, with proper filtration and treatment.

.2515(c)

(d) The minimum depth of water in the swimming pool shall be three feet (0.91 m) except where a minimum depth of less than three feet is needed to provide non-swimming areas such as children's activity areas and sun shelves.

What we inspect

Minimum water depth of 3 feet except in designated non-swimming areas

We measure the pool's water depth throughout the swimming areas.

Must be: Water must be at least 3 feet deep, except in designated non-swimming areas like kids' zones and sun shelves.

.2515(d)

(e) The maximum depth at the shallow end of a swimming pool shall be three and a half feet (1.07 m) except for pools used for competitive swimming, diving or other uses which require water deeper than three and a half feet.

What we inspect

Maximum shallow-end depth of 3.5 feet except for competitive/diving uses

We measure the depth at the shallow end of the pool.

Must be: The shallow end must be no more than 3.5 feet deep, unless the pool is used for competitive swimming or diving.

.2515(e)

(f) Connections for safety lines shall be recessed in the walls in a manner which presents no hazard to swimmers.

What we inspect

Safety line wall connections must be recessed and present no hazard

We check that the wall fittings for safety lines are recessed and don't stick out into the pool.

Must be: Safety line connections must be recessed into the pool wall so they don't create a hazard for swimmers.

If it fails: Replace protruding safety line hardware with a recessed fitting.

.2515(f)

(g) Decorative features such as planters, umbrellas, fountains and waterfalls located on pool decks shall comply with the following:
(1) Decorative features shall not occupy more than 20 percent of the pool perimeter;

What we inspect

Deck decorative features limited to 20% of pool perimeter

We check how much of the pool's edge is taken up by decorative features like planters or fountains.

Must be: Decorative deck features must not cover more than 20 percent of the pool's perimeter.

.2515(g)(1)

(2) If located adjacent to a water depth of greater than five feet, decorative features shall not be more than 20 feet wide;

What we inspect

Deck decorative features next to water deeper than 5 ft limited to 20 ft wide

We check the width of any decorative feature next to deep water.

Must be: A decorative feature next to water deeper than 5 feet must be no more than 20 feet wide.

.2515(g)(2)

(3) Decorative features shall not provide handholds or footholds that could encourage climbing above deck level;

What we inspect

Deck decorative features must not offer climbable handholds or footholds

We check that decorative deck features don't offer ledges or grips that invite climbing.

Must be: Decorative features must not provide handholds or footholds that could encourage someone to climb above deck level.

If it fails: Remove or modify ledges, footholds, or handholds on decorative features.

.2515(g)(3)

(4) A walkway shall be provided to permit free access around decorative features and shall be as wide as the lesser of five feet or the deck width required in Rule .2528 of this Section;

What we inspect

Walkway around decorative features must be at least 5 ft wide or the required deck width, whichever is less

We check that there's a clear walkway around decorative deck features.

Must be: A walkway at least 5 feet wide, or the pool's required deck width if narrower, must allow free passage around decorative features.

.2515(g)(4)

(5) Decorative features shall not obstruct the view of any part of the pool from any seating area; and

What we inspect

Deck decorative features must not obstruct view of the pool from seating areas

We check that decorative features don't block the view of the pool from seating areas.

Must be: Decorative features must not block the view of any part of the pool from any seating area.

If it fails: Reposition or trim the decorative feature so the full pool stays visible from seating areas.

.2515(g)(5)

(6) Features with moving water shall be separate from the pool recirculation system.

What we inspect

Moving-water decorative features must be separate from the pool recirculation system

We check that fountains or other moving-water features run on their own separate plumbing, not the pool's filter system.

Must be: Decorative features with moving water must use a water system separate from the pool's circulation system.

.2515(g)(6)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; August 1, 2000; April 1, 1999;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2516

Pool Profile

(a) The vertical walls of a public swimming pool shall not exceed 11 degrees from plumb. Corners formed by intersection of walls and floors shall be coved or radiused. Hopper bottomed pools are prohibited.

What we inspect

Pool vertical walls must not exceed 11 degrees from plumb

We check how steeply the pool walls slope from straight up and down.

Must be: Pool walls must be within 11 degrees of vertical.

.2516(a)

What we inspect

Wall-to-floor corners must be coved or radiused

We check that the corners where the pool walls meet the floor are rounded rather than sharp right angles.

Must be: The corners where walls meet the floor must be coved or rounded, not squared off.

.2516(a)

What we inspect

Hopper-bottomed pools are prohibited

We check that the pool floor doesn't have a hopper-style, funnel-shaped bottom.

Must be: Hopper-bottomed pool designs are not allowed.

.2516(a)

(b) Underwater ledges or protrusions are prohibited; except that underwater stairs, sun shelves, seats and benches may be installed in areas of the pool no more than four feet deep. Underwater benches shall have a maximum seat depth of two feet from the water surface, protrude no more than 18 inches from the wall and be marked by a two inch contrasting color band on the leading edge. Underwater protrusions may provide seating at swim-up bars located in offset areas away from swim lanes. Underwater stairs may adjoin a sun shelf to deeper water provided the depth at the bottom of the stairs is no more than four feet and the stairs meet all provisions of Rule .2521 of this Section.

What we inspect

Underwater ledges/protrusions prohibited except listed features in water 4 ft deep or less

We check for underwater ledges or protrusions and confirm any stairs, shelves, seats, or benches sit only in water 4 feet deep or less.

Must be: Underwater ledges and protrusions aren't allowed, except for stairs, sun shelves, seats, and benches in water no deeper than 4 feet.

If it fails: Remove or relocate any underwater ledge or protrusion in water deeper than 4 feet.

.2516(b)

What we inspect

Underwater bench seat depth limited to 2 ft from the water surface

We measure how far below the surface an underwater bench seat sits.

Must be: An underwater bench seat must be no more than 2 feet below the water surface.

.2516(b)

What we inspect

Underwater bench protrusion limited to 18 inches from the wall

We measure how far an underwater bench sticks out from the pool wall.

Must be: An underwater bench must not protrude more than 18 inches from the wall.

.2516(b)

What we inspect

Underwater bench leading edge marked with a 2-inch contrasting color band

We check that the front edge of any underwater bench is marked with a contrasting color stripe.

Must be: The leading edge of an underwater bench must have a 2-inch contrasting color band so swimmers can see it.

If it fails: Add a 2-inch stripe of contrasting color paint or tape along the bench's leading edge.

.2516(b)

What we inspect

Underwater stairs to a sun shelf must bottom at 4 ft or less and meet Rule .2521

We check that any underwater stairs leading from a sun shelf into deeper water bottom out at a safe depth and are built to the pool's step and ladder standards.

Must be: Underwater stairs leading to deeper water must bottom out at no more than 4 feet deep and meet the pool's standard step and ladder rules.

.2516(b)

(c) The slope of the bottom of any portion of any public swimming pool having a water depth of less than five feet (1.52 m) shall not be more than one foot vertical change in 10 feet (10 cm in one meter) of horizontal distance and the slope shall be uniform.

What we inspect

Bottom slope in water less than 5 ft deep limited to 1 ft vertical per 10 ft horizontal

We check how steeply the pool floor slopes in the shallower areas.

Must be: Where the water is less than 5 feet deep, the floor can't drop more than 1 foot for every 10 feet you walk across it, and the slope must be even.

.2516(c)

(d) In portions of pools with water depths greater than five feet (1.52 m), the slope of the bottom shall not be more than one foot vertical in three feet (33.3 cm in one meter) of horizontal distance.

What we inspect

Bottom slope in water deeper than 5 ft limited to 1 ft vertical per 3 ft horizontal

We check how steeply the pool floor slopes in the deeper areas.

Must be: Where the water is deeper than 5 feet, the floor can't drop more than 1 foot for every 3 feet you walk across it.

.2516(d)

(e) Design of diving areas shall be in accordance with Tables 1A and 1B of Rule .2517 of this Section.

What we inspect

Diving area design must follow Tables 1A and 1B of Rule .2517

We check that the diving area's shape and dimensions follow the standard diving design charts.

Must be: The diving area's length, depth, and layout must match the official diving design tables.

.2516(e)

(f) Fountains installed in public swimming pools shall be approved prior to installation and shall comply with the following:
(1) Fountains shall not be installed in an area with a water depth exceeding 18 inches;

What we inspect

In-pool fountains prohibited where water depth exceeds 18 inches

We check where any decorative fountains are installed in the pool.

Must be: Fountains can't be placed anywhere the water is deeper than 18 inches.

If it fails: Relocate the fountain to a shallower section of the pool.

.2516(f)(1)

(2) Fountains shall be recommended by the manufacturer for use in a public swimming pool;

What we inspect

In-pool fountains must be manufacturer-recommended for public pool use

We check that any installed fountain is rated for pool use.

Must be: The fountain must be a model the manufacturer specifically approves for use in a public pool.

If it fails: Swap the fountain for a pool-rated model.

.2516(f)(2)

(3) Fountains shall be installed in accordance with the manufacturer's instructions;

What we inspect

In-pool fountains must be installed per manufacturer instructions

We check that the fountain was installed the way its manufacturer specifies.

Must be: The fountain must be installed exactly as the manufacturer's instructions describe.

If it fails: Have the fountain reinstalled following the manufacturer's instructions.

.2516(f)(3)

(4) Fountains shall be separate from the pool water recirculation system; and

What we inspect

In-pool fountains must be separate from the pool recirculation system

We check how the fountain's plumbing is connected.

Must be: The fountain must run on its own plumbing, separate from the pool's main filtration and circulation system.

If it fails: Have a pool professional separate the fountain plumbing from the circulation system.

.2516(f)(4)

(5) Fountains shall not release water at a velocity greater than 10 feet per second.

What we inspect

In-pool fountains limited to a 10 ft/s water release velocity

We check how forcefully the fountain releases water.

Must be: The fountain can't shoot water out faster than 10 feet per second.

If it fails: Adjust the fountain's flow rate down to a safe speed.

.2516(f)(5)

History Note: Authority G.S. 130A-82;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; February 1, 2004; January 1, 1996;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2517

Diving Equipment

(a) When diving equipment is installed in a public swimming pool, it shall be located in the diving area of the pool so as to provide the minimum dimensions as shown in Tables 1A and 1B of this Rule and shall conform to the following specifications:

What we inspect

Installed diving equipment must meet the minimum dimensions of Tables 1A and 1B

We check where the diving board or platform sits relative to the pool's diving area.

Must be: Diving equipment must be positioned to meet the minimum clearances shown in the diving design tables.

.2517(a)

What we inspect

Diving equipment must have slip-resistant tread surfaces

We check the walking surfaces of the diving equipment for traction.

Must be: The diving board and any steps to it must have a slip-resistant surface.

If it fails: Add a slip-resistant tread or coating to the board and steps.

.2517(a)(4)

What we inspect

Max board overhang for 12 feet board, 30 in above water: 5 ft

We measure how far a 12-foot diving board mounted 30 inches above the water extends past the pool edge.

Must be: For this size and height of board, the overhang can't be more than 5 feet.

.2517 Table 1A

What we inspect

Min board overhang (Point A) for 12 feet board, 30 in above water: 4 ft

We measure how far this 12-foot diving board extends past the pool edge.

Must be: For this size and height of board, the overhang must be at least 4 feet.

.2517 Table 1A

What we inspect

Minimum D1 water depth for 12 feet board, 30 in above water: 8'0"

We measure the water depth near the wall at the deep end, below this diving board.

Must be: That depth must be at least 8 feet.

.2517 Table 1A

What we inspect

Minimum D2 water depth for 12 feet board, 30 in above water: 9'0"

We measure the water depth at the deepest point of the pool for this board setup.

Must be: That depth must be at least 9 feet.

.2517 Table 1A

What we inspect

Minimum D3 water depth for 12 feet board, 30 in above water: 8'3"

We measure the water depth where the deep end starts sloping up toward the shallow end.

Must be: That depth must be at least 8 feet 3 inches.

.2517 Table 1A

What we inspect

Max board overhang for 16 feet board, 1 meter above water: 6 ft

We measure how far a 16-foot diving board mounted 1 meter above the water extends past the pool edge.

Must be: For this size and height of board, the overhang can't be more than 6 feet.

.2517 Table 1A

What we inspect

Min board overhang (Point A) for 16 feet board, 1 meter above water: 5 ft

We measure how far this 16-foot diving board extends past the pool edge.

Must be: For this size and height of board, the overhang must be at least 5 feet.

.2517 Table 1A

What we inspect

Minimum D1 water depth for 16 feet board, 1 meter above water: 8'6"

We measure the water depth near the wall at the deep end, below this diving board.

Must be: That depth must be at least 8 feet 6 inches.

.2517 Table 1A

What we inspect

Minimum D2 water depth for 16 feet board, 1 meter above water: 10'0"

We measure the water depth at the deepest point of the pool for this board setup.

Must be: That depth must be at least 10 feet.

.2517 Table 1A

What we inspect

Minimum D3 water depth for 16 feet board, 1 meter above water: 8'6"

We measure the water depth where the deep end starts sloping up toward the shallow end.

Must be: That depth must be at least 8 feet 6 inches.

.2517 Table 1A

What we inspect

Max board overhang for 16 feet board, 3 meters above water: 6 ft

We measure how far a 16-foot diving board mounted 3 meters above the water extends past the pool edge.

Must be: For this size and height of board, the overhang can't be more than 6 feet.

.2517 Table 1A

What we inspect

Min board overhang (Point A) for 16 feet board, 3 meters above water: 5 ft

We measure how far this high-dive board extends past the pool edge.

Must be: For this size and height of board, the overhang must be at least 5 feet.

.2517 Table 1A

What we inspect

Minimum D1 water depth for 16 feet board, 3 meters above water: 11'6"

We measure the water depth near the wall at the deep end, below this high-dive board.

Must be: That depth must be at least 11 feet 6 inches.

.2517 Table 1A

What we inspect

Minimum D2 water depth for 16 feet board, 3 meters above water: 12'0"

We measure the water depth at the deepest point of the pool for this board setup.

Must be: That depth must be at least 12 feet.

.2517 Table 1A

What we inspect

Minimum D3 water depth for 16 feet board, 3 meters above water: 11'6"

We measure the water depth where the deep end starts sloping up toward the shallow end.

Must be: That depth must be at least 11 feet 6 inches.

.2517 Table 1A

What we inspect

Minimum pool width for 12 feet diving board: 20 ft

We measure how wide the pool is where the diving board is installed.

Must be: For a 12-foot diving board, the pool must be at least 20 feet wide.

.2517 Table 1B

What we inspect

Minimum separation distance F for 12 feet diving board: 10 ft

We measure the distance from the pool's side wall to the diving board's centerline.

Must be: That distance must be at least 10 feet.

.2517 Table 1B

What we inspect

Minimum separation distance G for 12 feet diving board: 10 ft

We measure the distance between the centerlines of two side-by-side diving boards.

Must be: That distance must be at least 10 feet.

.2517 Table 1B

What we inspect

Minimum pool width for 16 feet (1m board) diving board: 24 ft

We measure how wide the pool is where this 1-meter diving board is installed.

Must be: The pool must be at least 24 feet wide.

.2517 Table 1B

What we inspect

Minimum separation distance F for 16 feet (1m board) diving board: 12 ft

We measure the distance from the pool's side wall to this diving board's centerline.

Must be: That distance must be at least 12 feet.

.2517 Table 1B

What we inspect

Minimum separation distance G for 16 feet (1m board) diving board: 10 ft

We measure the distance between the centerlines of two side-by-side 1-meter diving boards.

Must be: That distance must be at least 10 feet.

.2517 Table 1B

What we inspect

Minimum pool width for 16 feet (3m board) diving board: 28 ft

We measure how wide the pool is where this high-dive (3-meter) board is installed.

Must be: The pool must be at least 28 feet wide.

.2517 Table 1B

What we inspect

Minimum separation distance F for 16 feet (3m board) diving board: 14 ft

We measure the distance from the pool's side wall to this high-dive board's centerline.

Must be: That distance must be at least 14 feet.

.2517 Table 1B

What we inspect

Minimum separation distance G for 16 feet (3m board) diving board: 12 ft

We measure the distance between the centerlines of two side-by-side high-dive boards.

Must be: That distance must be at least 12 feet.

.2517 Table 1B

What we inspect

L1 for a 12 ft board / 30 in diving board: 3'

We measure the radius of the curved cove where the deep-end wall meets the pool floor, for pools with a 12-foot, 30-inch diving board.

Must be: That curve must be at least 3 feet, per the state's diving-board depth chart.

.2517 Table 1B

What we inspect

L2 for a 12 ft board / 30 in diving board: 7'

We measure the distance from the center of that deep-end curve to the pool's deepest point, for a 12-foot, 30-inch diving board.

Must be: That distance must be at least 7 feet.

.2517 Table 1B

What we inspect

L3 for a 12 ft board / 30 in diving board: 10'3"

We measure how far the deepest part of the pool extends before the floor starts sloping up toward the shallow end, for a 12-foot, 30-inch diving board.

Must be: That distance must be at least 10 feet 3 inches.

.2517 Table 1B

What we inspect

L4 for a 12 ft board / 30 in diving board: 9'9"

We measure the length of the sloped transition zone between the deep and shallow ends, for a 12-foot, 30-inch diving board.

Must be: That transition length must be at least 9 feet 9 inches.

.2517 Table 1B

What we inspect

L5 for a 12 ft board / 30 in diving board: 30'

We check that the total diving-well length adds up correctly for a 12-foot, 30-inch diving board.

Must be: The combined length of the deep-end curve, deep floor, transition, and shallow area must equal at least 30 feet.

.2517 Table 1B

What we inspect

L6 for a 12 ft board / 30 in diving board: 4'

We measure the length of the shallow area at the end of the diving well, for a 12-foot, 30-inch diving board.

Must be: That shallow-area length must be at least 4 feet.

.2517 Table 1B

What we inspect

L1 for a 16 ft board / 1 m diving board: 5'

We measure the radius of the curved cove where the deep-end wall meets the pool floor, for pools with a 16-foot, 1-meter diving board.

Must be: That curve must be at least 5 feet.

.2517 Table 1B

What we inspect

L2 for a 16 ft board / 1 m diving board: 5'

We measure the distance from the center of that deep-end curve to the pool's deepest point, for a 16-foot, 1-meter diving board.

Must be: That distance must be at least 5 feet.

.2517 Table 1B

What we inspect

L3 for a 16 ft board / 1 m diving board: 11'6"

We measure how far the deepest part of the pool extends before the floor starts sloping up toward the shallow end, for a 16-foot, 1-meter diving board.

Must be: That distance must be at least 11 feet 6 inches.

.2517 Table 1B

What we inspect

L4 for a 16 ft board / 1 m diving board: 10'6"

We measure the length of the sloped transition zone between the deep and shallow ends, for a 16-foot, 1-meter diving board.

Must be: That transition length must be at least 10 feet 6 inches.

.2517 Table 1B

What we inspect

L5 for a 16 ft board / 1 m diving board: 32'

We check that the total diving-well length adds up correctly for a 16-foot, 1-meter diving board.

Must be: The combined length of the deep-end curve, deep floor, transition, and shallow area must equal at least 32 feet.

.2517 Table 1B

What we inspect

L6 for a 16 ft board / 1 m diving board: 4'

We measure the length of the shallow area at the end of the diving well, for a 16-foot, 1-meter diving board.

Must be: That shallow-area length must be at least 4 feet.

.2517 Table 1B

What we inspect

L1 for a 16 ft board / 3 m diving board: 5'

We measure the radius of the curved cove where the deep-end wall meets the pool floor, for pools with a 16-foot, 3-meter diving board.

Must be: That curve must be at least 5 feet.

.2517 Table 1B

What we inspect

L2 for a 16 ft board / 3 m diving board: 5'

We measure the distance from the center of that deep-end curve to the pool's deepest point, for a 16-foot, 3-meter diving board.

Must be: That distance must be at least 5 feet.

.2517 Table 1B

What we inspect

L3 for a 16 ft board / 3 m diving board: 7'6"

We measure how far the deepest part of the pool extends before the floor starts sloping up toward the shallow end, for a 16-foot, 3-meter diving board.

Must be: That distance must be at least 7 feet 6 inches.

.2517 Table 1B

What we inspect

L4 for a 16 ft board / 3 m diving board: 19'6"

We measure the length of the sloped transition zone between the deep and shallow ends, for a 16-foot, 3-meter diving board.

Must be: That transition length must be at least 19 feet 6 inches.

.2517 Table 1B

What we inspect

L5 for a 16 ft board / 3 m diving board: 37'

We check that the total length of the diving area in front of a 16-foot board set 3 meters above the water adds up correctly.

Must be: For this board size and height, the combined length of the diving area must be at least 37 feet.

If it fails: This is a design-stage check, so if the total comes up short, have your pool builder re-verify the layout before construction continues.

.2517 Table 1B

What we inspect

L6 for a 16 ft board / 3 m diving board: 3'

We measure the length of the shallow area next to a 16-foot diving board set 3 meters above the water.

Must be: For this board size and height, the shallow area must be at least 3 feet long.

.2517 Table 1B

(1) Diving equipment shall be designed for swimming pool use and shall be installed in accordance with the manufacturer's recommendations.

What we inspect

Diving equipment designed for pool use and installed per manufacturer recommendations

We check that the diving board is a pool-rated product, installed the way the maker recommends.

Must be: The diving board must be designed for pool use and installed according to the manufacturer's instructions.

.2517(a)(1)

(2) Installation instructions and specifications shall be provided with each unit.

What we inspect

Installation instructions and specifications provided with each diving unit

We check that the diving board's installation paperwork and specs are on hand.

Must be: Installation instructions and specifications for the diving equipment must be available.

If it fails: Request a copy of the installation instructions and specs from the manufacturer or installer.

.2517(a)(2)

(3) A label shall be permanently affixed to the diving equipment and shall include:

What we inspect

Diving equipment must carry a permanent label with manufacturer, length, type, and fulcrum data

We check the diving board for a permanent identification label.

Must be: The diving board must have a permanent label showing the manufacturer's name and address, the board's length, its type, and (if applicable) its fulcrum settings.

If it fails: Have the manufacturer or installer affix a proper ID label to the board.

.2517(a)(3)

(A) manufacturer's name and address;
(B) board length;

What we inspect

Diving supports, platforms, and steps must safely carry maximum anticipated loads

We check the diving board's supports, platform, and steps for sturdiness.

Must be: The supports, platform, and steps must be strong enough to safely hold the heaviest expected use.

If it fails: Have a professional inspect and reinforce the diving structure.

.2517(b)

What we inspect

Diving equipment steps must be of corrosion-resistant design

We check what material the diving board's steps are made of.

Must be: The steps must be made of a rust- and corrosion-resistant material.

If it fails: Replace the steps with a corrosion-resistant material like stainless steel or fiberglass.

.2517(b)

What we inspect

Handrails required at steps/ladders leading to diving boards 1 meter or higher

We check for handrails on any steps or ladder leading up to a diving board.

Must be: If the diving board is 1 meter (about 3.3 feet) or higher above the water, its access steps or ladder must have handrails.

If it fails: Install handrails along the steps or ladder to the board.

.2517(b)

(C) type of diving board;

What we inspect

13 ft clear vertical distance required above a diving board

We check the open space directly above the diving board.

Must be: There must be at least 13 feet of completely open space straight above the board, measured from the center of its front tip.

If it fails: Remove or relocate any overhead obstruction (trees, structures, wires) above the board.

.2517(c)

What we inspect

Diving clearance envelope must extend at least 8 ft behind Point A

We check the open space behind the point where the diving board overhangs the water.

Must be: The clear area must extend at least 8 feet behind that point, with nothing blocking it.

.2517(c)

What we inspect

Diving clearance envelope must extend at least 8 ft to each side of Point A

We check the open space to each side of the diving board's overhang point.

Must be: The clear area must extend at least 8 feet to each side of that point.

.2517(c)

What we inspect

Diving clearance envelope must extend at least 16 ft ahead of Point A

We check the open space out in front of the diving board's overhang point.

Must be: The clear area must extend at least 16 feet ahead of that point, out over the water.

.2517(c)

(D) fulcrum setting specifications if applicable.

What we inspect

Diving facilities over 3 meters or platform diving must meet FINA guidelines

We check that any high-dive setup over 3 meters, or any diving platform, meets international diving safety standards.

Must be: Diving facilities taller than 3 meters, or platform diving setups, must meet the FINA international diving guidelines.

.2517(d)

(4) Diving equipment shall have slip-resistant tread surfaces.
(b) Supports, platforms, and steps for diving equipment shall be of sufficient strength to carry safely the maximum anticipated loads. Steps shall be of corrosion-resistant design. Handrails shall be provided at all steps and ladders leading to diving boards that are one meter or more above the water.
(c) There shall be a completely unobstructed clear vertical distance of 13 feet above any diving board measured from the center of the front end of the board. This area shall extend horizontally at least eight feet behind, eight feet to each side, and 16 feet ahead of Point A in Table 1A. Table 1A Maximum Board Length Maximum Board Height Above Water Board Overhang (Pt. A) Minimum Water Depths Max Min D1 D2 D3 12 feet 30 in 5 feet 4 feet 8'0" 9'0" 8'3" 16 feet 1 meter 6 feet 5 feet 8'6" 10'0" 8'6" 16 feet 3 meters 6 feet 5 feet 11'6" 12'0" 11'6" KEY TO ABBREVIATIONS: Pt A is the point on the water line of the pool directly beneath the end of the diving board. D1 is the depth of the water measured from the water line to the floor at the beginning of the radius connecting the end wall with the floor at the deep end of the pool. D2 is the depth of the water at the deepest point in the pool. D3 is the depth of the water at the point where the deep area of the pool meets the transition to the shallow area of the pool. Table 1B Maximum Board Length Horizontal Distances L1 L2 L3 L4 L5 L6 Minimum Pool Width Minimum Separation Distances F G 12 feet 3' 7' 10'3" 9'9" 30' 4' 20' 10' 10' 16 feet 5' 5' 11'6" 10'6" 32' 4' 24' 12' 10' 16 feet 5' 5' 7'6" 19'6" 37' 3' 28' 14' 12' KEY TO ABBREVIATIONS: L1 is the radius of the curve connecting the side wall to the floor at the deep end of the pool. L2 is the distance between the center of the radius connecting the end wall to the floor at the deep end of the pool and the deepest point in the pool. L3 is the distance between the deepest point in the pool and the beginning of the transition to the shallow area of the pool. L4 is the length of the transition zone. L5 is the total of L1 + L2 + L3 + L4. L6 is the length of the shallow area of the pool. F is the distance between the side wall of the pool and the centerline of the diving board. G is the distance between the center lines of two adjacent diving boards.
(d) Public pools with diving facilities in excess of three meters in height, or pools designed for platform diving, shall meet the Federation Internationale De Nation Amateur (FINA) guidelines that are incorporated by reference in accordance with G.S. 130B-21.6 including any subsequent amendments or additions.
(e) Starting platforms used for racing starts during competition shall be secured from use when the pool is open for general use by removal; covering; or signage and active supervision. Minimum water depth for starting platforms shall be measured at a distance of 3 feet, 3 ½ inches (1.0 meter) to 16 feet, 5 inches (5.0 meters) from the end wall. Height of starting platforms shall not exceed the following:

What we inspect

Racing starting platforms must be secured from use during general swimming

We check whether racing starting blocks are made unusable during regular open swim time.

Must be: Starting blocks must be removed, covered, or clearly signed and actively supervised whenever the pool isn't being used for competition.

If it fails: Remove or cover the starting blocks, or post signage and station a lifeguard, during open swim.

.2517(e)

(1) In pools with water depth less than 3 feet, 6 inches (1.07 meters) at the starting end, raised starting platforms shall be prohibited.

What we inspect

Raised starting platforms prohibited where starting-end depth is less than 3'6"

We check the water depth at the end of the pool where starting blocks would be used.

Must be: If that water is shallower than 3 feet 6 inches, raised starting blocks aren't allowed at all.

If it fails: Remove any raised starting blocks from this end of the pool.

.2517(e)(1)

(2) In pools with water depth 3 feet, 6 inches (1.07 meters) to less than 4 feet (1.22 meters) at the starting end, starting platforms shall be no more than 18 inches (0.46 meter) above the water surface.

What we inspect

Starting platforms limited to 18 in above water where starting-end depth is 3'6" to under 4 ft

We measure how high the starting blocks sit above the water at this depth range.

Must be: Where the water is between 3 feet 6 inches and 4 feet deep, starting blocks can be no higher than 18 inches above the water.

If it fails: Lower or replace the starting blocks to meet the height limit.

.2517(e)(2)

(3) In pools with a water depth of 4 feet (1.22 meters) or greater at the starting end, starting platforms shall be no more than 30 inches (0.762 meter) above the surface of the water. Starting platforms shall be constructed to be easily removed from the deck when the swimming pool is used for other than competitive purposes.

What we inspect

Starting platforms limited to 30 in above water where starting-end depth is 4 ft or more

We measure how high the starting blocks sit above the water at this depth.

Must be: Where the water is 4 feet deep or more, starting blocks can be no higher than 30 inches above the water.

If it fails: Lower or replace the starting blocks to meet the height limit.

.2517(e)(3)

What we inspect

Starting platforms must be easily removable from the deck for non-competitive use

We check whether the starting blocks can be quickly taken off the deck.

Must be: Starting blocks must be built so they're easy to remove from the deck when the pool isn't being used for competition.

.2517(e)(3)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. February 1, 2004; April 1, 1999; January 1, 1996;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2518

Circulation System

(a) Public swimming pools shall be equipped with a water circulation system.

What we inspect

Water circulation system required

We check that the pool has a working water circulation system.

Must be: Every pool must have a functioning circulation system.

If it fails: Have a pool professional install a circulation system if one is missing.

15A NCAC 18A .2518(a)

(b) The water circulation system shall circulate and filter the entire volume of public swimming pool water four times or more in 24 hours. The water circulation system shall be operated 24 hours per day at no more than the maximum velocity allowed under Paragraph (d) of this Rule during the operating dates set out in the permit.

What we inspect

Turnover rate at least 4 times per 24 hours

We check how often the pool's filter system cycles the entire volume of water.

Must be: The system must filter and circulate the entire pool's water at least 4 times every 24 hours.

If it fails: Upsize the pump or filter, or increase run time, to reach the required turnover rate.

15A NCAC 18A .2518(b)

What we inspect

Circulation system operated continuously within velocity limit

We check whether the circulation system runs around the clock at a safe flow speed.

Must be: The pump must run 24 hours a day during the pool's open season, without exceeding the maximum allowed water speed.

15A NCAC 18A .2518(b)

(c) The water circulation system piping shall be designed and installed so that the flow from the public swimming pool shall be from main drains or the surface overflow system. If both main drains and a surface overflow system are used, the water circulation system piping shall be designed such that the flow of water from the public swimming pool is simultaneous from the surface overflow system and the main drains. Skimmer piping constructed after May 1, 2010 shall be sized to handle 100 percent of the flow rate determined by the Registered Design Professional in the pool design. Perimeter overflow system piping constructed after May 1, 2010 shall be sized to handle 100 percent of the flow rate determined by the Registered Design Professional in the pool design. Main drain piping constructed after May 1, 2010 shall be sized to handle 100 percent of the flow rate determined by the Registered Design Professional in the pool design.

What we inspect

Circulation piping fed from main drains and/or surface overflow

We check how the circulation piping pulls water from the pool.

Must be: Water must be drawn from the main drains, the surface skimmers/overflow, or both at the same time if both are present.

15A NCAC 18A .2518(c)

What we inspect

Skimmer piping sized to 100% of RDP flow rate (post-2010)

We check whether the skimmer plumbing is large enough for the pool's design flow rate.

Must be: For pools built after May 1, 2010, skimmer piping must be sized to handle the full flow rate the pool was designed for.

15A NCAC 18A .2518(c)

What we inspect

Perimeter overflow piping sized to 100% of RDP flow rate (post-2010)

We check whether the perimeter overflow (gutter) plumbing is large enough for the pool's design flow rate.

Must be: For pools built after May 1, 2010, perimeter overflow piping must be sized to handle the full flow rate the pool was designed for.

15A NCAC 18A .2518(c)

What we inspect

Main drain piping sized to 100% of RDP flow rate (post-2010)

We check whether the main drain plumbing is large enough for the pool's design flow rate.

Must be: For pools built after May 1, 2010, main drain piping must be sized to handle the full flow rate the pool was designed for.

15A NCAC 18A .2518(c)

(d) Piping shall be designed to carry water at a maximum velocity not to exceed six feet per second for suction piping and not to exceed 10 feet per second for discharge piping, except for copper pipe where the velocity shall not exceed eight feet per second for discharge piping. Piping shall comply with NSF/ANSI Standard 14 Plastics Piping System Components and Related Materials, incorporated by reference, including any subsequent amendments or editions, and available at http://webstore.ansi.org/ at a cost of one hundred sixty-five dollars ($165.00), and be free of visible water leaks. Public swimming pools constructed after the effective date of this Rule shall use plastic pipe made of a minimum of Schedule 40 PVC. Flexible pipe shall not be used, except that flexible PVC hoses that meet the requirements of NSF/ANSI/CAN Standard 50 Equipment and Chemicals for Swimming Pools, Spas, Hot Tubs, and Other Recreational Water Facilities, incorporated by reference, including any subsequent amendments or editions, and available at http://webstore.ansi.org/ at a cost of five hundred eighty dollars ($580.00)(hereinafter referred to as "NSF Standard 50"), may be used when affixed to spa shells and rigid pipes do not provide the necessary angles to connect water circulation system components. Exposed pipes and valves shall be identified by a color code with a legend or labels.

What we inspect

Suction piping velocity capped at 6 ft/s

We check how fast water moves through the suction (intake) plumbing.

Must be: Water in the suction piping can't move faster than 6 feet per second.

15A NCAC 18A .2518(d)

What we inspect

Discharge piping velocity capped at 10 ft/s

We check how fast water moves through the discharge (return) plumbing.

Must be: Water in the discharge piping can't move faster than 10 feet per second.

15A NCAC 18A .2518(d)

What we inspect

Copper discharge piping velocity capped at 8 ft/s

We check the flow speed of water through any copper discharge pipes.

Must be: Water flowing through copper discharge pipes must move no faster than 8 feet per second.

If it fails: If flow is too fast, a plumber can install larger pipe or adjust pump flow to slow it down.

15A NCAC 18A .2518(d)

What we inspect

Piping complies with NSF/ANSI 14 and is free of visible leaks

We check that your pool's plumbing is made of certified plastic piping and inspect it for any visible leaks.

Must be: All piping must meet NSF/ANSI Standard 14 for pool piping materials and show no visible leaks.

If it fails: Have a pool plumber repair or replace any leaking sections and swap out non-certified pipe.

15A NCAC 18A .2518(d)

What we inspect

New construction piping is minimum Schedule 40 PVC plastic pipe

We check the type and rating of the plastic pipe used in your pool's plumbing.

Must be: Pools built after November 1, 2024 must use plastic pipe rated at least Schedule 40 PVC.

15A NCAC 18A .2518(d)

What we inspect

Flexible pipe prohibited except listed flexible PVC hose at spa shells

We check whether any flexible hose is used in the plumbing instead of rigid pipe.

Must be: Rigid pipe is required throughout, except a certified flexible PVC hose may connect to a spa shell where rigid pipe can't make the needed angle.

If it fails: Replace any non-approved flexible tubing with rigid pipe or a certified flexible hose.

15A NCAC 18A .2518(d)

What we inspect

Exposed pipes and valves identified by color code with legend or labels

We check that exposed pipes and valves are marked so their purpose is easy to identify.

Must be: Visible pipes and valves must be color-coded with a legend, or clearly labeled.

If it fails: Add color-coded tape or paint with a posted legend, or attach labels to each pipe and valve.

15A NCAC 18A .2518(d)

(e) The water circulation system shall have a strainer with a basket to prevent hair, lint, and other debris from reaching the pump. The owner of the public swimming pool shall keep a spare strainer basket onsite at the public swimming pool. Strainers shall be designed for use in pools with openings not more than ¼ inch (6.4 mm) in size that provide a free flow area at least four times the cross-section area of the pump suction line and are accessible for daily cleaning.

What we inspect

Strainer basket required ahead of pump

We check that a strainer basket is installed ahead of the pump.

Must be: The system must have a strainer basket that catches hair, lint, and debris before it reaches the pump.

If it fails: Install a strainer basket ahead of the pump if one is missing.

15A NCAC 18A .2518(e)

What we inspect

Spare strainer basket kept onsite

We check whether a backup strainer basket is kept on site.

Must be: You must keep at least one spare strainer basket on the property.

If it fails: Buy and keep an extra strainer basket that matches your pump's strainer housing.

15A NCAC 18A .2518(e)

What we inspect

Strainer openings, free flow area, and access specifications

We check the strainer's opening size, flow capacity, and how easy it is to reach for cleaning.

Must be: Strainer openings must be no larger than 1/4 inch, provide flow area at least four times the pump suction line's cross-section, and be reachable for daily cleaning.

If it fails: Replace an undersized or hard-to-reach strainer with one that meets these specs.

15A NCAC 18A .2518(e)

(f) A swimming pool shall have a vacuum cleaning system to remove debris and foreign material that settles to the bottom of the swimming pool. Integral vacuum ports shall be located on the pool wall at least six inches and no greater than 18 inches below the water level. Skimmer vacuums may be used when connected to two or fewer skimmers that are isolated from the remaining water circulation system piping. Integral vacuum cleaning systems shall have valves and protective caps. Integral vacuum ports constructed after May 1, 2010 shall have self-closing caps designed to be opened with a tool. Portable vacuum equipment may be used to meet the requirements of this Rule.

What we inspect

Vacuum cleaning system required

We check that you have a way to vacuum debris off the pool floor.

Must be: The pool must have a vacuum system, which can be a built-in system or portable vacuum equipment.

15A NCAC 18A .2518(f)

What we inspect

Integral vacuum ports located 6-18 inches below water level

We measure how far below the water surface the built-in vacuum ports are located.

Must be: Built-in vacuum ports must sit between 6 and 18 inches below the water level.

15A NCAC 18A .2518(f)

What we inspect

Skimmer vacuums limited to two isolated skimmers

We check how many skimmers are connected for use with a skimmer vacuum.

Must be: A skimmer vacuum may only draw from two or fewer skimmers, and those skimmers must be isolated from the rest of the circulation piping.

15A NCAC 18A .2518(f)

What we inspect

Integral vacuum systems have valves and protective caps

We check that built-in vacuum ports have their valves and protective caps in place.

Must be: Built-in vacuum systems must have functioning valves and protective caps on each port.

If it fails: Replace any missing valves or caps on the vacuum ports.

15A NCAC 18A .2518(f)

What we inspect

Post-2010 integral vacuum ports have tool-opened self-closing caps

We check the caps on built-in vacuum ports installed since May 2010.

Must be: These vacuum port caps must self-close and only open with a tool, not by hand.

If it fails: Swap a hand-openable cap for a self-closing, tool-only cap.

15A NCAC 18A .2518(f)

(g) A flow meter, reading in gallons per minute, shall be installed in accordance with the manufacturer's instructions. The flow meter shall measure flows between the minimum circulation turnover rate required in Paragraph (b) of this Rule and the maximum velocity permitted under Paragraph (d) of this Rule and shall be accurate within 10 percent of true flow.

What we inspect

Flow meter installed and accurate within 10% of true flow

We check that a flow meter is installed and reads within the correct accuracy range.

Must be: A gallons-per-minute flow meter must be installed per the manufacturer's instructions and read within 10 percent of true flow.

If it fails: Recalibrate or replace a flow meter that's reading inaccurately.

15A NCAC 18A .2518(g)

(h) A public swimming pool shall have a pump or pumps with capacity to recirculate the public swimming pool water four times or more in 24 hours. The pump or pumps shall not need to be primed, shall be self-priming, or shall utilize an automated priming device labeled for use in public pools by the manufacturer. Any single speed pump shall be capable of maintaining required water turnover based on headloss calculations provided by a professional engineer licensed under G.S. Chapter 89C, the measurements of a flow meter installed in accordance with the manufacturer's instructions, or an assumed total dynamic head of 65 feet of water. Any variable speed pump or single speed pump utilizing a variable frequency drive shall be capable of maintaining water turnover as required by Paragraph (b) of this Rule based on a pump performance curve provided by the manufacturer and shall maintain the flow rate determined by the Registered Designed Professional in the pool design. Pumps shall be certified by NSF International as meeting NSF Standard 50 or verified by an independent third-party testing laboratory to meet provisions of NSF Standard 50 applicable to pumps. Verification conducted by an independent third-party testing laboratory shall include testing and quality control inspections.

What we inspect

Pump capacity to recirculate pool volume 4 times per 24 hours

We check that your pump can turn over the full pool volume enough times per day.

Must be: The pump or pumps must circulate the entire pool's water at least 4 times every 24 hours.

If it fails: Upgrade to a higher-capacity pump if the current one can't keep up.

15A NCAC 18A .2518(h)

What we inspect

Pump is self-priming, non-priming, or has a labeled automated priming device

We check how the pump primes itself before running.

Must be: The pump must not require manual priming — it must be self-priming, need no priming, or use an automated priming device approved for public pools.

If it fails: Replace a pump that needs manual priming with a self-priming model or an approved auto-primer.

15A NCAC 18A .2518(h)

What we inspect

Single-speed pump turnover shown via headloss calc, meter, or 65 ft TDH

We check the documentation showing your single-speed pump can meet the required turnover rate.

Must be: Turnover must be confirmed by an engineer's headloss calculation, a flow meter reading, or by assuming 65 feet of total dynamic head.

15A NCAC 18A .2518(h)

What we inspect

Variable speed/VFD pump turnover shown via manufacturer performance curve

We check the documentation showing your variable-speed pump meets the required flow rate.

Must be: Turnover must be confirmed using the pump manufacturer's performance curve, and the pump must maintain the flow rate set in the pool's design.

15A NCAC 18A .2518(h)

What we inspect

Pumps certified or verified to NSF/ANSI Standard 50

We check that your pump is certified for use in a pool.

Must be: The pump must be NSF-certified, or independently lab-verified, to meet NSF Standard 50.

If it fails: Replace an uncertified pump with an NSF Standard 50 certified model.

15A NCAC 18A .2518(h)

(i) All public swimming pools shall be equipped with water return inlets. The water return inlets shall meet the following requirements:
(1) The water return inlets shall produce a uniform circulation of water and maintain a uniform disinfectant residual throughout the pool;

What we inspect

Return inlets produce uniform circulation and disinfectant residual

We check how well water and sanitizer are distributed around the pool from the return inlets.

Must be: Return inlets must circulate water evenly and keep sanitizer levels consistent throughout the pool.

If it fails: Adjust or reposition return inlets to eliminate dead spots in circulation.

15A NCAC 18A .2518(i)(1)

(2) There shall be at least one water return inlet per 20 gallons per minute of return water flow with a minimum of four water return inlets for any swimming pool;

What we inspect

At least one return inlet per 20 GPM, minimum four per pool

We count the number of return inlets compared to your pump's flow rate.

Must be: There must be at least one return inlet for every 20 gallons per minute of flow, and at least 4 inlets total.

If it fails: Add return inlets to meet the ratio and the 4-inlet minimum.

15A NCAC 18A .2518(i)(2)

(3) Water return inlets shall be located so that no part of the swimming pool is more than 25 feet of horizontal distance from the nearest water return inlet; and

What we inspect

No point in pool more than 25 ft from a return inlet

We measure the distance from every part of the pool to the nearest return inlet.

Must be: No spot in the pool can be more than 25 feet from a return inlet.

If it fails: Add return inlets to close any gap greater than 25 feet.

15A NCAC 18A .2518(i)(3)

(4) Water return inlets shall be replaced when damaged or missing.

What we inspect

Damaged or missing return inlets replaced

We check the condition of each return inlet.

Must be: Any return inlet that is damaged or missing must be replaced.

15A NCAC 18A .2518(i)(4)

(j) Drains shall not be required in public swimming pools when an alternate method to drain the pool is provided. Public swimming pools constructed without main drains shall be designed with water return inlets positioned to return water uniformly throughout the public swimming pool. Public swimming pools constructed with main drains shall have the main drains installed in accordance with the manufacturer's instructions and meet the following requirements:

What we inspect

Alternate drain method permitted in lieu of drains

We check how the pool is drained when it doesn't have main drains.

Must be: Main drains aren't required as long as another approved method exists for draining the pool.

15A NCAC 18A .2518(j)

What we inspect

Pools without main drains use return inlets for uniform drainage flow

We check the placement of return inlets in pools that don't have main drains.

Must be: Without main drains, return inlets must be positioned to return water evenly throughout the pool.

15A NCAC 18A .2518(j)

What we inspect

Main drains installed per manufacturer's instructions

We check that any main drains were installed the way the manufacturer specifies.

Must be: Main drains must be installed following the manufacturer's instructions.

If it fails: Have a licensed installer correct any main drain installation that deviates from spec.

15A NCAC 18A .2518(j)

(1) Public swimming pools with main drains shall be provided with one or more unblockable drains or two or more main drains located at the deepest section of the pool on a horizontal plane and connected by symmetrical "T" piping. Except when unblockable drains are used, piping between main drains shall be sized and configured such that blocking any one drain will not result in flow through the remaining drain covers exceeding the manufacturer's flow rating while handling 100 percent of the pump's maximum flow. Dual main drains connected by "T" piping shall be spaced not more than 30 feet apart, and not more than 15 feet away from the side walls of the pool, Main Drains shall be separated by at least three feet measured from the centers of the drain covers or installed with one main drain on a horizontal plane and one main drain on a vertical plane. Main drains with two or more outlets with a common suction line shall not be equipped with valves that allow the outlets to be isolated. Public swimming pools constructed prior to May 1, 2010 with a single drain or multiple drains closer than three feet apart shall protect against bather entrapment with an unblockable drain cover or a secondary method of preventing bather entrapment in accordance with Rule .2539 of this Section.

What we inspect

Main drains: unblockable drain(s) or dual drains on symmetrical T piping

We check the number and configuration of your pool's main drains.

Must be: Pools with main drains need either one or more unblockable drains, or two or more drains at the deepest point connected by symmetrical T-shaped piping.

15A NCAC 18A .2518(j)(1)

What we inspect

T-piping sized so a single blocked drain does not overload remaining covers

We check whether the piping between main drains is sized to handle one drain becoming blocked.

Must be: If one drain gets blocked, the piping must still keep flow through the remaining drain covers within the manufacturer's rated limit, even at full pump flow.

If it fails: Have an engineer or pool contractor resize the drain piping if it can't safely handle a single blockage.

15A NCAC 18A .2518(j)(1)

What we inspect

Dual main drains spaced no more than 30 ft apart

We measure the distance between paired main drains.

Must be: Dual main drains connected by T-piping must be no more than 30 feet apart.

15A NCAC 18A .2518(j)(1)

What we inspect

Dual main drains no more than 15 ft from pool side walls

We measure how far the main drains sit from the pool's side walls.

Must be: Dual main drains connected by T-piping must be no more than 15 feet from the nearest side wall.

15A NCAC 18A .2518(j)(1)

What we inspect

Main drains separated by at least 3 ft, or on horizontal/vertical planes

We check the spacing and orientation between multiple main drains.

Must be: Main drains must be at least 3 feet apart center-to-center, or one must be on the floor and the other on a wall.

15A NCAC 18A .2518(j)(1)

What we inspect

Common-suction-line main drains with 2+ outlets cannot have isolating valves

We check whether drains sharing a suction line can be shut off individually.

Must be: Main drains that share a common suction line with two or more outlets must not have valves that let you isolate one outlet.

If it fails: Remove or disable any valve that allows isolating a single outlet on a shared drain line.

15A NCAC 18A .2518(j)(1)

What we inspect

Pre-2010 close/single drains need unblockable cover or secondary method

We check older pools with a single drain, or drains closer than 3 feet apart, for entrapment protection.

Must be: Pools built before May 2010 with a single drain or closely spaced drains must have an unblockable drain cover or another approved anti-entrapment safeguard.

If it fails: Install an unblockable drain cover or an approved secondary entrapment-prevention device.

15A NCAC 18A .2518(j)(1)

(2) Drain outlets shall comply with the ANSI/APSP/ICC-16 2017 American National Standard for Suction Outlet Fittings Assemblies (SOFA) for Use in Pools, Spas, and Hot Tubs, which is hereby incorporated by reference, including any subsequent amendments or editions, and available at https://webstore.ansi.org/ at a cost of one hundred sixty-five dollars ($165.00).

What we inspect

Drain outlets comply with ANSI/APSP/ICC-16 2017 (SOFA)

We check that your drain covers meet the current national safety standard for suction outlet fittings.

Must be: Drain covers must comply with the ANSI/APSP/ICC-16 2017 suction outlet fitting standard.

If it fails: Replace outdated or uncertified drain covers with ones rated to this standard.

15A NCAC 18A .2518(j)(2)

(3) Public swimming pool drains shall comply with ANSI/PHTA/ICC-7 2020 American National Standard for Suction Entrapment Avoidance in Swimming Pools, Wading Pools, Spas, Hot Tubs and Catch Basins, which is hereby incorporated by reference, including any subsequent amendments or editions, and available at https://webstore.ansi.org at a cost of one hundred and sixty-five dollars ($165.00)(hereinafter referred to as "ANSI/PHTA/ICC-7").

What we inspect

Pool drains comply with ANSI/PHTA/ICC-7 2020

We check that the drain system meets the national standard for preventing suction entrapment.

Must be: Pool drains must comply with the ANSI/PHTA/ICC-7 2020 suction entrapment avoidance standard.

15A NCAC 18A .2518(j)(3)

(k) Public swimming pools shall have a surface overflow system that is an integral part of the water circulation system and that consists of a built-in-place perimeter overflow system, a pre-fabricated perimeter overflow system, or recessed automatic surface skimmers. The surface overflow system shall comply with the following:

What we inspect

Surface overflow system required (perimeter overflow or recessed skimmers)

We check what type of surface skimming system your pool uses.

Must be: The pool must have a surface overflow system — either a built-in or pre-fabricated perimeter overflow, or recessed automatic skimmers.

15A NCAC 18A .2518(k)

What we inspect

Recessed automatic surface skimmers designed and constructed per NSF Standard 50

We check that recessed skimmers are built to the correct certified standard.

Must be: Recessed automatic skimmers must be designed and built to meet NSF Standard 50 for pool circulation components.

If it fails: Replace any skimmer that isn't NSF Standard 50 rated.

15A NCAC 18A .2518(k)(2)

What we inspect

Recessed skimmer flow rate at least 20 GPM and within NSF certification

We check the flow rate passing through each recessed skimmer.

Must be: Each skimmer must handle at least 20 gallons per minute, but no more than its NSF-certified maximum flow.

15A NCAC 18A .2518(k)(2)(A)

What we inspect

At least one recessed skimmer per 400 sq ft of water surface

We count the number of recessed skimmers relative to your pool's surface area.

Must be: There must be at least one recessed skimmer for every 400 square feet of water surface, or part thereof.

If it fails: Add skimmers to meet the required ratio for your pool's surface area.

15A NCAC 18A .2518(k)(2)(B)

What we inspect

Multiple recessed skimmers located to skim entire pool surface

We check the placement of recessed skimmers when more than one is required.

Must be: Multiple skimmers must be positioned so the entire pool surface gets skimmed.

If it fails: Reposition skimmers to eliminate any surface area they can't reach.

15A NCAC 18A .2518(k)(2)(C)

What we inspect

Recessed skimmers must not protrude into the pool water

We check whether skimmer housings stick out into the swimming area.

Must be: Skimmers must sit flush and not protrude into the pool water.

If it fails: Have a pool contractor reset a protruding skimmer flush with the wall.

15A NCAC 18A .2518(k)(2)(D)

What we inspect

Recessed-skimmer-only pools: water level no more than 9 in below deck

We measure the water level relative to the pool deck in pools using only recessed skimmers.

Must be: Water level must stay within 9 inches of the top of the deck.

If it fails: Add water or adjust the auto-fill or level control if the water sits too low.

15A NCAC 18A .2518(k)(2)(D)

(1) When a public swimming pool uses a built-in-place perimeter overflow system or a pre-fabricated perimeter overflow system, the public swimming pool may be designed with the operating water level, perimeter overflow system, and deck at the same elevation. The perimeter overflow system shall:

What we inspect

Perimeter overflow system handles 100% of RDP flow rate without flooding

We check whether the perimeter overflow troughs can handle the pool's full design flow without overflowing.

Must be: The perimeter overflow system must handle 100 percent of the pool's designed flow rate without flooding the troughs.

If it fails: Have a pool professional adjust or resize the overflow system to handle full flow.

15A NCAC 18A .2518(k)(1)(A)

What we inspect

Perimeter overflow system handles 1 gal/sq ft water surge

We check whether the overflow system can absorb a sudden surge of water, like from bathers entering the pool.

Must be: The system must handle a surge equal to at least 1 gallon per square foot of pool surface, which a surge tank can help provide.

If it fails: Add or upsize a surge tank if the system can't absorb this much water.

15A NCAC 18A .2518(k)(1)(B)

What we inspect

Water level maintained above overflow rim except brief surge-tank transfers

We check the water level relative to the overflow rim.

Must be: Water must stay above the overflow rim at all times, except for surge-tank transfers lasting no more than 20 minutes.

If it fails: Add water or adjust the surge tank controls if the level regularly drops below the rim.

15A NCAC 18A .2518(k)(1)(C)

What we inspect

Overflow rim dimensional tolerance not to exceed 1/4 inch

We measure how level the overflow rim is around the pool.

Must be: The overflow rim can vary by no more than 1/4 inch between its highest and lowest points.

If it fails: Have a mason relevel the rim if it's out of tolerance.

15A NCAC 18A .2518(k)(1)(D)

What we inspect

Perimeter overflow system provides continuous automatic skimming

We check that the overflow system continuously skims the surface even when the water is still.

Must be: The overflow system must skim the surface automatically and continuously, not just when the water is disturbed.

15A NCAC 18A .2518(k)(1)(E)

What we inspect

Overflow troughs continuous around perimeter (except steps/ladders/stairs)

We check whether the overflow trough runs continuously around the pool's edge.

Must be: The trough must be continuous around the whole perimeter, except where interrupted by steps, ladders, or stairs, or where recessed skimmers are used instead.

15A NCAC 18A .2518(k)(1)(F)

What we inspect

Hand-hold provided on exposed overflow trough surfaces

We check that swimmers have something to grab onto at the overflow trough edge.

Must be: The exposed edge of the overflow trough must include a hand-hold.

If it fails: Install a hand-hold along the exposed trough edge if one is missing.

15A NCAC 18A .2518(k)(1)(G)

(A) Be capable of handling 100 percent of the flow rate determined by the Registered Design Professional in the pool design without flooding the overflow troughs;
(B) Be capable of handling a water surge equal to one gallon per square foot, or 41 liters per square meter, of swimming pool water surface area. A surge tank may be used to meet this requirement;
(C) Be capable of maintaining the water level of the swimming pool above the level of the overflow rim of the perimeter overflow system, except for time intervals of no more than 20 minutes when water is transferred between a surge tank and the public swimming pool;
(D) Be constructed so the dimensional tolerance of the overflow rim shall not exceed ¼ inch (6.4 mm) as measured between the highest point and the lowest point of the overflow rim;
(E) Be capable of providing continuous and automatic skimming of the water during quiescence;
(F) Be constructed so that the overflow troughs are installed continuously around the perimeter of the public swimming pool, except at steps, recessed ladders, and stairs, or except when used in combination with recessed automatic surface skimmers; and
(G) Provide a hand-hold on the exposed surfaces of the overflow trough.
(2) When a public swimming pool uses recessed automatic surface skimmers, the recessed automatic surface skimmers shall be designed and constructed in accordance with NSF Standard 50 requirements for water circulation system components for swimming pools, spas, or hot tubs and be installed as follows:
(A) The rate of water flowing through any one recessed automatic surface skimmer shall be no less than 20 gallons per minute and no more than the maximum flow the skimmer is certified to handle under NSF Standard 50;
(B) There shall be at least one recessed automatic surface skimmer for each 400 square feet of water surface area of the swimming pool or fraction thereof;
(C) When two or more recessed automatic surface skimmers are required, they shall be located to enable skimming of the entire swimming pool water surface;
(D) Skimmers shall not protrude into the water of the public swimming pool. Pools using recessed automatic surface skimmers without a perimeter overflow system shall be installed so that the operating water level of the pool is no more than nine inches below the level of the finished deck.
(l) Where flooded suction on the pump is not possible to prevent cavitation and loss of prime, skimmers shall have a device or other protection to prevent air entrainment in the suction line. Skimmer equalizer lines shall be in compliance with ANSI/PHTA/ICC-7 or disabled. Skimmer equalizer lines shall be disabled by plugging the line under the skimmer basket and where the equalizer pipe exits the pool shell.

What we inspect

Air-entrainment protection when flooded suction not possible

We check for air-entrainment protection on skimmers when the pump can't stay flooded.

Must be: If the pump can't maintain flooded suction, skimmers need a device to keep air out of the suction line.

If it fails: Install an anti-air-entrainment device, such as a check valve or weighted flapper, on the skimmer line.

15A NCAC 18A .2518(l)

What we inspect

Skimmer equalizer lines must comply with ANSI/PHTA/ICC-7 or be disabled

We check the skimmer's equalizer line for compliance or confirm it has been properly disabled.

Must be: Equalizer lines must meet the ANSI/PHTA/ICC-7 entrapment standard, or be plugged both under the skimmer basket and where the pipe exits the pool shell.

If it fails: Have a licensed pool professional plug the equalizer line at both points if it isn't code-compliant.

15A NCAC 18A .2518(l)

(m) Nothing in this Section shall preclude the use of a surface overflow system that combines both a perimeter overflow system and a recessed automatic surface skimmer or skimmers that meet the requirements of this Rule.
History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; February 1, 2004; April 1, 1999; January 1, 1996; July 1, 1992;
Readopted Eff. November 1, 2024.
.2519

Filters

(a) All swimming pools shall be equipped with a filtration system for the purpose of clarifying the swimming pool water; said filtration system shall be an integral part of the circulation system and shall consist of one or more units of sand type filters, of diatomaceous earth type filters, or of cartridge type filters.

What we inspect

Filtration system required, integral to circulation system

We check that your pool has a working filtration system built into the circulation.

Must be: The pool must have a sand, diatomaceous earth (DE), or cartridge filter as part of the circulation system.

15A NCAC 18A .2519(a)

(b) All filter units shall be designed and constructed in accordance with Section 5 of the National Sanitation Foundation's Standard number 50 which is hereby adopted by reference in accordance with G.S. 150B-14(c), or equivalent.

What we inspect

Filter units designed and constructed per NSF Standard 50 Section 5

We check that your filter is a certified, code-compliant model.

Must be: Filter units must be built to meet Section 5 of NSF Standard 50, or an equivalent standard.

If it fails: Replace a non-compliant filter with an NSF Standard 50 certified unit.

15A NCAC 18A .2519(b)

(c) When a sand type filter is installed on a swimming pool, it may be either a gravity or a pressure sand type filter, and it may be either a standard-rate sand type filter which shall be designed for filtration rates not in excess of three gallons per minute per square foot (122 L per minute per square meter) of sand bed area, or a high-rate sand type filter which shall be designed for filtration rates not in excess of 15 gallons per minute per square foot (612 L per minute per square meter) of sand bed area or the flow rate indicated for commercial pools in the most recent NSF listing.

What we inspect

Standard-rate sand filter maximum rate 3 gpm/sq ft

We check the flow rate your sand filter is rated for and running at.

Must be: A standard-rate sand filter must run at no more than 3 gallons per minute per square foot of sand bed.

If it fails: Reduce pump flow or upsize the filter if it's running above this rate.

15A NCAC 18A .2519(c)

What we inspect

High-rate sand filter maximum rate 15 gpm/sq ft (or NSF-listed commercial rate)

We check the flow rate your high-rate sand filter is rated for and running at.

Must be: A high-rate sand filter must run at no more than 15 gallons per minute per square foot of sand bed, or the manufacturer's NSF-listed commercial rate.

15A NCAC 18A .2519(c)

(d) When a sand type filter is installed on a swimming pool, it shall be designed and installed such that it may be backwashed at a rate recommended by the manufacturer or, in the absence of manufacturer's recommendations, at a rate not less than 15 gallons per minute per square foot (612 L per minute per square meter) of filter bed area. The backwash water shall be discharged to waste. A sight glass or other means for viewing the clarity of the backwash water shall be provided.

What we inspect

Sand filter backwash rate at least 15 gpm/sq ft absent manufacturer spec

We check the backwash rate used to clean your sand filter.

Must be: Backwashing must follow the manufacturer's recommended rate, or at least 15 gallons per minute per square foot if none is specified.

If it fails: Adjust the backwash valve or pump settings to reach the required rate.

15A NCAC 18A .2519(d)

What we inspect

Sand filter backwash water discharged to waste

We check where the backwash water from your sand filter goes.

Must be: Backwash water must be sent to waste, not returned to the pool.

If it fails: Redirect the backwash line to a proper waste drain if it currently returns to the pool.

15A NCAC 18A .2519(d)

What we inspect

Sight glass or other means provided to view backwash clarity

We check whether you can see the clarity of the water during backwashing.

Must be: A sight glass or similar viewing method must be provided so you can watch the backwash water's clarity.

If it fails: Install a sight glass in the backwash line if one is missing.

15A NCAC 18A .2519(d)

(e) If the sand type filter is designed to be operated in conjunction with a coagulant, a chemical feeder shall be provided for adding the coagulant ahead of the filters.

What we inspect

Coagulant feeder required ahead of filters when coagulant is used

We check whether a coagulant feeder is installed if your filter uses a coagulant.

Must be: If the sand filter uses a coagulant, a chemical feeder must add it before the water reaches the filter.

If it fails: Install a chemical feeder ahead of the filter if coagulant is being used without one.

15A NCAC 18A .2519(e)

(f) When a diatomaceous earth type filter is installed on a swimming pool, it may be either a pressure or vacuum type and it may be designed to operate either with or without continuous body feed. Diatomaceous earth filters which operate with continuous body feed shall be designed for filtration rates not in excess of 2.5 gallons per minute per square foot (102 L per minute per square meter) of filter area; and diatomaceous earth filters which operate without continuous body feed shall be designed for filtration rates not in excess of two gallons per minute per square foot (82 L per minute per square meter) of filter area.

What we inspect

DE filter with continuous body feed: maximum rate 2.5 gpm/sq ft

We check the flow rate on your diatomaceous earth (DE) filter with continuous body feed.

Must be: A DE filter using continuous body feed must run at no more than 2.5 gallons per minute per square foot of filter area.

15A NCAC 18A .2519(f)

What we inspect

DE filter without continuous body feed: maximum rate 2 gpm/sq ft

We check the flow rate of your DE (diatomaceous earth) filter when it isn't using continuous body feed.

Must be: Without continuous body feed, the filter's flow rate must be no more than 2 gallons per minute per square foot of filter area.

If it fails: Have a pool professional adjust the pump or filter sizing to bring the flow rate down to spec.

15A NCAC 18A .2519(f)

(g) When a diatomaceous earth type filter is installed on a swimming pool, it shall be designed and installed with provisions for cleaning by one or more of the following methods:

What we inspect

DE filter provided with an approved cleaning method

We confirm your DE filter has a way to be cleaned, such as backwashing, air-bump-assist, spray wash, or agitation.

Must be: The filter must include at least one built-in cleaning method — backwashing, air-bump-assist backwashing, spray washing, or agitation.

If it fails: Have a pool professional install a backwash valve or other approved cleaning method for the filter.

15A NCAC 18A .2519(g)

(1) backwashing at two gallons per minute per square foot minimum;
(2) air-bump-assist backwashing;
(3) spray wash, (either mechanical or manual); or
(4) agitation.
(h) The water used in cleaning a diatomaceous earth type filter shall be discharged to waste, or in a manner approved by the Department.

What we inspect

DE filter cleaning water discharged to waste or Department-approved manner

We check where the wastewater from cleaning your DE filter goes.

Must be: Filter cleaning water must be discharged to an approved waste location, not just dumped anywhere.

If it fails: Reroute the filter's backwash discharge line to a sewer, drywell, or other health-department-approved outlet.

15A NCAC 18A .2519(h)

(i) When a cartridge type filter is installed on a swimming pool, it shall be designed for filtration rates not in excess of 0.375 gallons per minute per square foot (15 L per minute per square meter) of effective filtration area.

What we inspect

Cartridge filter maximum rate 0.375 gpm/sq ft

We check the flow rate of your cartridge filter.

Must be: The cartridge filter's flow rate must be no more than 0.375 gallons per minute per square foot of filtration area.

If it fails: Have a pool professional install a larger cartridge filter or reduce pump flow to meet the rate limit.

15A NCAC 18A .2519(i)

(j) When a cartridge type filter is installed on a swimming pool, it shall be designed and installed with provisions being provided for cleaning or replacement as recommended by the manufacturer. Two sets of filter cartridges shall be provided to facilitate the cleaning and drying of one set while the filter is operating.

What we inspect

Cartridge filter cleaning/replacement per manufacturer recommendation

We check that your cartridge filter can be cleaned or swapped out as the manufacturer instructs.

Must be: The filter must allow for cartridge cleaning or replacement following the manufacturer's recommendations.

15A NCAC 18A .2519(j)

What we inspect

Two sets of filter cartridges provided to allow cleaning while operating

We check whether you have a spare set of filter cartridges on hand.

Must be: A second set of cartridges must be available so one set can be cleaned and dried while the other is in use.

If it fails: Purchase a second set of cartridges matching your filter model.

15A NCAC 18A .2519(j)

(k) All filters on swimming pools shall be designed and installed so as to provide easy accessibility for cleaning, operating, maintaining, and servicing. All filter tanks shall be so positioned as to provide adequate circulation of air beneath and around all sides, when necessary, to reduce corrosion and to facilitate cleaning. Whenever filter tanks are installed in the ground (i.e. buried), provisions shall be made so that the tanks are protected against corrosion and are installed in accordance with the recommendations of the manufacturer.

What we inspect

Filters accessible for cleaning, operating, maintaining, and servicing

We check that your filter is easy to reach for cleaning, operating, and servicing.

Must be: The filter must be positioned with clear access on all sides and enough air circulation around it to prevent corrosion.

If it fails: Clear obstructions around the filter or relocate it to a more accessible spot.

15A NCAC 18A .2519(k)

What we inspect

Buried filter tanks protected against corrosion per manufacturer

We check whether your filter tank is buried in the ground and, if so, how it's protected.

Must be: A buried filter tank must be protected against corrosion and installed exactly as the manufacturer specifies.

If it fails: Have a pool professional add manufacturer-approved corrosion protection or reinstall the tank per spec.

15A NCAC 18A .2519(k)

(l) Filters on swimming pools shall be equipped with an approved type pressure gauge or gauges.

What we inspect

Filters equipped with a pressure gauge

We check that your filter has a working pressure gauge.

Must be: The filter must be equipped with an approved pressure gauge.

If it fails: Install or replace the filter pressure gauge with an approved model.

15A NCAC 18A .2519(l)

(m) Filters on swimming pools shall be designed and installed with all the necessary valves and piping which may be needed to drain the filters completely.

What we inspect

Filters equipped with valves and piping to drain completely

We check that your filter can be fully drained for maintenance.

Must be: The filter must have the valves and piping needed to drain it completely.

If it fails: Have a pool professional add a drain valve and piping so the filter can be fully emptied.

15A NCAC 18A .2519(m)

(n) All pressure filters on swimming pools shall be designed and installed with an air-relief valve or valves which shall be located at or near the high point of the filters.

What we inspect

Pressure filters equipped with an air-relief valve near the high point

We check that your pressure filter has an air-relief valve near its highest point.

Must be: An air-relief valve must be installed at or near the top of the filter tank.

If it fails: Have a pool professional install an air-relief valve near the filter's high point.

15A NCAC 18A .2519(n)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. January 1, 1996;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2520

Chemical Feeders

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Repealed Eff. July 1, 1992.
.2521

Ladders, Recessed Steps, and Stairs

(a) If the vertical distance from the bottom of the swimming pool to the deck is over two feet (0.61 m), recessed steps, stairs, or ladders shall be provided in the shallow area of all swimming pools. Recessed steps or ladders shall be provided at the deep portion of all pools; and, if the swimming pool is over 30 feet (9.14 m) wide, such recessed steps or ladders shall be installed on each side near the deep end. A stairway, ladder or set of recessed steps shall be provided every 75 feet along the shallow area perimeter. Where stairs are provided in the shallow area of the pool, one ladder may be deleted in the shallow area for each stairway provided.

What we inspect

Steps/ladder required in shallow area when depth to deck exceeds 2 ft

We check whether the shallow end has steps, stairs, or a ladder for entry and exit.

Must be: If the pool bottom is more than 2 feet below the deck, recessed steps, stairs, or a ladder must be provided in the shallow area.

If it fails: Install recessed steps or a ladder in the shallow end.

15A NCAC 18A .2521(a)

What we inspect

Recessed steps or ladders required at deep end of pool

We check whether the deep end has steps or a ladder for entry and exit.

Must be: Recessed steps or a ladder must be provided at the deep end of the pool.

If it fails: Install recessed steps or a ladder at the deep end.

15A NCAC 18A .2521(a)

What we inspect

Pools over 30 ft wide need deep-end egress on each side

We check whether a wide pool has exit access on both sides near the deep end.

Must be: If the pool is wider than 30 feet, recessed steps or ladders must be installed on each side near the deep end.

If it fails: Add a second set of recessed steps or a ladder on the opposite side near the deep end.

15A NCAC 18A .2521(a)

What we inspect

Stairway, ladder or steps required every 75 ft of shallow-area perimeter

We check the spacing of exit points around the shallow end of the pool.

Must be: A stairway, ladder, or set of recessed steps must be located at least every 75 feet along the shallow-area perimeter.

If it fails: Add an additional stairway or ladder so no stretch of shallow perimeter exceeds 75 feet without one.

15A NCAC 18A .2521(a)

What we inspect

One shallow-area ladder may be omitted per stairway provided

We check how the required exit points in the shallow area are counted when stairs are present.

Must be: One shallow-area ladder may be skipped for each stairway that's already provided.

15A NCAC 18A .2521(a)

(b) Pool Stairs - The design and construction of pool ladders and stairs shall conform to the following:

What we inspect

Stair tread leading edge marked with contrasting band at least 2 in wide

We check that the edge of each stair tread is marked with a contrasting color.

Must be: The leading edge of every stair tread must have a contrasting color stripe at least 2 inches wide, visible from above.

If it fails: Add a contrasting-color safety stripe or tile band along the edge of each tread.

15A NCAC 18A .2521(b)(4)

What we inspect

Ladders corrosion-resistant, slip-resistant, rigid, with handhold

We check the condition and construction of your pool ladders.

Must be: Ladders must resist corrosion, have slip-resistant treads, offer a solid handhold, and be mounted rigidly with no wobble.

If it fails: Replace a corroded or wobbly ladder, or resecure it so it no longer moves.

15A NCAC 18A .2521(b)(5)

What we inspect

Ladder-to-wall clearance between 3 and 6 inches

We measure the gap between the ladder and the pool wall.

Must be: The clearance between the ladder and the pool wall must be between 3 and 6 inches.

If it fails: Have a pool professional reposition the ladder so the wall clearance falls within the required range.

15A NCAC 18A .2521(b)(5)

What we inspect

Step holes designed to be cleanable and drain into the pool

We check that any built-in step holes are easy to clean and drain properly.

Must be: Step holes must be designed so they can be cleaned easily and drain back into the pool rather than collecting dirt.

15A NCAC 18A .2521(b)(5)

What we inspect

Step holes minimum tread depth 5 inches

We measure the depth of the step holes built into the pool wall.

Must be: Step hole treads must be at least 5 inches deep.

15A NCAC 18A .2521(b)(5)

What we inspect

Step holes minimum width 14 inches

We measure the width of the step holes built into the pool wall.

Must be: Step holes must be at least 14 inches wide.

15A NCAC 18A .2521(b)(5)

What we inspect

Handrail required at each side of step holes or in-pool ladders

We check that step holes or in-pool ladders have handrails on both sides.

Must be: A handrail must be present on each side of any step holes or ladder built into the pool.

If it fails: Install a handrail on the missing side of the step holes or ladder.

15A NCAC 18A .2521(b)(6)

(1) Stair treads shall have a minimum unobstructed horizontal depth of 10 inches, a maximum horizontal depth of 36 inches, and a minimum unobstructed surface area of 240 square inches.

What we inspect

Stair tread depth between 10 and 36 inches

We measure the depth of the stair treads in your pool.

Must be: Stair treads must be between 10 and 36 inches deep, front to back.

If it fails: Have a pool professional rebuild the stairs so each tread falls within the required depth range.

15A NCAC 18A .2521(b)(1)

What we inspect

Stair tread minimum unobstructed surface area 240 sq in

We measure the open, usable surface area of each stair tread.

Must be: Each stair tread must have at least 240 square inches of unobstructed standing surface.

If it fails: Have a pool professional widen or reshape the treads to meet the minimum surface area.

15A NCAC 18A .2521(b)(1)

(2) Risers at the centerline of the treads shall have a maximum height of 12 inches and shall be within one inch of a uniform height with the bottom riser height allowed to vary plus or minus two inches from the uniform riser height.

What we inspect

Stair riser height maximum 12 inches at centerline

We measure the height of each stair riser at its centerline.

Must be: Stair risers must be no taller than 12 inches, measured at the centerline of the treads.

If it fails: Have a pool professional rebuild the stairs with shorter, code-compliant risers.

15A NCAC 18A .2521(b)(2)

What we inspect

Stair risers uniform within 1 inch (bottom riser may vary +/- 2 inches)

We check that the stair risers are consistent in height from step to step.

Must be: Riser heights must be within 1 inch of each other, except the bottom riser, which can vary by up to 2 inches.

If it fails: Have a pool professional adjust the risers so their heights are consistent.

15A NCAC 18A .2521(b)(2)

(3) Each set of stairs shall be provided with at least one handrail to serve all treads and risers. For stairs wider than 20 feet, additional handrails shall be provided and spaced no more than 10 feet from adjacent handrails or stair ends.

What we inspect

Each stair set has at least one handrail

We check that each set of pool stairs has at least one handrail.

Must be: Every staircase must have at least one handrail running the full length of the treads and risers.

If it fails: Install a handrail along the stairs.

15A NCAC 18A .2521(b)(3)

What we inspect

Stairs wider than 20 ft need handrails spaced no more than 10 ft apart

We check the spacing of handrails on wide staircases.

Must be: Stairs wider than 20 feet need extra handrails spaced no more than 10 feet apart.

If it fails: Add additional handrails so no gap along the stairs exceeds 10 feet.

15A NCAC 18A .2521(b)(3)

What we inspect

Removable handrails cannot be removed without tools

We check whether removable handrails can be taken out by hand.

Must be: A removable handrail must require tools to remove — it can't just lift out or unscrew by hand.

If it fails: Install a handrail base that locks and requires a tool to remove.

15A NCAC 18A .2521(b)(3)(A)

What we inspect

Handrail leading edge within 18 inches of bottom riser

We check how close the handrail's edge is to the bottom stair or pool entry.

Must be: The leading edge of the handrail must be within 18 inches of the bottom step, measured horizontally.

If it fails: Reposition or extend the handrail so its leading edge falls within 18 inches of the bottom step.

15A NCAC 18A .2521(b)(3)(B)

What we inspect

Handrail outside diameter between 1 and 1.9 inches

We measure the diameter of the handrail.

Must be: The handrail must be between 1 inch and 1.9 inches thick.

If it fails: Replace the handrail with one sized within the required diameter range.

15A NCAC 18A .2521(b)(3)(C)

(A) Handrails, if removable, shall be installed in such a way than they cannot be removed without the use of tools.
(B) The leading edge of handrails facilitating stairs and pool entry/exit shall be no more than 18 inches horizontally from the vertical plane of the bottom riser.
(C) The outside diameter of handrails shall be between one inch and one and nine-tenths inches.
(4) The leading edge of stair treads shall be marked with a contrasting color band or line at least two inches (5 cm) wide visible from above the stairs. Use of contrasting color tiles installed in the stair tread is acceptable provided the tiles are spaced no more than one inch (2.5 cm) from the edge of the tread or from adjacent tiles.
(5) Swimming pool ladders shall be corrosion-resistant and shall be equipped with slip-resistant treads. All ladders shall be designed to provide a handhold and shall be installed rigidly. There shall be a clearance of not more than six inches (15.3 cm), nor less than three inches (7.6 cm), between any ladder and the swimming pool wall. If the steps are inserted in the walls or if step holes are provided, they shall be of such design that they may be cleaned easily and shall be arranged to drain into the swimming pool to prevent the accumulation of dirt thereon. Step holes shall have a minimum tread of five inches (12.7 cm) and a minimum width of 14 inches (35.6 cm).
(6) When step holes or ladders are provided within the swimming pool, there shall be a handrail at each side.
History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; January 1, 1996;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2522

Decks

(a) Outdoor swimming pools shall have a continuous deck extending completely around the swimming pool. The width of the deck or walkway shall provide at least six feet of clear walking space at all points. If the swimming area of the pool is 1600 square feet or larger, at least eight feet of clear walking space is required.

What we inspect

Outdoor pool: continuous deck, minimum 6 ft clear walking space

We measure the walking space on the deck surrounding your outdoor pool.

Must be: An outdoor pool must have a continuous deck all the way around, with at least 6 feet of clear walking space everywhere.

If it fails: Have a pool professional widen the deck or clear obstructions to reach the 6-foot minimum.

15A NCAC 18A .2522(a)

What we inspect

Outdoor pool with 1600+ sq ft water surface: minimum 8 ft deck width

We check whether a larger outdoor pool has extra-wide deck space.

Must be: If the pool's water surface is 1,600 square feet or more, the deck needs at least 8 feet of clear walking space.

If it fails: Widen the deck to meet the 8-foot minimum required for larger pools.

15A NCAC 18A .2522(a)

(b) Indoor swimming pools shall have a continuous deck or walkway extending completely around the swimming pool. The width of the deck shall provide at least five feet of clear walking space at all points. Structures covering swimming pools, including temporary domes, shall be constructed to maintain a vertical clearance of at least seven feet from all parts of the required clear walk space.

What we inspect

Indoor pool: continuous deck, minimum 5 ft clear walking space

We measure the walking space on the deck surrounding your indoor pool.

Must be: An indoor pool must have a continuous deck all the way around, with at least 5 feet of clear walking space everywhere.

If it fails: Widen the deck or clear obstructions to reach the 5-foot minimum.

15A NCAC 18A .2522(b)

What we inspect

Domes/covers over indoor pool need 7 ft vertical clearance

We measure the headroom under any dome or cover over an indoor pool.

Must be: Any structure covering the pool, including a temporary dome, must leave at least 7 feet of vertical clearance above the walkway.

If it fails: Raise or reconfigure the cover structure to restore the required 7-foot clearance.

15A NCAC 18A .2522(b)

(c) Wading pools shall have a continuous deck extending completely around the wading pool. The width of the deck or walkway shall provide at least four feet of clear walking space at all points.

What we inspect

Wading pool: continuous deck, minimum 4 ft clear walking space

We measure the walking space on the deck surrounding the wading pool.

Must be: A wading pool must have a continuous deck all the way around, with at least 4 feet of clear walking space everywhere.

If it fails: Widen the deck or remove obstructions to reach the 4-foot minimum.

15A NCAC 18A .2522(c)

(d) Spas shall have a continuous deck extending at least one-half way around the spa. The width of the deck or walkway shall provide at least four feet of clear walking space at all points.

What we inspect

Spa: deck at least half way around, minimum 4 ft clear walking space

We check the deck around your spa for coverage and clear width.

Must be: A spa needs a deck covering at least half its perimeter, with at least 4 feet of clear walking space wherever the deck exists.

If it fails: Extend the deck or clear obstructions to meet the coverage and width requirements.

15A NCAC 18A .2522(d)

(e) There shall be at least five feet of clear walking space around any diving board, handrail, slide or other permanent structure installed on a swimming pool deck.

What we inspect

Minimum 5 ft clear deck space around fixed deck structures

We check the clearance around fixed deck features like diving boards, slides, and handrails.

Must be: There must be at least 5 feet of clear walking space around any diving board, slide, handrail, or other permanent deck structure.

If it fails: Relocate furniture or obstructions to restore 5 feet of clearance around the fixed structure.

15A NCAC 18A .2522(e)

(f) All deck areas and walkways shall be sloped at a grade of one-fourth inch to one-half inch per foot to a deck drain or sheet drain to deck edge. Deck drains shall not be connected to the circulation system in any manner.

What we inspect

Deck slope between 1/4 and 1/2 inch per foot to drain

We check the slope of the deck and walkways around the pool.

Must be: The deck must slope between a quarter inch and a half inch per foot so water drains away properly.

If it fails: If the deck is too flat or too steep, a contractor may need to regrade or repour sections to fix the slope.

15A NCAC 18A .2522(f)

What we inspect

Deck drains shall not connect to the pool circulation system

We check whether the deck drains are connected to the pool's circulation system.

Must be: Deck drains must be completely separate from the pool's circulation (filter/pump) system.

If it fails: If they're connected, have a pool contractor disconnect the deck drain line from the circulation system.

15A NCAC 18A .2522(f)

(g) All decks and walkways shall have a slip-resistant, impervious surface.

What we inspect

Decks and walkways must have a slip-resistant, impervious surface

We check the surface material of the decks and walkways.

Must be: Decks and walkways must have a slip-resistant surface that doesn't absorb water.

15A NCAC 18A .2522(g)

(h) Sufficient hose bibs shall be provided to allow all areas of the deck to be reached with a 100 foot hose.

What we inspect

Hose bibs sufficient to reach all deck areas with a 100 ft hose

We check the placement of hose bibs (outdoor spigots) around the deck.

Must be: Hose bibs must be placed so every part of the deck can be reached with a 100-foot hose.

If it fails: Add another hose bib if any deck area is out of reach.

15A NCAC 18A .2522(h)

(i) Special purpose pools such as waterslides and wave pools may vary from the minimum deck area requirements to the extent necessary to accommodate the special features of the pool.

What we inspect

Special-purpose pools may vary from minimum deck requirements

We note whether your pool is a special-purpose pool, like a waterslide or wave pool, that may need different deck dimensions.

Must be: Special-purpose pools may have smaller deck areas than standard pools if needed to fit their unique features.

15A NCAC 18A .2522(i)

(j) Structures necessary to provide access to a public swimming pool by persons with disabilities shall be allowed to vary from the provisions of this Section to the extent necessary to accommodate such access. Such structures shall be approved on a case- by-case basis and shall be designed so as to minimize obstruction of the deck.

What we inspect

Accessible-entry structures may vary from deck provisions, approved case-by-case

We check whether any accessibility structures, like ramps or lifts, affect the required deck space.

Must be: Structures that provide pool access for people with disabilities may take up deck space as long as they're approved and kept as unobtrusive as possible.

15A NCAC 18A .2522(j)

(k) For all swimming pools constructed after April 1, 2000 decks shall be continuous with the top of the pool wall or gutter and shall not be more than nine inches above the standard operating water level.

What we inspect

Post-2000 pools: deck continuous with wall/gutter, max 9 in above water level

We check the height of the deck relative to the pool's water level.

Must be: For pools built after April 2000, the deck must be level with the pool's edge and no more than 9 inches above the normal water level.

If it fails: If the deck sits too high, it may need to be built up or the coping adjusted to reduce the gap.

15A NCAC 18A .2522(k)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. February 1, 2004; April 1, 1999; January 1, 1996; July 1, 1992;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2523

Depth Markings and Safety Ropes

(a) On swimming pools the depth of the water shall be marked at or above the water surface on the vertical wall of the swimming pool where possible and on the edge of the deck next to the swimming pool. Where depth markers cannot be placed on the vertical walls at or above the water level, other means shall be used; provided the markings shall be visible to persons in the swimming pool. Depth markers shall be placed at the following locations:

What we inspect

Depth markings placed on wall at water line and on deck edge

We check that the water depth is marked both on the pool wall and on the deck at the pool's edge.

Must be: Depth numbers must appear at or above the waterline on the pool wall, and also on the deck next to the pool.

If it fails: Add depth markers on the wall and/or deck wherever they're missing.

15A NCAC 18A .2523(a)

(1) at the points of maximum and minimum depths;

What we inspect

Depth markers required at key depth-change and end locations

We check that depth markers are placed at the pool's deepest and shallowest points, at the diving area, and at both ends.

Must be: Depth markers must appear at the deepest and shallowest points, where the floor slope changes, in the diving area (if any), and at both ends of the pool.

15A NCAC 18A .2523(a)(1)-(4)

(2) at the transition point where the slope of the bottom changes from the uniform slope of the shallow area;
(3) if the pool is designed for diving, at points to denote the water depths in the diving area; and
(4) at both ends of the pool.
(b) Depth markers shall be so spaced that the distance between adjacent markers is not greater than 25 feet (7.5 m) when measured along the perimeter of the pool.

What we inspect

Depth markers spaced no more than 25 ft apart along the pool perimeter

We check the spacing between depth markers around the pool.

Must be: Depth markers must be no more than 25 feet apart along the pool's edge.

If it fails: Add extra depth markers to close any gaps larger than 25 feet.

15A NCAC 18A .2523(b)

(c) Depth markers shall be in Arabic numerals at least four inches (10 cm) high and of a color contrasting with the background. Depth markings shall indicate the depth of the pool in feet of water and shall include the word "feet" or symbol "ft" to indicate the unit of measurement. Depth markings installed in pool decks shall provide a slip resistant walking surface.

What we inspect

Depth numerals at least 4 inches high, contrasting color, with unit label

We check the size, color, and labeling of the depth number markers.

Must be: Depth numbers must be at least 4 inches tall, in a color that stands out from the background, and labeled with 'feet' or 'ft'.

If it fails: Replace or repaint markers that are too small, blend into the background, or lack a unit label.

15A NCAC 18A .2523(c)

What we inspect

Depth markings set in deck must provide a slip-resistant walking surface

We check the surface texture of any depth markings built into the deck.

Must be: Depth markings set into the deck must still be slip-resistant to walk on.

15A NCAC 18A .2523(c)

(d) "No Diving" markers shall be provided on the pool deck adjacent to all areas of the pool less than five feet deep. "No Diving" markers shall consist of the words "No Diving" in letters at least four inches high and of a color contrasting with the background or at least a six-by-six inch international symbol for no diving in red and black on a white background. The distance between adjacent markers shall not be more than 25 feet. Posting of "No Diving" markers shall not preclude shallow diving for racing starts and competitive swimming practice.

What we inspect

"No Diving" markers required in areas less than 5 ft deep, letters min 4 in high

We check for 'No Diving' markers next to any pool area shallower than 5 feet.

Must be: Areas less than 5 feet deep need 'No Diving' markers, either lettering at least 4 inches high or a 6-by-6 inch red-and-black no-diving symbol on white.

If it fails: Add the missing 'No Diving' signs or symbols next to shallow areas.

15A NCAC 18A .2523(d)

What we inspect

"No Diving" markers spaced no more than 25 ft apart

We check the spacing between 'No Diving' markers.

Must be: 'No Diving' markers must be no more than 25 feet apart.

If it fails: Add additional markers to close gaps larger than 25 feet.

15A NCAC 18A .2523(d)

What we inspect

"No Diving" postings do not preclude racing starts or competitive practice

We note whether 'No Diving' signage is worded in a way that still allows racing starts and swim team practice.

Must be: 'No Diving' signs must not be worded so broadly that they block competitive racing starts or swim practice.

15A NCAC 18A .2523(d)

(e) A minimum of ¾ inch diameter safety rope shall be provided at the breakpoint where the slope of the bottom changes to exceed a 1 to 10 vertical rise to horizontal distance at a water depth of five feet (1.5 m) or less. The position of the rope shall be marked with colored floats at not greater than a five-foot spacing and a minimum two inch wide contrasting color band across the pool bottom. Float ropes shall be positioned within two feet on the shallow side of the breakpoint marker.

What we inspect

Safety rope min 3/4 in dia. required at slope breakpoint

We check for a safety rope at the point where the pool floor slopes down sharply.

Must be: A safety rope at least three-quarters of an inch thick must be installed where the floor drops steeply in water 5 feet deep or less.

If it fails: Install a rope of the correct thickness at the slope break if one is missing or undersized.

15A NCAC 18A .2523(e)

What we inspect

Safety rope floats spaced max 5 ft, with 2 in contrasting bottom color band

We check the floats marking the safety rope and the color band on the pool floor beneath it.

Must be: Floats must be spaced no more than 5 feet apart, and a contrasting-color stripe at least 2 inches wide must mark the spot on the pool floor.

If it fails: Add floats or repaint the floor stripe if either is missing or too sparse.

15A NCAC 18A .2523(e)

What we inspect

Float rope positioned within 2 ft on shallow side of the breakpoint marker

We check where the safety rope sits relative to the slope breakpoint marker.

Must be: The safety rope must sit within 2 feet of the breakpoint marker, on the shallow side.

If it fails: Reposition the rope closer to the breakpoint if it's too far off.

15A NCAC 18A .2523(e)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; February 1, 2004; January 1, 1996; July 1, 1992;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2524

Lighting and Ventilation

(a) Artificial lighting shall be provided at all pools that are to be used at night, or when natural lighting is insufficient to provide visibility in the pool area.

What we inspect

Artificial lighting required for night use or insufficient natural light

We check whether the pool has lighting for nighttime use or dim conditions.

Must be: Artificial lighting is required if the pool is used at night or when natural light isn't enough to see clearly.

If it fails: Install pool and deck lighting if night swimming is intended and none currently exists.

15A NCAC 18A .2524(a)

(b) Lighting fixtures shall be of such number and design as to illuminate all parts of the pool, the water, the depth markers, signs, entrances, restrooms, safety equipment and the required deck area and walkways.

What we inspect

Lighting must illuminate pool, markers, signs, and deck areas

We check whether the lighting covers the whole pool, depth markers, signs, entrances, and deck.

Must be: Lights must be positioned and numerous enough to light up the entire pool, depth markers, signage, entrances, and deck areas.

If it fails: Add or reposition fixtures to cover any dark spots.

15A NCAC 18A .2524(b)

(c) Fixtures shall be installed so as not to create hazards such as burning, electrical shock, mechanical injury, or temporary blinding by glare to the bathers, and so that lifeguards, when provided, can see every part of the pool area without being blinded by glare. The illumination shall be sufficient so that the floor of the pool can be seen at all times the pool is in use.

What we inspect

Lighting must avoid glare hazards; pool floor visible at all times

We check for glare hazards from lighting and confirm the pool floor is visible at night.

Must be: Lights must not create glare, shock, or burn hazards, and must be bright enough that the pool floor is visible at all times it's in use.

If it fails: Reposition or shield fixtures that cause glare, and add lighting if the floor isn't clearly visible.

15A NCAC 18A .2524(c)

(d) If underwater lighting is used, it shall provide at least 0.5 watts or 8.35 lumens per square foot of water surface and deck lighting shall provide not less than 10 foot candles of light measured at 6 inches above the deck surface.

What we inspect

Underwater lighting, when used, min 0.5 watts or 8.35 lumens per sq ft

We check the brightness of any underwater lighting, if installed.

Must be: Underwater lights, if used, must provide at least 0.5 watts or 8.35 lumens per square foot of water surface.

If it fails: Upgrade underwater fixtures to a higher-output model if they fall short.

15A NCAC 18A .2524(d)

What we inspect

Deck lighting (with underwater lighting) min 10 foot-candles at 6 in above deck

We check the deck lighting level near the pool when underwater lights are used.

Must be: When underwater lighting is installed, deck lighting must provide at least 10 foot-candles of light measured near the deck surface.

If it fails: Add deck fixtures or higher-wattage bulbs to reach the required brightness.

15A NCAC 18A .2524(d)

(e) Where underwater lighting is not used, and night swimming is permitted, area and pool lighting combined shall provide not less than 10 foot candles of light to all parts of the pool and required deck area.

What we inspect

Without underwater lighting: night lighting min 10 foot-candles on pool and deck

We check overall lighting levels on the pool and deck when there's no underwater lighting and night swimming is allowed.

Must be: Without underwater lights, combined pool and deck lighting must provide at least 10 foot-candles across the pool and deck if used at night.

If it fails: Add more overhead or deck lighting to reach the required brightness.

15A NCAC 18A .2524(e)

(f) Mechanical ventilation is required for all indoor pools.

What we inspect

Mechanical ventilation required for all indoor pools

We check whether an indoor pool has a mechanical ventilation system.

Must be: Indoor pools must have mechanical (powered) ventilation, not just windows or natural airflow.

If it fails: Have an HVAC contractor install proper ventilation for the indoor pool room.

15A NCAC 18A .2524(f)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; February 1, 2004; January 1, 1996; July 1, 1992;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2525

Heater and Temperature Requirements

(a) Pool heaters shall be designed for the purpose intended.

What we inspect

Pool heaters shall be designed for the purpose intended

We check that the pool heater is a model actually designed for pool or spa use.

Must be: The heater must be a unit built and rated for heating pool or spa water.

If it fails: Replace any heater that isn't rated for pool or spa use with an appropriate model.

15A NCAC 18A .2525(a)

(b) Heaters shall be equipped with thermostatic controls capable of assuring that the maximum operating temperature of spa water does not exceed 104 degrees Fahrenheit (40 degrees C), and that the maximum operating temperature of other heated public swimming pools does not exceed 90 degrees Fahrenheit (32 degrees C). Such controls shall be accessible only to the operator.

What we inspect

Spa water thermostatic control caps temperature at 104 degrees F

We check the spa's thermostat and its maximum temperature setting.

Must be: The spa heater's thermostat must be set so the water can't exceed 104°F.

If it fails: Have a technician adjust or repair the thermostat so it can't exceed 104°F.

15A NCAC 18A .2525(b)

What we inspect

Heated pool thermostatic control caps temperature at 90 degrees F

We check the pool heater's thermostat and its maximum temperature setting.

Must be: The pool heater's thermostat must be set so the water can't exceed 90°F.

If it fails: Have a technician adjust or repair the thermostat so it can't exceed 90°F.

15A NCAC 18A .2525(b)

What we inspect

Heater thermostatic controls accessible only to the operator

We check whether the heater's temperature controls are locked or restricted from guest access.

Must be: Only the pool operator, not swimmers or guests, should be able to adjust the heater's thermostat.

If it fails: Add a lock, cover, or restricted-access panel to keep guests from adjusting it.

15A NCAC 18A .2525(b)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. February 1, 2004; August 1, 1991;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2526

Dressing and Sanitary Facilities

(a) Dressing and sanitary facilities shall be provided at all pools, except for pools at hotels, motels, condominiums, and apartments where pool use is restricted to residents or guests. At hotels, motels, condominiums and apartments where the farthest unit is more than 300 feet from the pool, as measured along walkways provided for access by residents or guests to the pool area, a toilet and lavatory shall be provided. All public swimming pools shall post a sign visible upon entering the pool enclosure directing pool users to shower before entering the pool.

What we inspect

Dressing and sanitary facilities required, except restricted-use lodging pools

We check whether the pool has dressing rooms and restrooms, or qualifies for an exception.

Must be: Dressing and restroom facilities are required unless the pool is a restricted-use pool at a hotel, condo, or apartment reserved for residents or guests.

15A NCAC 18A .2526(a)

What we inspect

Lodging pools with farthest unit over 300 ft need toilet/lavatory

We check the distance from the farthest unit to the pool at hotel, condo, or apartment properties.

Must be: If the farthest unit is more than 300 feet from the pool by the walking path, a toilet and sink must be provided near the pool.

If it fails: Add a toilet and sink near the pool area if the distance requirement isn't met.

15A NCAC 18A .2526(a)

What we inspect

Shower-before-entering sign posted at pool enclosure entrance

We check for a sign at the pool entrance reminding swimmers to shower before entering.

Must be: A visible sign directing swimmers to shower before entering must be posted at the entrance to the pool area.

If it fails: Add the missing shower-reminder sign.

15A NCAC 18A .2526(a)

(b) Partitions shall be of material, not subject to damage by water and shall be designed so that a waterway is provided between partitions and floor to permit thorough cleaning of the walls and floor areas with hoses and brooms.

What we inspect

Dressing partitions water-resistant with cleanable floor gap

We check the material and floor gap of the dressing room partitions.

Must be: Partitions must be water-resistant and have a gap above the floor so the area can be hosed down and cleaned.

15A NCAC 18A .2526(b)

(c) Dressing facility floors shall be continuous throughout the areas. Floors shall have a slip-resistant surface that shall be smooth, to insure complete cleaning. Floor drains shall be provided, and floors shall be sloped not less than ¼ inch per foot toward the drains to insure positive drainage.

What we inspect

Dressing facility floors continuous, slip-resistant, smooth, with floor drains

We check the dressing room floor surface and drainage.

Must be: Dressing room floors must be one continuous, smooth, slip-resistant surface with working floor drains.

If it fails: Repair or replace flooring that's uneven, slippery, or missing drains.

15A NCAC 18A .2526(c)

What we inspect

Dressing facility floors sloped at least 1/4 inch per foot toward drains

We check the slope of the dressing room floor toward its drains.

Must be: Dressing room floors must slope at least a quarter inch per foot toward the drains.

If it fails: Regrade the floor if it's too flat to drain properly.

15A NCAC 18A .2526(c)

(d) Hose bibs shall be provided such that all parts of the dressing facility interior can be reached with a 50 foot hose.

What we inspect

Hose bibs sufficient to reach all dressing facility interior with a 50 ft hose

We check the placement of hose bibs inside the dressing facility.

Must be: Hose bibs must be placed so every part of the dressing room interior can be reached with a 50-foot hose.

If it fails: Add another hose bib if any interior area is out of reach.

15A NCAC 18A .2526(d)

(e) The minimum number of fixtures required in dressing and sanitary facilities shall be based upon the maximum bather load.
(f) One water closet, one lavatory, and one urinal shall be provided for the first 100 male users. One additional water closet, lavatory, and urinal shall be provided for each additional 200 male users up to a total of 500 users. Where user load exceeds 500 male users, two additional water closets or urinals and one lavatory shall be provided for each additional 250 male users. Where the maximum bather load includes less than 50 male users, one water closet and one lavatory will be sufficient.

What we inspect

Male fixture counts scaled to bather load

We check the number of toilets, sinks, and urinals available for men against the pool's expected bather load.

Must be: Men's facilities must scale with attendance: at least one toilet, sink, and urinal for the first 100 users, with more added as the crowd grows.

15A NCAC 18A .2526(f)

(g) Two water closets and two lavatories shall be provided for the first 100 female users. One additional water closet and lavatory shall be provided for each additional 100 female users up to a total of 500 users. Where user load exceeds 500 female users, two additional water closets and one lavatory shall be provided for each additional 250 female users. Where the maximum bather load includes less than 50 female users, one water closet and one lavatory will be sufficient.

What we inspect

Female fixture counts scaled to bather load

We check the number of toilets and sinks available for women against the pool's expected bather load.

Must be: Women's facilities must scale with attendance: at least two toilets and two sinks for the first 100 users, with more added as the crowd grows.

15A NCAC 18A .2526(g)

(h) Showers shall be provided in the proportion of one for each 200 persons at the time of maximum bather load.

What we inspect

Showers provided at a ratio of one per 200 persons at maximum bather load

We check the number of showers against the pool's expected maximum attendance.

Must be: There must be at least one shower for every 200 people at peak attendance.

If it fails: Add more shower heads if the current count falls short of peak attendance needs.

15A NCAC 18A .2526(h)

(i) The water heater shall be inaccessible to users. The system shall be designed such that water temperature at the shower heads and lavatories cannot exceed 110° Fahrenheit.

What we inspect

Water heater inaccessible to users

We check whether the water heater is kept out of reach of pool guests.

Must be: The water heater must be in a location or enclosure that swimmers and guests can't access.

If it fails: Relocate or enclose the water heater so guests can't reach it.

15A NCAC 18A .2526(i)

What we inspect

Shower and lavatory water temperature capped at 110 degrees F

We check the water temperature at the showers and sinks.

Must be: Water at the showers and sinks must never exceed 110°F.

If it fails: Have a plumber install or adjust a tempering valve to cap the temperature.

15A NCAC 18A .2526(i)

(j) Soap dispensers with either liquid or powdered soap shall be provided at each lavatory or required shower. The dispenser shall be of all metal or plastic type, with no glass permitted in these units.

What we inspect

Soap dispensers (metal or plastic, no glass) at each lavatory or required shower

We check for soap dispensers at the sinks and showers, and what they're made of.

Must be: Every sink and required shower needs a soap dispenser made of metal or plastic, never glass.

If it fails: Add missing dispensers or swap out any glass ones for metal or plastic.

15A NCAC 18A .2526(j)

(k) If mirrors are provided, they shall be of shatterproof materials.

What we inspect

Mirrors, if provided, must be shatterproof

We check whether any mirrors in the facility are shatterproof.

Must be: Any mirror provided must be made of a shatterproof material.

If it fails: Replace ordinary glass mirrors with shatterproof ones.

15A NCAC 18A .2526(k)

(l) Toilet paper holders with toilet paper shall be provided at each water closet.

What we inspect

Toilet paper holders with toilet paper at each water closet

We check for toilet paper holders stocked with toilet paper at each toilet.

Must be: Every toilet needs a holder stocked with toilet paper.

If it fails: Add or restock missing toilet paper holders.

15A NCAC 18A .2526(l)

(m) Dressing and sanitary facilities shall be kept clean and in good repair.

What we inspect

Dressing and sanitary facilities kept clean and in good repair

We check the overall cleanliness and condition of the dressing rooms and restrooms.

Must be: Dressing rooms and restrooms must be kept clean and in good working repair.

If it fails: Clean and repair any damaged fixtures, walls, or floors.

15A NCAC 18A .2526(m)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. February 1, 2004; April 1, 1999; January 1, 1996; July 1, 1992;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2527

Swimming Pool Slides

All swimming pool slides installed at a public swimming pool shall be labeled by the manufacturer for use in public pools, and shall be installed in accordance with manufacturer's instructions.

What we inspect

Pool slides must be manufacturer-labeled for public pool use

We check any pool slide for a manufacturer's label confirming it's rated for public pool use.

Must be: Pool slides must carry a manufacturer's label certifying they're approved for public pool use.

If it fails: Contact the manufacturer for proper labeling, or replace an unlabeled slide with a certified one.

15A NCAC 18A .2527

What we inspect

Pool slides must be installed per manufacturer's instructions

We check whether the pool slide was installed according to the manufacturer's instructions.

Must be: Pool slides must be installed exactly as the manufacturer specifies.

If it fails: Have the slide reinstalled or adjusted to match the manufacturer's instructions.

15A NCAC 18A .2527

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2528

Fences

(a) Public Swimming pools shall be completely enclosed by a fence, wall, building, or other enclosure, or any combination thereof, which encloses the swimming pool area such that all of the following conditions are met:

What we inspect

Pool completely enclosed by a barrier meeting fence rule conditions

We check that a fence, wall, or other barrier fully encloses the pool area.

Must be: The pool must be completely enclosed by a fence, wall, building, or combination of these, meeting all the specific barrier requirements.

If it fails: Close any gaps in the enclosure so the pool area is fully surrounded.

15A NCAC 18A .2528(a)

(1) The top of the barrier shall be at least 48 inches above grade measured on the side of the barrier that faces away from the swimming pool. The maximum vertical clearance between grade and the bottom of the barrier shall be two inches measured on the side of the barrier that faces away from the swimming pool;

What we inspect

Barrier height at least 48 inches above grade

We measure the height of the pool fence or barrier.

Must be: The barrier must stand at least 48 inches tall, measured from the ground on the outside, away from the pool.

If it fails: Raise or replace sections of fence that are shorter than 48 inches.

15A NCAC 18A .2528(a)(1)

What we inspect

Barrier-to-grade gap at most 2 inches

We measure the gap between the ground and the bottom of the pool barrier.

Must be: The gap under the barrier, measured on the outside, can be no more than 2 inches.

If it fails: Fill in the gap under the fence or add a bottom rail so it's within 2 inches.

15A NCAC 18A .2528(a)(1)

(2) Openings in the barrier shall not allow passage of a four-inch-diameter sphere and shall provide no external handholds or footholds. Solid barriers that do not have openings shall not contain indentations or protrusions except for normal construction tolerances and tooled masonry joints;

What we inspect

Barrier openings must not pass a 4-inch sphere and no external hand/footholds

We check the size of any gaps in the fence and look for footholds or handholds a child could climb.

Must be: Openings in the barrier must be small enough that a 4-inch ball can't pass through, and the fence must have no external footholds or handholds.

If it fails: Close gaps or remove climbable features like decorative crossbars on the outside of the fence.

15A NCAC 18A .2528(a)(2)

What we inspect

Solid barriers must be free of climbable indentations or protrusions

We check solid fence or wall sections for footholds like decorative ledges or protrusions.

Must be: Solid barrier sections must be smooth, without climbable indentations or protrusions beyond normal construction details.

If it fails: Remove or smooth over any climbable features on a solid barrier.

15A NCAC 18A .2528(a)(2)

(3) Where the barrier is composed of horizontal and vertical members and the distance between the tops of the horizontal members is 45 inches or more, spacing between the vertical members shall not exceed four inches. Where there are decorative cutouts within the vertical members, spacing within the cutouts shall not exceed 1.75 inches in width;

What we inspect

Horizontal tops 45+ in apart: vertical member gaps max 4 in

We measure the gaps between vertical fence pickets on fences with widely spaced horizontal rails.

Must be: When the top horizontal rails are 45 inches or more apart, the gaps between vertical pickets can't exceed 4 inches.

If it fails: Add pickets or a mesh insert to close gaps wider than 4 inches.

15A NCAC 18A .2528(a)(3)

What we inspect

Decorative cutouts in that configuration limited to 1.75 inches wide

We measure any decorative cutout openings within the fence pickets.

Must be: In that same fence style, decorative cutouts in the pickets can't be wider than 1.75 inches.

If it fails: Cover or modify oversized cutouts so they're no wider than 1.75 inches.

15A NCAC 18A .2528(a)(3)

(4) Where the barrier is composed of horizontal and vertical members and the distance between the tops of the horizontal members is less than 45 inches, the horizontal members shall be located on the swimming pool side of the fence. Spacing between the vertical members shall not exceed 1.75 inches in width. Where there are decorative cutouts within the vertical members, spacing within the cutouts shall not exceed 1.75 inches in width;

What we inspect

Horizontal tops under 45 in apart: rails must face pool side

We check whether horizontal fence rails are positioned on the pool side when spaced less than 45 inches apart.

Must be: When the top horizontal rails are less than 45 inches apart, they must be on the pool side of the fence, not the outside, to prevent climbing.

If it fails: Reinstall the fence with horizontal rails facing the pool side.

15A NCAC 18A .2528(a)(4)

What we inspect

In that configuration, vertical member and cutout spacing max 1.75 inches

We measure the picket and cutout spacing on fences with closely spaced horizontal rails.

Must be: In that same fence style, gaps between vertical pickets and any decorative cutouts can't exceed 1.75 inches.

If it fails: Add pickets or filler to bring gaps within 1.75 inches.

15A NCAC 18A .2528(a)(4)

(5) Maximum mesh size for chain link fences shall be a 2.25 inch square unless the fence is provided with slats fastened at the top or the bottom that reduce the openings to no more than 1.75 inches;

What we inspect

Chain link mesh max 2.25 inch square unless slats reduce openings to 1.75 inches

We check the mesh size of any chain link fence, and whether slats are installed if needed.

Must be: Chain link mesh openings can be up to 2.25 inches square, or larger only if slats reduce the openings to 1.75 inches or less.

If it fails: Add privacy slats or switch to tighter-weave mesh if the openings are too large.

15A NCAC 18A .2528(a)(5)

(6) Where the barrier is composed of diagonal members, the maximum opening formed by the diagonal members shall be no more than 1.75 inches;

What we inspect

Diagonal-member barrier openings max 1.75 inches

We measure the openings formed by diagonal fence members, like lattice-style fencing.

Must be: Openings formed by diagonal fence members can't exceed 1.75 inches.

If it fails: Add mesh or reduce the diagonal spacing so openings meet the limit.

15A NCAC 18A .2528(a)(6)

(7) Access gates shall comply with the dimensional requirements for fences and shall be equipped to accommodate a locking device. Effective April 1, 2011, pedestrian access gates shall open outward away from the pool and shall be self-closing and have a self-latching device except where a gate attendant and lifeguard are on duty. Gates other than pedestrian access gates shall have a self-latching device. Where the release mechanism of the self-latching device is located less than 54 inches from the bottom of the gate, the release mechanism shall require the use of a key, combination or card reader to open or shall be located on the pool side of the gate at least three inches below the top of the gate, and the gate and barrier shall have no openings greater than 0.5 inch within 18 inches of the release mechanism; and

What we inspect

Access gates comply with fence dimensions and accommodate a locking device

We check the pool gate's construction and whether it can accommodate a lock.

Must be: Gates must meet the same size and spacing rules as the fence and be built to hold a locking device.

If it fails: Modify or replace the gate so it matches fence requirements and can be locked.

15A NCAC 18A .2528(a)(7)

What we inspect

Pedestrian gates open outward, self-close and self-latch

We check that the pool gate swings away from the pool and closes and latches on its own.

Must be: Pedestrian gates must open outward, away from the pool, and close and latch by themselves.

If it fails: Install a self-closing hinge and self-latching mechanism, and rehang the gate to swing outward if needed.

15A NCAC 18A .2528(a)(7)

What we inspect

Non-pedestrian gates require a self-latching device

We check that any gate other than the main walk-through gate has a self-latching device.

Must be: Every gate besides the pedestrian entry gate must latch itself closed automatically.

15A NCAC 18A .2528(a)(7)

What we inspect

Low-mounted gate releases need a lock or protected placement

We check the height and design of the gate latch's release mechanism.

Must be: If the release is less than 54 inches from the ground, it must need a key, code, or card to open, or sit on the pool side at least 3 inches below the top of the gate.

If it fails: Move the release higher, add a keyed or coded lock, or relocate it to the protected pool-side position.

15A NCAC 18A .2528(a)(7)

What we inspect

No openings greater than 0.5 inch within 18 inches of the gate release mechanism

We check for gaps in the gate or fence near the latch release.

Must be: There must be no opening larger than half an inch within 18 inches of the release mechanism.

If it fails: Close nearby gaps with matching fence material so a hand or tool can't reach the latch.

15A NCAC 18A .2528(a)(7)

(8) Ground level doors and windows opening from occupied buildings to inside the pool enclosure shall be self- closing or child protected by means of a barrier or audible alarm.

What we inspect

Ground-level building doors/windows self-close or are child-protected

We check any house doors or windows that open directly into the pool area.

Must be: Ground-level doors and windows leading into the pool enclosure must close themselves automatically or be protected by a barrier or alarm.

If it fails: Add a self-closing hinge, a window barrier, or a door/window alarm.

15A NCAC 18A .2528(a)(8)

(b) Public swimming pool fences constructed prior to May 1, 2010 may vary from the provisions of Paragraph (a) of this Rule as follows:
(1) the maximum vertical clearance between grade and the bottom of the barrier may exceed two inches, but shall not exceed four inches;

What we inspect

Pre-5/1/2010 fences may have grade clearance up to 4 inches

We measure the gap between the ground and the bottom of the pool fence.

Must be: For fences built before May 1, 2010, the gap under the fence can be up to 4 inches; newer fences must keep it to 2 inches or less.

15A NCAC 18A .2528(b)(1)

(2) where the barrier is composed of vertical and horizontal members and the space between vertical members exceeds 1.75 inches, the distance between the tops of the bottom horizontal member and the next higher horizontal member may be less than 45 inches, but shall not be less than 30 inches;

What we inspect

Pre-5/1/2010 fences: horizontal-member spacing threshold reduced to 30 inches

We check the spacing between horizontal rails on older fences with wide vertical gaps.

Must be: On fences built before May 1, 2010 with vertical gaps over 1.75 inches, the horizontal rails must be at least 30 inches apart.

15A NCAC 18A .2528(b)(2)

(3) gates other than pedestrian access gates are not required to have self-latching devices if the gates are kept locked; and

What we inspect

Pre-5/1/2010: non-pedestrian gates need no self-latch if kept locked

We check whether older non-walk-through gates are kept locked.

Must be: For fences built before May 1, 2010, a self-latching device isn't required on non-pedestrian gates as long as the gate stays locked.

15A NCAC 18A .2528(b)(3)

(4) gates may swing towards a pool where natural topography, landscape position or emergency egress requirements prevent gates from swinging away from the pool.

What we inspect

Pre-5/1/2010: gates may swing toward the pool where site conditions require it

We check which direction the pool gates swing.

Must be: Gates on fences built before May 1, 2010 may swing toward the pool if the yard's slope, layout, or an emergency exit path makes swinging away impractical.

15A NCAC 18A .2528(b)(4)

(c) Public swimming pools permitted prior to April 1, 2010 with existing fences that do not comply with the dimensional requirements of Subparagraphs (a)(1) through (a)(6) and (b)(1) through (b)(2) shall not be denied an operation permit solely due to the preexisting non-compliance. Operation permits shall be denied to an owner or operator who fails to comply with Subparagraphs (a)(1) through (a)(6) and (b)(1) through (b)(2) of this Rule when:

What we inspect

Pre-2010 pools: noncompliant fences excused unless damaged/replaced

We check the age and condition of the pool fence and whether it's ever been significantly damaged or replaced.

Must be: A fence from before April 1, 2010 that doesn't meet current dimensions can stay as-is, unless at least half of it has been damaged or you replace it.

If it fails: If more than half the fence is damaged or you're replacing it, rebuild it to current fence code.

15A NCAC 18A .2528(c)

(1) at least fifty percent (50%) of the fence has been damaged or destroyed; or
(2) the owner or operator elects to replace the fence.
History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; February 1, 2004; April 1, 1999; January 1, 1996; July 1, 1992;
Temporary Amendment Eff. November 30, 2011;
Amended Eff. October 1, 2012;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2529

User Loading

In determining the maximum number of persons allowed in the pool at any one time, the following criteria shall govern:
(1) Fifteen square feet (1.39 sq m) of water surface area per person shall be provided in areas of the pool five feet (1.52 m) deep or less.

What we inspect

Shallow area (5 ft or less) bather load: 15 sq ft water surface per person

We calculate the water surface area in the shallow end, 5 feet deep or less.

Must be: The shallow area must provide at least 15 square feet of water surface per swimmer allowed at one time.

15A NCAC 18A .2529(1)

(2) Twenty-four square feet (2.23 sq m) of water surface area per person shall be provided in areas of the pool greater than five feet (1.52 m) deep. Three hundred square feet (27.87 sq m) of pool area around each diving board or platform, where provided, shall not be included in computing this area for the purpose of determining maximum bather load.

What we inspect

Deep area (over 5 ft) bather load: 24 sq ft water surface per person

We calculate the water surface area in the deep end, over 5 feet deep.

Must be: The deep area must provide at least 24 square feet of water surface per swimmer allowed at one time.

15A NCAC 18A .2529(2)

What we inspect

300 sq ft around each diving board/platform excluded from bather-load area

We check how the area around any diving board or platform is counted toward pool capacity.

Must be: The 300 square feet of water around each diving board or platform isn't counted toward the pool's swimmer capacity.

15A NCAC 18A .2529(2)

(3) Ten square feet (0.9 sq m) of water surface area per person shall be provided in spas.

What we inspect

Spa bather load: 10 sq ft water surface per person

We calculate the water surface area of the spa.

Must be: The spa must provide at least 10 square feet of water surface per person allowed at one time.

15A NCAC 18A .2529(3)

(4) Twenty-five square feet of splash zone area per person shall be provided at interactive play attractions.

What we inspect

Interactive play attraction load: 25 sq ft splash-zone area per person

We calculate the splash zone area at any interactive play feature.

Must be: Interactive play areas must provide at least 25 square feet of splash zone per person allowed at one time.

15A NCAC 18A .2529(4)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. March 1, 2004; January 1, 1996;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2530

Safety Provisions

(a) Swimming pools shall have lifesaving equipment conspicuously and conveniently on hand at all times. A unit of lifesaving equipment shall include the following:

What we inspect

Lifesaving equipment conspicuously and conveniently on hand at all times

We check that rescue equipment is out in the open and easy to reach.

Must be: Lifesaving equipment must be visibly displayed and readily accessible at the pool at all times.

If it fails: Mount the rescue pole and ring buoy on an open wall or stand near the pool instead of storing it away.

15A NCAC 18A .2530(a)

(1) A pole not less than 12 feet long, with a body hook securely attached. The pole attached to the body hook shall be non-telescoping, non-adjustable and non-collapsible.

What we inspect

Reach pole at least 12 ft long with a fixed, non-collapsible body hook

We check the length and design of the pool's rescue pole.

Must be: The reach pole must be at least 12 feet long with a body hook that doesn't extend, adjust, or collapse.

If it fails: Replace a telescoping or shorter pole with a fixed 12-foot (or longer) pole and securely attached hook.

15A NCAC 18A .2530(a)(1)

(2) A minimum ¼ inch diameter throwing rope as long as one and one-half times the maximum width of the pool or 50 feet, whichever is less, attached to a U.S. Coast Guard approved ring buoy. A rescue tube or rescue can shall be accepted as a substitute for the ring buoy where it is accompanied by a lifeguard who has been trained to use it properly.

What we inspect

Throwing rope at least 1/4 inch diameter attached to a USCG-approved ring buoy

We check the throwing rope and ring buoy kept at the pool.

Must be: The rope must be at least 1/4 inch thick and attached to a Coast Guard-approved ring buoy.

If it fails: Replace a thin or unapproved rope or buoy with a 1/4-inch-plus rope and a USCG-approved ring buoy.

15A NCAC 18A .2530(a)(2)

What we inspect

Throwing rope length capped at 1.5x max pool width or 50 ft, whichever is less

We measure the throwing rope's length against the pool's width.

Must be: The rope must be 1.5 times the pool's widest point, or 50 feet, whichever is shorter.

15A NCAC 18A .2530(a)(2)

What we inspect

Trained-lifeguard rescue tube or can may substitute for the ring buoy

We check whether a rescue tube or can is used in place of the ring buoy, and who's on duty.

Must be: A rescue tube or can may replace the ring buoy only if a trained lifeguard who knows how to use it is present.

15A NCAC 18A .2530(a)(2)

(b) Two units of lifesaving equipment must be provided for any pool that exceeds 3,000 square feet (186 sq m) of total surface area.

What we inspect

Pools over 3,000 sq ft need two units of lifesaving equipment

We measure the pool's total surface area to see if a second set of rescue equipment is required.

Must be: Pools larger than 3,000 square feet must have two complete sets of lifesaving equipment.

If it fails: Add a second reach pole and rope-and-buoy set at the opposite end of the pool.

15A NCAC 18A .2530(b)

(c) When a swimming pool does not have at least one lifeguard on duty, a sign shall be posted with legible letters of at least four inches (10 cm) in height stating: "WARNING-NO LIFEGUARD ON DUTY." In addition there shall be signs legible from all bather entrances with a minimum letter size of one inch stating: "CHILDREN SHOULD NOT USE THE SWIMMING POOL WITHOUT ADULT SUPERVISION", and: "ADULTS SHOULD NOT SWIM ALONE". Wading pools that do not have a lifeguard inside the wading pool enclosure shall have a sign posted stating "WARNING NO LIFEGUARD ON DUTY". Such signs shall be mounted permanently.

What we inspect

"NO LIFEGUARD ON DUTY" sign required, letters at least 4 in

We check for a posted lifeguard-status sign and measure its lettering.

Must be: If there's no lifeguard on duty, a sign reading 'WARNING - NO LIFEGUARD ON DUTY' must be posted with letters at least 4 inches tall.

15A NCAC 18A .2530(c)

What we inspect

Bather-entrance supervision signs required, letters at least 1 inch

We check for supervision-reminder signs at each pool entrance.

Must be: Signs about adult supervision and not swimming alone must be visible from every entrance, with letters at least 1 inch tall.

15A NCAC 18A .2530(c)

What we inspect

Wading pools without in-enclosure lifeguard need warning sign

We check whether the wading pool has its own lifeguard or a warning sign.

Must be: If no lifeguard is stationed inside the wading pool area, a 'NO LIFEGUARD ON DUTY' sign must be posted.

15A NCAC 18A .2530(c)

What we inspect

Lifeguard-status warning signs must be permanently mounted

We check how the lifeguard-status sign is attached.

Must be: The warning sign must be permanently mounted, not just propped up or hung temporarily.

If it fails: Screw or bolt the sign to a post or wall rather than leaning or hanging it.

15A NCAC 18A .2530(c)

(d) A sign prohibiting pets and glass containers in the pool area shall be provided.

What we inspect

Sign prohibiting pets and glass containers in the pool area

We check for a sign banning pets and glass in the pool area.

Must be: A sign prohibiting pets and glass containers must be posted in the pool area.

15A NCAC 18A .2530(d)

(e) Pool closed signs shall be provided and shall be posted at bather entrances whenever an operation permit is suspended for water quality or safety violations.

What we inspect

Pool-closed signs posted at bather entrances when permit is suspended

We check for pool-closed signage on hand in case the pool's permit is ever suspended.

Must be: Pool-closed signs must be available and posted at every entrance whenever the permit is suspended for a water quality or safety issue.

15A NCAC 18A .2530(e)

(f) A telephone capable of directly dialing 911 or other emergency notification system shall be provided and accessible to all pool users. Effective April 1, 2005 the telephone shall be permanently affixed to a location inside the pool enclosure or outside the enclosure within 75 feet of a bather entrance. The telephone shall be visible from within the pool enclosure or a sign shall be posted indicating the location of the emergency telephone. A sign with legible letters shall be posted at the telephone providing dialing instructions, address of the pool location and the telephone number. Where the telephone does not directly access 911, the emergency notification system shall:

What we inspect

Emergency phone/notification system accessible to all pool users

We check for a phone or emergency system that anyone at the pool can use.

Must be: A phone able to dial 911 directly, or another emergency notification system, must be available and reachable by every pool user.

If it fails: Install a landline or dedicated emergency phone within easy reach of the pool.

15A NCAC 18A .2530(f)

What we inspect

Emergency phone affixed inside enclosure or within 75 ft of entrance

We check the emergency phone's mounting and its distance from the pool entrance.

Must be: The phone must be permanently mounted either inside the pool enclosure or outside it within 75 feet of an entrance.

If it fails: Relocate or permanently mount the phone within 75 feet of a bather entrance.

15A NCAC 18A .2530(f)

What we inspect

Emergency phone visible from enclosure, or a location sign posted

We check whether the emergency phone can be seen from inside the pool area, or if a sign points to it.

Must be: The phone must be visible from inside the pool enclosure, or a sign must show where it's located.

If it fails: Post a sign directing swimmers to the phone if it isn't visible from the pool.

15A NCAC 18A .2530(f)

What we inspect

Sign at emergency phone with dialing instructions, address and phone number

We check the signage posted at the emergency phone.

Must be: A legible sign at the phone must list dialing instructions, the pool's address, and the phone number.

15A NCAC 18A .2530(f)

(1) Provide 24 hour monitoring of all incoming calls by a telecommunicator who answers only emergency calls;

What we inspect

Indirect 911 system must provide 24-hr monitoring and transfer full E911 data

We check how an indirect emergency phone system, one that doesn't dial 911 directly, is monitored and connected.

Must be: If the phone doesn't dial 911 directly, the system must be monitored around the clock by a live operator and automatically send the caller's number and location to 911.

If it fails: Confirm with your provider that the system meets 24-hour monitoring and automatic E911 data-transfer requirements.

15A NCAC 18A .2530(f)(1)-(3)

(2) Be capable of routing calls to the local 911 telecommunicator via the 911 dedicated emergency trunk line; and
(3) Electronically transfer Automatic Number Identification and Automatic Locator Identification for the emergency telephone at the pool to the Enhanced 911 system for all calls routed to 911.
History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. February 1, 2004; April 1, 1999; January 1, 1996; July 1, 1992;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2531

Wading Pools

(a) Wading pools shall meet all design specifications for swimming pools and wading pools included in Rules .2512 through .2530 of this Section with the following exceptions:
(1) Wading pools shall be physically separate from other public swimming pools except that a fill pipe and valve from a swimming pool recirculation system may be used to introduce water to a wading pool.

What we inspect

Wading pool physically separate from other pools

We check that the wading pool is a separate structure from the main pool.

Must be: The wading pool must be physically separate from other pools, though it can share a fill line from the main pool's circulation system.

.2531(a)(1)

(2) Every wading pool shall be equipped with a circulation system that is separate from, and independent of, the circulation system of the swimming pool. Such circulation system shall at least consist of a circulating pump, piping, a filter, a rate-of-flow meter, a disinfectant feeder, two inlets, and one automatic surface skimmer. Individual components of a wading pool system must meet the criteria of Rule .2518 of this Section.

What we inspect

Wading pool has independent circulation system

We check the wading pool's filter and pump setup.

Must be: The wading pool needs its own circulation system, including a separate pump, piping, filter, flow meter, disinfectant feeder, two inlets, and a skimmer.

If it fails: Install a dedicated pump, filter, and skimmer system for the wading pool rather than sharing the main pool's.

.2531(a)(2)

(3) The capacity of the circulation system shall be capable of filtering and disinfecting the entire volume of water in the wading pool 12 times in every 24 hours.

What we inspect

Wading pool circulation turns over full volume 12x/24hr

We check the wading pool's circulation flow rate.

Must be: The wading pool's system must be able to filter and disinfect its entire water volume 12 times every 24 hours.

If it fails: Upgrade the pump or filter size so it can turn over the full volume 12 times a day.

.2531(a)(3)

(4) Wading pools shall be equipped with a surface overflow system capable of removing floating material.

What we inspect

Wading pool has surface overflow system

We check for a surface skimming or overflow system on the wading pool.

Must be: The wading pool must have a system in place that removes floating debris from the surface.

If it fails: Add a skimmer or overflow gutter to the wading pool.

.2531(a)(4)

(5) Wading pools shall be no deeper than 24 inches (61 cm) at the deepest point.

What we inspect

Wading pool maximum depth 24 inches

We measure the deepest point of the wading pool.

Must be: The wading pool can be no deeper than 24 inches at its deepest point.

.2531(a)(5)

(6) Wading pools' floor slope shall not exceed one foot in 12 feet.

What we inspect

Wading pool floor slope limit

We check the slope of the wading pool floor.

Must be: The floor can rise no more than 1 foot for every 12 feet it runs horizontally.

.2531(a)(6)

(7) Wading pools shall be located in the vicinity of the shallow end of the swimming pool, and shall be separated from the swimming pool by a fence or structure similar to that described in Rule .2528 of this Section, that shall be equipped with self-closing and positive self-latching closure mechanisms, and shall be equipped with permanent locking devices. Wading pool entrance gates located inside another public swimming pool enclosure shall open away from the deeper pool. Wading pool fences constructed after April 1, 2000 shall be at least four feet high.

What we inspect

Wading pool separated from swimming pool by locking fence

We check the barrier between the wading pool and the main pool.

Must be: The wading pool must sit near the main pool's shallow end, separated by a self-closing, self-latching, lockable fence at least 4 feet high, with gates swinging away from the deeper pool.

If it fails: Install a self-latching, lockable fence between the wading pool and main pool, with the gate opening away from the deep end.

.2531(a)(7)

(8) Wading pools shall be designed to provide at least 10 square feet per child.

What we inspect

Wading pool minimum 10 sq ft per child

We calculate the wading pool's area relative to how many children it's meant for.

Must be: The wading pool must provide at least 10 square feet of area per child.

.2531(a)(8)

(9) Depth markers are not required at wading pools.
(10) The free chlorine residual in wading pools shall be maintained at no less than two parts per million.

What we inspect

Wading pool free chlorine residual minimum 2 ppm

We test the chlorine level in the wading pool.

Must be: Free chlorine in the wading pool must stay at 2 parts per million or higher.

If it fails: Increase the disinfectant feed rate to bring the wading pool's chlorine up to at least 2 ppm.

.2531(a)(10)

(11) Wading pools are not required to provide the lifesaving equipment described in Rule .2530(a) of this Section.
(b) Children's activity pools shall be constructed and operated in accordance with the rules of this Section including the requirements for wading pools with the following exceptions:
(1) The filter circulation system shall be separate from any feature pump circulation system.

What we inspect

Children's activity pool filter system separate from feature pumps

We check that the filter system and the water-feature pumps at a children's activity pool run independently.

Must be: The filtration circulation system must be separate from any pump that powers water features like sprays or fountains.

If it fails: Wire and plumb the feature pumps on a separate circuit from the filtration pump.

.2531(b)(1)

(2) The filter circulation system for stand-alone children's activity pools shall filter and return the entire water capacity in no more than one hour and shall operate 24 hours a day.

What we inspect

Stand-alone children's activity pool turnover within 1 hour, continuous

We check the filtration flow rate and run schedule of a stand-alone children's activity pool.

Must be: The system must filter and return the full water volume within one hour and run continuously, 24 hours a day.

If it fails: Upsize the pump or filter to reach a one-hour turnover, and set it to run continuously rather than on a timer.

.2531(b)(2)

(3) The disinfectant residual in children's activity pools shall be maintained at a level of at least two parts per million of free chlorine measured in the pool water and at least one part per million in all water features.

What we inspect

Children's activity pool disinfectant residual minimums

We test the chlorine level in the pool water and in the water features.

Must be: Free chlorine must be at least 2 parts per million in the pool itself and at least 1 part per million in the water features.

If it fails: Adjust the disinfectant feed to keep the pool at 2 or more ppm and features at 1 or more ppm.

.2531(b)(3)

(4) Valves shall be provided to control water flow to the features in accordance with the manufacturers' specifications.

What we inspect

Children's activity pool feature flow valves per manufacturer specs

We check that flow-control valves are installed for each water feature.

Must be: Valves controlling water flow to each feature must be set up according to the manufacturer's specifications.

.2531(b)(4)

(5) Children's activity pools built prior to February 1, 2004 that do not comply with this Paragraph may operate as built if no water quality or safety violations occur.
History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; February 1, 2004; April 1, 1999; January 1, 1996;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2532

Spas and Hot Tubs

Spas and hot tubs shall meet all design specifications for swimming pools and wading pools included in Rules .2512 through .2530 of this Section with the following exceptions:

What we inspect

Spa discharge piping water velocity limit

We check the flow rate through the spa's discharge piping.

Must be: Water speed in the discharge pipe must not exceed 10 feet per second, or 8 feet per second if the pipe is copper.

If it fails: Use larger-diameter piping to slow the water velocity to within the limit.

.2532(5)a

What we inspect

Spa discharge piping velocity limit for copper pipe

We check the flow rate through any copper discharge piping at the spa.

Must be: Water speed in copper discharge piping must not exceed 8 feet per second.

.2532(5)b

What we inspect

Spa suction piping water velocity limit

We check the flow rate through the spa's suction piping.

Must be: Water speed in suction piping must not exceed 6 feet per second.

If it fails: Use larger-diameter suction piping to bring the velocity within the limit.

.2532(5)c

What we inspect

Spa hydrotherapy timer maximum 15 minutes, switch out of reach from spa

We check the jet timer's maximum setting and where its switch is located.

Must be: The jet timer can run for no more than 15 minutes per cycle, and its switch must be placed far enough away that a bather has to leave the spa to reach it.

If it fails: Reprogram the timer to a 15-minute max and relocate the switch out of arm's reach of the spa.

.2532(7)

What we inspect

Spa maximum operational water depth 4 feet

We measure the water depth in the spa.

Must be: The spa's water depth must be no more than 4 feet.

.2532(8)

What we inspect

Spa maximum seat/bench depth 2 feet

We measure the depth of any seats or benches in the spa.

Must be: Seats and benches in the spa must be no deeper than 2 feet below the waterline.

.2532(9)

What we inspect

Spa minimum ceiling height 7.5 feet above rim

We measure the clearance above an indoor spa, if it's enclosed.

Must be: There must be at least 7.5 feet of open space between the spa's rim and the ceiling above it.

.2532(10)

What we inspect

Spa entry aids required where depth exceeds 24 inches

We check for steps or a ladder to get in and out of the spa.

Must be: If the spa is deeper than 24 inches, it must have steps, step-seats, a ladder, or recessed hand and foot holds.

If it fails: Add a step, ladder, or recessed treads for easier, safer entry and exit.

.2532(12)

What we inspect

Contrasting color bands on spa step treads, seats, benches

We check that the edges of spa steps, seats, and benches have a contrasting color band or line.

Must be: The leading edge of each step, seat, and bench in the spa must be marked with a contrasting color band or line.

If it fails: Add a contrasting stripe or paint band along the edges of steps, seats, and benches so they stand out underwater.

.2532(13)

What we inspect

Spa handrail spacing at least one per 50 feet of perimeter

We check how many handrails or ladders the spa has compared to its perimeter.

Must be: The spa needs at least one handrail or ladder for every 50 feet of perimeter, or any part of that distance.

If it fails: Install an additional handrail or ladder so entry and exit points are spaced no more than 50 feet apart.

.2532(14)

What we inspect

Caution sign required at spas exceeding 90°F

We check for a posted caution sign near the spa entrance and check the water temperature.

Must be: If the spa water is hotter than 90°F, a caution sign with health and safety warnings, in letters at least half an inch tall, must be posted at the entrance.

If it fails: Post a spa caution sign covering health conditions, time limits, and supervision rules near the entrance.

.2532(15)

What we inspect

Spa meets pool emergency telephone and signage requirements

We check that the spa area has the same emergency phone and signage as the pool.

Must be: The spa must meet the same emergency telephone and warning sign requirements as the main pool.

.2532(16)

What we inspect

Sign required requiring shower before spa entry, prohibiting oils/lotions

We check for a sign at the spa about showering before use and avoiding oils and lotions.

Must be: A sign must be posted telling bathers to shower before entering the spa and not to use oils, lotions, or bath minerals in the water.

If it fails: Post a sign near the spa reminding bathers to shower first and avoid oils, lotions, and minerals.

.2532(17)

What we inspect

Spa wall slope limit for spas less than 4 feet deep

We check the angle of the spa walls in areas less than 4 feet deep.

Must be: In spa areas under 4 feet deep, the wall can angle inward but no more than 15 degrees from vertical.

.2532(19)

(1) The circulation system equipment shall provide a turnover rate for the entire water capacity at least once every 30 minutes.

What we inspect

Spa turnover rate at least every 30 minutes

We check the spa's circulation flow rate.

Must be: The spa's system must turn over its entire water volume at least once every 30 minutes.

If it fails: Increase pump flow, or reduce spa volume, so a full turnover happens within 30 minutes.

.2532(1)

(2) The arrangement of water inlets and outlets shall produce a uniform circulation of water so as to maintain a uniform disinfectant residual throughout the spa.

What we inspect

Spa inlets/outlets produce uniform disinfectant residual

We check the placement of the spa's water inlets and outlets.

Must be: Inlets and outlets must be arranged so water circulates evenly and chlorine levels stay consistent throughout the spa.

.2532(2)

(3) A minimum of two inlets shall be provided with inlets added as necessary to maintain required flowrate.

What we inspect

Spa minimum two inlets

We count the water inlets in the spa.

Must be: The spa needs at least two inlets, with more added if needed to keep up the required flow.

If it fails: Add a second inlet if the spa currently has only one.

.2532(3)

(4) Water outlets shall be designed so that each pumping system in the spa (filter systems or booster systems if so equipped) provides the following:
(a) Where drains are provided, drains shall be unblockable or shall consist of two or more drains connected by a "T" pipe. Connecting piping shall be of the same diameter as the main drain outlet. Filter system drains shall be capable of emptying the spa completely. In spas constructed after April 1, 2000 drains shall be installed at least three feet apart or located on two different planes of the pool structure.

What we inspect

Spa drains unblockable or dual with T-pipe; spacing after 4/1/2000

We check the spa's drain design and spacing.

Must be: Drains must be unblockable, or come as a connected pair able to fully drain the spa; newer spas need drains at least 3 feet apart or on different planes.

If it fails: Replace a single blockable drain with an unblockable cover or a connected dual-drain system.

.2532(4)(a)

What we inspect

Spa two-pump system dedicated timer to hydrotherapy pump only

We check how the spa's two pumps and timer switch are wired, if the spa uses two pumps.

Must be: One pump must handle filtration and disinfection continuously, the other handles the bubbling jets, and the timer switch must control only the jet pump.

.2532(6)(a)

(b) Filtration systems shall provide at least one surface skimmer per 100 square feet, or fraction thereof of surface area.

What we inspect

Spa surface skimmer ratio

We count the spa's surface skimmers relative to its size.

Must be: There must be at least one surface skimmer for every 100 square feet of spa surface area, or any fraction of that.

If it fails: Add another skimmer if the spa's surface area exceeds what the current skimmers can cover.

.2532(4)(b)

What we inspect

Spa single two-speed pump timer limited to hydrotherapy portion

We check the wiring and settings of a spa's two-speed pump and its timer.

Must be: The pump must keep filtering and disinfecting at all times, and the timer switch must only control the jet, or hydrotherapy, speed.

.2532(6)(b)

(5) The water velocity in spa or hot tub discharge piping shall not exceed 10 feet per second (3.05 meters per second); except for copper pipe where water velocity shall not exceed eight feet per second (2.44 meters per second). Suction water velocity in any piping shall not exceed six feet per second (1.83 meters per second).
(6) Spa recirculation systems shall be separate from companion swimming pools.
(a) Where a two-pump system is used, one pump shall provide the required turnover rate, filtration and disinfection for the spa water. The other pump shall provide water or air for hydrotherapy turbulence without interfering with the operation of the recirculation system. The timer switch shall activate only the hydrotherapy pump.
(b) Where a single two-speed pump is used, the pump shall be designed and installed to provide the required turnover rate for filtration and disinfection of the spa water at all times without exceeding the maximum filtration rates specified in Rule .2519 of this Section. The timer switch shall activate only the hydrotherapy portion of the pump.
(c) Where a single one-speed pump is used, a timer switch shall not be provided.

What we inspect

Spa single one-speed pump: no timer switch provided

We check whether a timer switch is installed on a spa with a single one-speed pump.

Must be: A spa with only one single-speed pump must not have a timer switch at all.

If it fails: Remove the timer switch if the spa runs on a single one-speed pump.

.2532(6)(c)

(7) A timer switch shall be provided for the hydrotherapy turbulence system with a maximum of 15 minutes on the timer. The switch shall be placed such that a bather must leave the spa to reach the switch.
(8) The maximum operational water depth shall be four feet (1.22 m) measured from the water line.
(9) The maximum depth of any seat or sitting bench shall be two feet (61 centimeters) measured from the waterline.
(10) A minimum height between the top of the spa/hot tub rim and the ceiling shall be seven and a half feet.
(11) Depth markers are not required at spas.
(12) Steps, step-seats, ladders or recessed treads shall be provided where spa and hot tub depths are greater than 24 inches (61 centimeters).
(13) Contrasting color bands or lines shall be used to indicate the leading edge of step treads, seats, and benches.
(14) A spa or hot tub shall be equipped with at least one handrail (or ladder equivalent) for each 50 feet (15.2 meters) of perimeter, or portion thereof, to designate points of entry and exit.
(15) Where water temperature exceeds 90 degrees Fahrenheit (32 degrees Celsius), a caution sign shall be mounted adjacent to the entrance to the spa or hot tub. It shall contain the following warnings in letters at least ½ inch in height: CAUTION: -Pregnant women; elderly persons, and persons suffering from heart disease, diabetes, or high or low blood pressure should not enter the spa/hot tub without prior medical consultation and permission from their doctor; -Do not use the spa/hot tub while under the influence of alcohol, tranquilizers, or other drugs that cause drowsiness or that raise or lower blood pressure; -Do not use alone; -Unsupervised use by children is prohibited; -Enter and exit slowly; -Observe reasonable time limits (that is, 10-15 minutes), then leave the water and cool down before returning for another brief stay; -Long exposure may result in nausea, dizziness, or fainting; -Keep all breakable objects out of the area.
(16) Spas shall meet the emergency telephone and signage requirements for swimming pools in Rule .2530(f).
(17) A sign shall be posted requiring a shower for each user prior to entering the spa or hot tub and prohibiting oils, body lotion, and minerals in the water.
(18) Spas are not required to provide the lifesaving equipment described in Rule .2530(a) of this Section.
(19) In spas less than four feet deep, the slope of the pool wall may exceed 11 degrees from plumb, but shall not exceed 15 degrees from plumb.
History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; January 1, 2006; July 1, 2004; February 1, 2004; April 1, 1999; January 1,
1996; July 1, 1992;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2533

Equipment Room

(a) All pumps, chemical feeding apparatus and other mechanical and electrical equipment shall be enclosed in a weatherproof structure with a minimum ceiling height of seven feet. The equipment room shall be provided with a door with a permanent lock that must be kept locked when not in use by the pool operator. Filters located outside the equipment room shall be completely enclosed by a fence.

What we inspect

Equipment room minimum ceiling height 7 feet

We check the ceiling height of the equipment room.

Must be: The equipment room must be a weatherproof enclosure with a ceiling at least 7 feet high.

.2533(a)-1

What we inspect

Equipment room door has permanent lock kept locked when unattended

We check that the equipment room door has a working lock and stays locked when no one is tending it.

Must be: The equipment room door must have a permanent lock and be kept locked whenever the pool operator isn't present.

If it fails: Install a permanent lock on the equipment room door and keep it locked except when actively working inside.

.2533(a)-2

What we inspect

Filters located outside equipment room must be fully fenced

We check whether any filters located outside the equipment room are fully enclosed by a fence.

Must be: Filters that aren't inside the equipment room must be completely enclosed by a fence.

If it fails: Install a fence fully enclosing any filter equipment located outside the equipment room.

.2533(a)-3

(b) Lighting to allow the operator to read all gauges and control devices shall be provided.

What we inspect

Equipment room lighting sufficient to read gauges

We check that the equipment room has enough light to read the gauges and controls.

Must be: Lighting in the equipment room must be bright enough for the operator to read all gauges and controls.

If it fails: Add or upgrade lighting in the equipment room so gauges and dials are easy to read.

.2533(b)

(c) Valves and control devices shall be accessible and visible to the pool operator. At least three feet of clear walkway shall be provided to allow access to equipment.

What we inspect

Equipment room valves/controls accessible and visible

We check that the valves and control devices in the equipment room are easy to reach and see.

Must be: All valves and controls in the equipment room must be accessible and visible to the operator.

If it fails: Clear obstructions or relocate blocked valves and controls so they're easy to reach and see.

.2533(c)-1

What we inspect

Equipment room minimum 3 feet clear walkway to equipment

We check the width of the walkway leading to the equipment in the equipment room.

Must be: There must be at least 3 feet of clear walkway to access the equipment.

If it fails: Clear stored items or relocate equipment to open up at least 3 feet of walkway.

.2533(c)-2

(d) Drainage in and around the equipment room shall preclude the possibility of water entering or accumulating on any interior surface of the enclosure. Equipment room floors shall be sloped not less than ¼ inch per foot toward the drains.

What we inspect

Equipment room drainage precludes water accumulation

We check the drainage in and around the equipment room for standing water.

Must be: Drainage must keep water from entering or pooling on any interior surface of the equipment room.

If it fails: Improve grading or add drains so water can't collect inside the equipment room.

.2533(d)-1

What we inspect

Equipment room floor slope toward drains

We check the slope of the equipment room floor toward its drains.

Must be: The floor must slope at least a quarter inch per foot toward the drains.

.2533(d)-2

(e) Natural cross draft or continuous forced ventilation is required.

What we inspect

Equipment room ventilation required

We check that the equipment room has adequate airflow.

Must be: The equipment room needs natural cross-ventilation or continuous forced ventilation.

If it fails: Add vents, louvers, or an exhaust fan to keep air moving through the equipment room.

.2533(e)

(f) A permanent means of access shall be provided to all equipment rooms.

What we inspect

Permanent means of access to equipment room

We check that there's a permanent, reliable way to reach the equipment room.

Must be: The equipment room must have a permanent means of access, such as a fixed door or walkway.

.2533(f)

(g) A hose bib with an approved backflow prevention device shall be provided within 50 feet of the equipment room.

What we inspect

Hose bib with backflow prevention within 50 feet of equipment room

We check for a hose bib fitted with a backflow preventer near the equipment room.

Must be: A hose bib with an approved backflow prevention device must be within 50 feet of the equipment room.

If it fails: Install a hose bib with a backflow prevention device within 50 feet of the equipment room.

.2533(g)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. February 1, 2004; January 1, 1996;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2534

Chemical Storage Room

A separate chemical storage room that meets the following criteria shall be provided:
(1) The chemical storage room shall be in a dry, weatherproof structure with a minimum ceiling height of seven feet.

What we inspect

Chemical storage room dry, weatherproof, 7 ft ceiling

We check that the chemical storage room is dry, weatherproof, and tall enough.

Must be: The chemical storage room must be a dry, weatherproof space with a ceiling at least 7 feet high.

.2534(1)

(2) For public swimming pools built after May 1, 1996, chemical storage space shall be provided based on a minimum of five square feet for the first 10,000 gallons of pool water plus one additional square foot for each additional 3,000 gallons or portion thereof up to a total area of 100 square feet. Public swimming pools constructed after April 1, 2004 shall provide a separate room for storage of pool chemicals.

What we inspect

Chemical storage room minimum area formula (pools built after 5/1/1996)

We check the size of the chemical storage room against the pool's water volume.

Must be: Pools built after May 1996 need at least 5 square feet of chemical storage for the first 10,000 gallons, plus 1 more square foot for every 3,000 gallons after that, up to 100 square feet.

If it fails: Expand the chemical storage room, or add a second storage area, to meet the size required for your pool's volume.

.2534(2)a

What we inspect

Separate chemical storage room required for pools built after 4/1/2004

We check whether pool chemicals have their own separate storage room.

Must be: Pools built after April 2004 must have a room dedicated just to storing pool chemicals, separate from other equipment.

If it fails: Set aside or build a dedicated room for chemical storage, separate from the pump and filter equipment.

.2534(2)b

(3) Natural cross draft or continuous forced ventilation is required.

What we inspect

Chemical storage room ventilation required

We check that the chemical storage room has adequate airflow.

Must be: The chemical storage room needs natural cross-ventilation or continuous forced ventilation.

If it fails: Add vents, louvers, or an exhaust fan to ventilate the chemical storage room.

.2534(3)

(4) Provision shall be made for dry storage of all pool chemicals in waterproof containers or above the floor on shelves, pallets or dollies.

What we inspect

Chemicals stored dry, in waterproof containers or off the floor

We check how pool chemicals are stored in the room.

Must be: Chemicals must be kept dry, in waterproof containers, or raised off the floor on shelves, pallets, or dollies.

If it fails: Move chemical containers onto shelves or pallets, or switch to waterproof containers, so they stay dry.

.2534(4)

(5) The chemical storage room shall be arranged so that chemicals which can react with other pool chemicals are stored separately and shall be constructed and arranged to permit easy cleanup of chemical spills.

What we inspect

Reactive chemicals stored separately

We check whether chemicals that can react with each other are kept apart.

Must be: Chemicals that could react with each other must be stored in separate areas of the room.

If it fails: Separate incompatible chemicals, such as chlorine and acid, onto different shelves or areas.

.2534(5)a

What we inspect

Chemical storage room arranged for easy spill cleanup

We check whether the chemical storage room is set up to make spill cleanup easy.

Must be: The room's layout and surfaces must allow chemical spills to be cleaned up easily.

If it fails: Use sealed, non-absorbent flooring and keep aisles clear so spills can be cleaned up quickly.

.2534(5)b

(6) Lighting shall be provided in chemical storage rooms.

What we inspect

Lighting provided in chemical storage room

We check that the chemical storage room has working lighting.

Must be: Lighting must be provided in the chemical storage room.

If it fails: Install a light fixture in the chemical storage room.

.2534(6)

History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. February 1, 2004; January 1, 1996;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2535

Water Quality Standards

Whenever a public swimming pool is open for use, water quality shall be maintained in accordance with the following:

What we inspect

Chlorine disinfected pools: free chlorine residual minimum 1 ppm

We test the free chlorine level throughout the pool.

Must be: Free chlorine must stay at least 1 ppm everywhere in the pool whenever it's open.

If it fails: Add chlorine or check the feeder/chlorinator, then retest until the reading is at least 1 ppm.

.2535(4)a

What we inspect

Chlorine pools must be stabilized with cyanuric acid (with exceptions)

We check whether an outdoor chlorine pool has cyanuric acid (stabilizer) in the water.

Must be: Outdoor chlorine pools must use cyanuric acid to keep chlorine stable, unless it's proven the chlorine level already stays stable without it.

If it fails: Add a cyanuric acid stabilizer product and retest to confirm the chlorine residual holds steady.

.2535(4)b

What we inspect

Cyanuric acid level maximum 100 ppm

We test the cyanuric acid (stabilizer) level in the water.

Must be: Cyanuric acid must not exceed 100 ppm.

If it fails: Dilute the water by draining and refilling partially, since cyanuric acid can only be lowered by adding fresh water.

.2535(4)c

What we inspect

Bromine disinfected pools: free bromine residual minimum 2 ppm

We test the free bromine level throughout the pool.

Must be: Free bromine must stay at least 2 ppm everywhere in the pool whenever it's open.

If it fails: Add bromine or check the feeder, then retest until the reading is at least 2 ppm.

.2535(5)

What we inspect

Automatic chemical feeders required for chlorine/bromine

We check that chlorine or bromine is dosed by an automatic feeder rather than by hand.

Must be: Pools using chlorine or bromine must use an automatic chemical feeder to add it.

If it fails: Install an automatic chlorine or bromine feeder instead of hand-dosing chemicals.

.2535(6)a

What we inspect

Automatic chlorine/bromine feeders must meet NSF/ANSI Standard 50

We check that the automatic chlorine or bromine feeder is a certified, properly installed unit.

Must be: The feeder must meet NSF/ANSI Standard 50 for pool equipment and be installed correctly.

If it fails: Replace the feeder with an NSF/ANSI 50-certified model installed per the manufacturer's instructions.

.2535(6)b

What we inspect

Chlorine/bromine feeder pumps interlocked with circulation pump

We check that the chemical feeder automatically shuts off when the circulation pump isn't running.

Must be: The chlorine or bromine feeder must be wired so it can't run unless the circulation pump is also running.

If it fails: Add an interlock, such as a flow switch, so the feeder pump only runs while the circulation pump is on.

.2535(6)c

What we inspect

Biguanide disinfected pools: residual 30-50 ppm

We test the biguanide level in the pool water.

Must be: Biguanide must be kept between 30 and 50 ppm whenever the pool is open.

If it fails: Add biguanide sanitizer or dilute the water, then retest until the level falls between 30 and 50 ppm.

.2535(7)

What we inspect

Silver/copper ion systems: copper max 1 ppm and chlorine residual maintained

We test the copper level and chlorine residual in pools with a silver/copper ionizer.

Must be: Copper must not exceed 1 ppm, and a chlorine residual must still be maintained at all times.

If it fails: Reduce the ionizer output to bring copper under 1 ppm, and keep maintaining chlorine as required.

.2535(8)

What we inspect

Elemental gaseous chlorine prohibited

We check what form of chlorine is used to sanitize the pool.

Must be: Gaseous (elemental) chlorine cannot be used to disinfect the pool.

If it fails: Switch to a liquid, granular, or tablet chlorine product instead of gas chlorine.

.2535(9)

What we inspect

Test kits for disinfectant, pH, and total alkalinity required on site

We check for a working test kit on site for disinfectant, pH, and total alkalinity.

Must be: A test kit or equipment able to measure disinfectant level, pH, and total alkalinity must be kept on site.

If it fails: Buy a test kit that covers disinfectant, pH, and total alkalinity and keep it at the pool.

.2535(10)a

What we inspect

Cyanuric acid test kit required when using stabilized chlorine

We check for a cyanuric acid test kit if the pool uses stabilized chlorine.

Must be: Pools using cyanuric acid or stabilized chlorine products need a test kit that measures cyanuric acid levels.

If it fails: Buy a cyanuric acid test kit or test strips and keep them on site.

.2535(10)b

What we inspect

Daily pool inspection and 6-month record retention

We check for a daily inspection log covering pool operating conditions.

Must be: The pool must be inspected at least once a day, with written records kept on site for at least 6 months.

If it fails: Start a daily log of water testing and pool checks, and keep at least 6 months of records on site.

.2535(11)-intro

What we inspect

Heated swimming pool water temperature maximum 90°F

We check the water temperature of a heated swimming pool.

Must be: Heated pool water must not be hotter than 90°F.

If it fails: Lower the heater's thermostat setting so the water stays at or below 90°F.

.2535(12)a

What we inspect

Heated spa water temperature maximum 104°F

We check the water temperature of the spa.

Must be: Heated spa water must not be hotter than 104°F.

If it fails: Lower the spa heater's thermostat setting so the water stays at or below 104°F.

.2535(12)b

(1) The chemical quality of the water shall be maintained in an alkaline condition at all times with the pH between 7.2 and 7.8.

What we inspect

Pool pH maintained between 7.2 and 7.8

We test the pool water's pH level.

Must be: The pH must stay between 7.2 and 7.8 whenever the pool is open.

If it fails: Add a pH increaser or decreaser as needed and retest until the level falls between 7.2 and 7.8.

.2535(1)

(2) The clarity of the water shall be maintained such that the main drain grate is visible from the pool deck at all times.

What we inspect

Pool water clarity: main drain visible from deck

We check whether the main drain grate is clearly visible from the pool deck.

Must be: The water must stay clear enough that the main drain grate can be seen from the deck at all times.

If it fails: Shock the pool, run the filter longer, and check circulation until the water clears enough to see the main drain.

.2535(2)

(3) Disinfection shall be provided in accordance with manufacturers' instructions for all pools by a chemical or other process that meets the criteria listed as follows:

What we inspect

Disinfectant chemical/process must meet EPA registration and safety criteria

We check what disinfectant is used and confirm it's an approved, EPA-registered product used as directed.

Must be: The disinfectant must be EPA-registered for pool or drinking water, leave a measurable residual, be safe for bathers and equipment, and control germs as well as 1 ppm of free chlorine.

If it fails: Switch to an EPA-registered pool disinfectant and use it exactly as the label directs.

.2535(3)

(a) registered with the U.S. Environmental Protection Agency for pool water or potable water;

What we inspect

Daily recording of disinfectant residual

We check that the daily log includes the disinfectant reading.

Must be: The disinfectant level, such as chlorine or bromine, must be recorded in the log every day.

.2535(11)(a)

What we inspect

Fecal/vomit accident: evacuate affected pools

We check that staff know to clear everyone out of any pool affected by a fecal or vomit accident.

Must be: Everyone must leave any pool sharing circulated water with the contaminated pool, and no one may re-enter until decontamination is finished.

.2535(13)(a)

(b) provides a residual effect in the pool water that can be measured by portable field test equipment;

What we inspect

Daily recording of pool water pH

We check that the daily log includes the pH reading.

Must be: The pool water pH must be recorded in the log every day.

.2535(11)(b)

What we inspect

Fecal/vomit accident: remove material and dispose properly

We check that staff have a plan to remove contamination with a net or scoop and dispose of it properly.

Must be: As much of the feces or vomit as possible must be removed with a net or scoop and disposed of into a sewage system.

.2535(13)(b)

(c) will not impart any immediate or cumulative adverse physiological effects to pool bathers when used as directed;

What we inspect

Daily recording of heated pool water temperature and maintenance activities

We check the log for daily water temperature entries on heated pools and for maintenance activities like chemical additions and filter backwashing.

Must be: Heated pools must log water temperature daily, and the log must note maintenance activities such as chemical additions and filter backwashes.

.2535(11)(c)

What we inspect

Fecal/vomit accident: raise chlorine to 2 ppm at pH 7.2-7.5 and mix

We check the response procedure for raising and testing chlorine after a contamination event.

Must be: Free chlorine must be raised to exactly 2 ppm at a pH of 7.2 to 7.5 and confirmed to be mixed throughout the pool.

.2535(13)(c)

(d) will not produce any safety hazard when stored or used as directed;

What we inspect

Weekly recording of total alkalinity and cyanuric acid

We check that the log includes weekly readings of total alkalinity and cyanuric acid.

Must be: Total alkalinity and cyanuric acid levels must be recorded in the log at least once a week.

.2535(11)(d)

What we inspect

Formed stool/vomit closure time: 2 ppm for 25 min or 3 ppm for 19 min

We check how long the pool stays closed and at what chlorine level after a formed-stool or vomit accident.

Must be: The pool must stay closed while holding 2 ppm chlorine for at least 25 minutes, or 3 ppm for at least 19 minutes, before reopening.

.2535(13)(d)

(e) will not damage pool components or equipment; and

What we inspect

Daily recording of pool drain cover/grate inspection

We check that the log includes a daily note confirming the drain cover was inspected.

Must be: The drain cover/grate must be checked and logged as inspected every day.

.2535(11)(e)

What we inspect

Liquid stool accident: CT value 15,300 and backwash before reopening

We check the closure and disinfection procedure used after a liquid stool accident.

Must be: The chlorine level and closure time together must reach a combined CT value of 15,300, and the filter must be backwashed, before the pool reopens.

.2535(13)(e)

(f) will demonstrate reduction of total coliform and fecal coliform to a level at least equivalent to free chlorine at a level of one part per million in the same body of water.
(4) When chlorine is used as the disinfectant, a free chlorine residual of at least one part per million (ppm) shall be maintained throughout the pool whenever it is open or in use. Pools that use chlorine as the disinfectant must be stabilized with cyanuric acid except at indoor pools or where it can be shown that cyanuric acid is not necessary to maintain a stable free chlorine residual. The cyanuric acid level shall not exceed 100 parts per million.
(5) When bromine or compounds of bromine are used as the disinfectant, a free bromine residual of at least two parts per million, shall be maintained throughout the pool whenever it is open or in use.
(6) When chlorine or bromine are used as the disinfectant, automatic chemical feeders shall be used. Automatic chlorine or bromine feeders shall be manufactured and installed in accordance with NSF/ANSI Standard number 50. Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation.
(7) When biguanide is used as the disinfectant, a residual of 30 to 50 parts per million shall be maintained throughout the pool whenever it is open or in use.
(8) When silver/copper ion systems are used, the copper concentration in the pool water shall not exceed one part per million and a chlorine residual must be maintained in accordance with Item (4) of this Rule.
(9) The use of chlorine in its elemental (gaseous) form for disinfection of public swimming pools is prohibited.
(10) Test kits or equipment capable of measuring disinfectant level, pH, and total alkalinity must be maintained at all public swimming pools. Pools using cyanuric acid or chlorinated isocyanurates must have a test kit capable of measuring cyanuric acid levels.
(11) The pool operator shall inspect the pool at least daily and maintain written records of the operating conditions of each pool. Records shall be maintained at the pool site for a period of not less than six months. Records shall include the following:
(a) daily recording of the disinfectant residual in the pool;
(b) daily recording of pool water pH;
(c) daily recording of water temperature in heated pools; recording of activities pertaining to pool water maintenance including chemical additions and filter backwash cycles;
(d) weekly recording of total alkalinity and cyanuric acid levels; and
(e) daily recording of pool drain cover/grate inspection.
(12) Water temperature in heated swimming pools shall not exceed 90 degrees Fahrenheit (32 degrees Celsius) and in heated spas shall not exceed 104 degrees Fahrenheit (40 degrees Celsius).
(13) The pool operator shall take the following steps to manage fecal and vomitus accidents:
(a) Direct everyone to leave all pools into which water containing the feces or vomit is circulated and do not allow anyone to enter the pool(s) until decontamination is completed;
(b) Remove as much of the feces or vomit as possible using a net or scoop and dispose of it in a sewage treatment and disposal system;
(c) Raise the free available chlorine concentration to two ppm at a pH of 7.2 to 7.5 and test to assure the chlorine concentration is mixed throughout the pool; and
(d) For accidents involving formed stools or vomit, maintain the free available chlorine concentration at two ppm for at least 25 minutes or at three ppm for at least 19 minutes before reopening the pool. For accidents involving liquid stools increase the free chlorine residual and closure time to reach a CT inactivation value of 15,300 then backwash the pool filter before reopening the pool. CT refers to concentration (C) of free available chlorine in parts per million multiplied by time (T) in minutes.
History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Amended Eff. May 1, 2010; February 1, 2004; April 1, 1999; January 1, 1996; July 1, 1992;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2536

Revocation of Permits

The Department may suspend or revoke permits in accordance with G.S. 130A-23.
History Note: Authority G.S. 130A-282;
Eff. May 1, 1991;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2537

Maintenance and Operation

(a) All public swimming pools constructed or remodeled on or after May 1, 1991 shall be maintained and operated in accordance with the Rules of this Section.
(b) On or after May 1, 1993 all public swimming pools including those constructed prior to May 1, 1991 shall be maintained and operated in accordance with the following:
(1) All safety provisions of Rule .2530 of this Section shall be met.
(2) Decks shall be structurally sound and shall be maintained free of trip hazards or offsets greater than one-half inch resulting from deterioration or changes from the original deck profile.

What we inspect

Deck free of trip hazards/offsets greater than 1/2 inch

We check the pool deck for cracks, uneven spots, or raised edges.

Must be: The deck must be structurally sound with no trip hazards or height changes greater than half an inch.

If it fails: Grind down or patch any deck offsets and repair cracked or uneven sections.

.2537(b)(2)

(3) There shall be no loose coping.

What we inspect

No loose coping

We check the coping stones or edging around the pool for looseness.

Must be: All coping around the pool must be firmly set with no loose or wobbly pieces.

If it fails: Re-mortar or replace any loose coping stones so they're securely set.

.2537(b)(3)

(4) Artificial lighting shall be provided for all pools used when natural lighting is not sufficient to make all parts of the pool and pool area clearly visible.

What we inspect

Artificial lighting provided when natural light insufficient

We check whether the pool area has lighting for use after dark or in low light.

Must be: Artificial lighting must make the whole pool and deck clearly visible whenever natural light isn't enough.

If it fails: Install pool and deck lighting so the area stays clearly visible whenever it's used after dark.

.2537(b)(4)

(5) Swimming pools shall be protected by a fence, wall, building, or other enclosure, or any combination thereof, that completely encloses the swimming pool area. All gates and doors shall be equipped with self-closing and positive self-latching closure mechanisms. Existing waterslide flumes and other appurtenances are not required to be located inside the fence.

What we inspect

Pool fully enclosed by fence, wall, building, or combination

We check that the pool area is completely enclosed by a fence, wall, building, or combination of these.

Must be: A fence, wall, building, or combination must fully enclose the pool area with no gaps.

If it fails: Close any gaps in the barrier and extend fencing or walls until the pool area is fully enclosed.

.2537(b)(5)a

What we inspect

Pool enclosure gates/doors self-closing and self-latching

We check that each gate and door in the pool barrier closes and latches on its own.

Must be: Every gate and door in the enclosure must automatically swing shut and latch itself.

If it fails: Install self-closing hinges and a positive self-latching mechanism on each gate and door.

.2537(b)(5)b

(6) Depth and safety markings shall be provided as required in Rule .2523 of this Section

What we inspect

Depth and safety markings maintained as required

We check that the pool's depth markers and safety signage are present, legible, and correctly placed.

Must be: Depth and safety markings must be kept in place and readable as required.

If it fails: Repaint or replace worn, missing, or hard-to-read depth and safety markings.

.2537(b)(6)

(7) Drain covers shall be in good condition and securely attached.

What we inspect

Drain covers in good condition and securely attached

We inspect the pool's drain covers for cracks, damage, and secure attachment.

Must be: Drain covers must be undamaged and securely fastened in place.

If it fails: Replace any cracked or broken drain covers and tighten or refasten any loose ones.

.2537(b)(7)

(8) Damaged face plates or fittings shall be repaired or replaced.

What we inspect

Damaged face plates or fittings repaired or replaced

We check that face plates and fittings around your pool are intact and not damaged.

Must be: Any damaged face plates or fittings must be repaired or replaced.

.2537(b)(8)

(9) Underwater light niches shall be maintained or covered so as not to present a potential hazard to bathers.

What we inspect

Underwater light niches maintained or covered to eliminate hazard

We check the underwater light fixtures for damage or exposed parts that could hurt swimmers.

Must be: Underwater light niches must be kept in good repair or covered so they don't pose a hazard.

If it fails: Repair damaged light housings or install a niche cover if the fixture isn't in use.

.2537(b)(9)

(10) Diving equipment and pool slides including stairs and railing shall be maintained in good working order.

What we inspect

Diving equipment maintained in good working order

We check diving boards and diving equipment for wear, looseness, or damage.

Must be: Diving equipment must be kept in good working order.

.2537(b)(10)a

What we inspect

Pool slides, stairs, and railings maintained in good working order

We check pool slides, their stairs, and railings for wear, looseness, or damage.

Must be: Slides, stairs, and railings must be kept in good working order.

.2537(b)(10)b

(11) A timer switch that allows no more than 15 minutes of operation without manual resetting shall be used to control air blowers and hydrotherapy pumps on heated spas.

What we inspect

Heated spa air blower/hydrotherapy timer limited to 15 minutes

We check that the air blower or jet timer on a heated spa shuts off on its own.

Must be: The timer must limit blower or jet operation to 15 minutes or less before it needs to be reset by hand.

If it fails: Install a timed switch that automatically shuts the blower off after 15 minutes.

.2537(b)(11)

(12) All breaks in grade of the pool bottom including the leading edges of stair treads and seats and the tops of breakpoints where the slope of the bottom changes at a depth of five feet (15m) or less shall be marked with a contrasting color band by May 1, 2000. Contrasting color bands are not required where a registered engineer, registered architect or licensed swimming pool contractor certifies in writing that structural weakness or materials of construction prevent the installation of permanent markings.

What we inspect

Contrasting color bands maintained at grade breaks and breakpoints

We check that edges like stair treads, seats, and slope changes in shallow water are marked with a contrasting stripe.

Must be: Any break in the pool floor five feet deep or less, including stair edges and slope changes, must have a contrasting color band, unless a licensed professional has certified in writing that the pool's structure can't support one.

If it fails: Repaint or reapply a contrasting marking strip along the affected edges.

.2537(b)(12)

(13) All heated spas shall post a caution sign as specified in Rule .2532 of this Section.

What we inspect

Heated spas post required caution sign

We check that a caution sign is posted at the heated spa.

Must be: Heated spas must have the required caution sign posted where it can be seen.

.2537(b)(13)

(14) Pool maintenance shall include removal of debris from the water surface and bottom of the pool.

What we inspect

Debris removed from pool water surface and bottom

We check the pool for leaves, debris, and dirt on the water surface and the bottom.

Must be: Debris must be regularly removed from both the water surface and the pool floor.

If it fails: Skim and vacuum the pool on a regular schedule to keep debris cleared.

.2537(b)(14)

(15) All pool chemicals shall be stored in a clean, dry, well ventilated area and shall be organized so as to prevent chemicals from reacting.

What we inspect

Pool chemicals stored clean, dry, ventilated, and organized to prevent reactions

We check where and how pool chemicals are stored.

Must be: Chemicals must be kept in a clean, dry, well-ventilated space and organized so incompatible ones can't mix and react.

If it fails: Move chemicals to a dry, ventilated storage area and keep different chemical types separated.

.2537(b)(15)

(16) No submersible pumps or mechanical pool cleaning equipment shall be placed or used in the pool while bathers are in the pool.

What we inspect

No submersible pumps or mechanical cleaning equipment while bathers in pool

We check whether cleaning equipment is used while people are swimming.

Must be: Submersible pumps or mechanical pool cleaners must not be running in the pool while bathers are in the water.

.2537(b)(16)

(c) The owner of a public swimming pool shall provide for the operation of the pool by a person or persons who shall be responsible to the owner for operation, maintenance, pool safety and record keeping. The pool owner shall maintain documentation that the person responsible for operating the pool has been trained on pool equipment operation, disease and injury prevention, pool water chemistry and regulatory requirements for public swimming pools. A pool and spa operator certificate issued by the National Swimming Pool Foundation or other organization that provides training on those subjects shall be accepted as meeting this requirement.

What we inspect

Pool operator training documented; CPO or equivalent accepted

We check that the person responsible for running the pool has documented training.

Must be: The pool must have a designated, trained operator with records showing training in equipment operation, safety, water chemistry, and regulations; a Certified Pool Operator (CPO) certificate satisfies this.

If it fails: Have the responsible person complete a CPO or equivalent training course and keep the certificate on file.

.2537(c)

History Note: Authority G.S. 130A-282;
Eff. July 1, 1992;
Temporary Amendment Eff. May 11, 1993 for a period of 180 days or until the permanent rule becomes
effective, whichever is sooner.
The Codifier of Rules determined that the agency's findings of need did not meet the criteria listed in GS
150B-21.1(a);
Temporary Amendment Eff. May 1, 1993 for a period of 180 days or until the permanent rule becomes
effective, whichever is sooner;
Amended Eff. February 1, 2004; April 1, 1999; January 1, 1996; October 1, 1993; May 1, 1993;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2538

Fill and Draw Pools

Fill and draw pools are prohibited. Provisions shall be made for filtration and recirculation of water in all public swimming pools, wading pools, and spas.

What we inspect

Fill and draw pools prohibited

We check that your pool has proper filtration rather than relying on periodic draining and refilling.

Must be: Pools that are simply filled and drained instead of being filtered and recirculated are not allowed.

If it fails: Install a filtration and recirculation system rather than relying on drain-and-refill.

.2538-1

What we inspect

Filtration and recirculation required for all pools, wading pools, and spas

We check that your pool, wading pool, or spa has a working filtration and recirculation system.

Must be: Every pool, wading pool, and spa must have a system that filters and recirculates the water.

.2538-2

History Note: Authority G.S. 130A-282;
Eff. May 1, 1993;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2539

Suction Hazard Reduction

(a) At all public wading pools that use a single main drain for circulation of water, signs shall be posted stating, "WARNING: To prevent serious injury do not allow children in wading pool if drain cover is broken or missing." Signs shall be in letters at least one-half inch in height and shall be posted where they are visible to people entering the wading pool. Submerged suction outlets shall be prohibited in wading pools in accordance with ANSI/PHTA/ICC-7 2020 American National Standard for Suction Entrapment Avoidance in Swimming Pools, Wading Pools, Spas, Hot Tubs, and Catch Basins, which is incorporated by reference, including any subsequent amendments or editions, and available at https://webstore.ansi.org/ at a cost of one hundred and sixty five dollars ($165.00)(hereinafter referred to as "ANSI/PHTA/ICC-7").

What we inspect

Wading pool drain-hazard warning sign required

We check for a warning sign at wading pools that use a single main drain.

Must be: A sign warning about broken or missing drain covers must be posted where entrants can see it, with letters at least half an inch tall.

If it fails: Post the required warning sign near the wading pool entrance with letters at least a half-inch tall.

15A NCAC 18A .2539(a)

What we inspect

Submerged suction outlets prohibited in wading pools

We check whether your wading pool has any submerged suction outlets.

Must be: Wading pools must not have submerged suction outlets at all.

If it fails: Have a pool professional remove or convert the submerged suction outlet to an approved alternative.

15A NCAC 18A .2539(a)

(b) All submerged suction outlets in public swimming pools other than vacuum ports shall be protected by a cover in compliance with ANSI/APSP/ICC-16 2017 (PA 2021) American National Standard for Suction Outlet Fitting Assemblies (SOFA) for Use in Pools, Spas, and Hot Tubs, which is hereby incorporated by reference, including any subsequent amendments or editions, and available at https://webstore.ansi.org/ at a cost of one hundred and sixty five dollars ($165.00)(hereinafter referred to as "ANSI/APSP/ICC-16"). All submerged suction fittings shall be installed in accordance with the manufacturer's instructions.

What we inspect

Suction outlets protected by ANSI/APSP/ICC-16 2017 (PA 2021) drain covers

We check that submerged suction outlets, other than vacuum ports, have approved safety drain covers.

Must be: Every submerged suction outlet must be fitted with a drain cover that meets the current national safety standard.

If it fails: Replace outdated or damaged drain covers with ones certified to the current safety standard.

15A NCAC 18A .2539(b)

What we inspect

Submerged suction fittings installed per manufacturer's instructions

We check that submerged suction fittings were installed the way the manufacturer specifies.

Must be: Suction fittings must be installed exactly as instructed by their manufacturer.

15A NCAC 18A .2539(b)

(c) Public swimming pools that have a single main drain or single submerged suction outlet other than an unblockable drain, or that have multiple outlets in the same plane separated by less than three feet, measured from the centers of the covers, shall have one or more secondary methods of preventing bather entrapment. Secondary methods of preventing bather entrapment include:

What we inspect

Secondary anti-entrapment method for single/close-spaced suction outlets

We check whether your pool needs, and has, a backup safety system to prevent a swimmer from getting stuck against a drain.

Must be: If your pool has a single main drain, a single suction outlet, or outlets closer than 3 feet apart, a secondary anti-entrapment safeguard must be in place.

If it fails: Have a pool professional add an approved secondary anti-entrapment device, such as a safety vacuum release system.

15A NCAC 18A .2539(c)

(1) A safety vacuum release system which ceases operation of the water pump, reverses the circulation flow, or otherwise provides a vacuum release at the suction outlet when a blockage has been detected, and that has been tested by a third party and found to conform with ANSI/PHTA/ICC-7. The operator of the public swimming pool shall test an installed safety vacuum release system using the methodology and at the frequency recommended by the manufacturer, and the test dates and results shall be recorded in the written records required by Rule .2535(11) of this Section. Safety vacuum release systems installed or replaced after the effective date of this Rule shall have a shut off valve for testing the device, if recommended by the manufacturer;

What we inspect

SVRS must conform to ANSI/PHTA/ICC-7 and be third-party tested

We check that any safety vacuum release system (SVRS) is a certified, third-party-tested model.

Must be: An SVRS used as a backup safety device must stop or reverse water flow when it senses a blockage and be independently tested to the national safety standard.

If it fails: Replace an uncertified device with an SVRS that's tested and listed to the national standard.

15A NCAC 18A .2539(c)(1)

What we inspect

Operator tests installed SVRS per manufacturer method/frequency, logs results

We check that the SVRS is being tested regularly and the results are being written down.

Must be: The device must be tested at the method and frequency the manufacturer recommends, with dates and results logged in the pool's written records.

If it fails: Set up a regular testing schedule per the manufacturer's instructions and start a log of results.

15A NCAC 18A .2539(c)(1)

What we inspect

New/replacement SVRS has testing shut-off valve if mfr recommends

We check whether a recently installed or replaced SVRS has a shut-off valve for testing, if the manufacturer calls for one.

Must be: An SVRS installed or replaced after November 1, 2024 must include a shut-off valve for testing, when the manufacturer recommends one.

If it fails: Have a pool professional add the manufacturer-recommended shut-off valve for testing.

15A NCAC 18A .2539(c)(1)

(2) A suction-limiting vent system with an atmospheric opening inaccessible to the public;

What we inspect

Suction-limiting vent system as secondary method

We check whether a suction-limiting vent system is being used as your backup safety measure.

Must be: If used, the vent system's atmospheric opening must not be accessible to the public.

15A NCAC 18A .2539(c)(2)

(3) A gravity drainage system that utilizes a surge tank;

What we inspect

Gravity drainage system with surge tank as secondary method

We check whether a gravity drainage system with a surge tank is being used as your backup safety measure.

Must be: If used, the surge tank system must be properly installed as an accepted secondary safety method.

15A NCAC 18A .2539(c)(3)

(4) An automatic pump shut-off system;

What we inspect

Automatic pump shut-off system as secondary method

We check whether an automatic pump shut-off system is being used as your backup safety measure.

Must be: If used, the system must automatically shut off the pump as an accepted secondary safety method.

15A NCAC 18A .2539(c)(4)

(5) Disabling the submerged suction outlet; or

What we inspect

Disabling the submerged suction outlet as secondary method

We check whether the submerged suction outlet has simply been disabled as your backup safety measure.

Must be: If this method is used, the outlet must be fully and permanently disabled.

15A NCAC 18A .2539(c)(5)

(6) Any other system that complies with ANSI/PHTA/ICC-7.

What we inspect

Any other ANSI/PHTA/ICC-7-compliant system as secondary method

We check whether any other approved anti-entrapment system is in use as your backup safety measure.

Must be: Any alternative system used must comply with the national anti-entrapment safety standard.

15A NCAC 18A .2539(c)(6)

(d) Owners of all public swimming pools shall provide documentation to the Department, as part of the application for an operation permit under Rule .2510(c) of this Section, to verify suction outlet safety compliance. This documentation shall include:
(1) Documentation of the maximum possible flow rate for each [pump] with a submerged suction outlet. This shall be the pump's maximum flow shown on the manufacturer's pump performance curve except where flow reductions are justified with total dynamic head measurements or calculations. Flow reduction measurement documentation shall include photographs taken within two hours of backwashing or replacing the filter with all valves in the fully open position that show the levels of all the gauges used in the public swimming pool. All systems using a flow reduction to comply with this rule shall have a flow meter installed in accordance with manufacturer's instructions confirming that the water flow does not exceed the gallon per minute flow rating of the drain covers or a sealed statement from a Registered Design Professional showing calculations used to justify the reduction;

What we inspect

Permit application documents max possible pump flow for drain safety

We check that the pool's permit paperwork documents the maximum flow rate for each drain pump.

Must be: The owner must document each suction pump's maximum flow rate, based on the manufacturer's performance curve unless a reduction is justified with real measurements.

If it fails: Gather the pump's manufacturer performance curve or have a professional measure and document the flow rate.

15A NCAC 18A .2539(d)(1)

What we inspect

Flow-reduction docs need gauge photos within 2 hrs, valves fully open

We check that flow-reduction documentation includes timely photos of the gauges.

Must be: Photos of all gauges, with valves fully open, must be taken within 2 hours of backwashing or replacing the filter.

If it fails: Retake the gauge photos within the required 2-hour window with all valves fully open.

15A NCAC 18A .2539(d)(1)

What we inspect

Flow-reduction systems need compliant flow meter or sealed RDP statement

We check that any flow-reduction claim is backed by either a flow meter reading or an engineer's sealed calculations.

Must be: The system must have a properly installed flow meter confirming flow stays within the drain covers' rating, or a sealed engineering statement justifying the reduction.

If it fails: Install a compliant flow meter or obtain a sealed statement from a licensed design professional.

15A NCAC 18A .2539(d)(1)

(2) Documentation that drain covers are in compliance with ANSI/APSP/ICC-16 and the manufacturer's instructions. This includes documentation that each drain cover on a single or dual drain submerged suction outlet is rated to meet or exceed the pump's maximum flow or the measured flow of the water through the submerged suction outlets. Drain covers on a submerged suction system with three or more suction outlets shall together be rated to meet or exceed the pump's maximum flow with one drain completely blocked, unless the combined flow of all unblockable drains meet or exceed the pump's maximum flow or the measured flow of the water; and

What we inspect

Drain covers documented ICC-16 compliant and rated to pump's max flow

We check that documentation shows the drain covers meet the national safety standard and are rated for the pump's flow.

Must be: Each drain cover must be documented as compliant with the drain cover safety standard and rated to meet or exceed the pump's maximum or measured flow.

If it fails: Obtain compliance documentation and flow ratings from the drain cover manufacturer.

15A NCAC 18A .2539(d)(2)

What we inspect

3+ outlet systems: combined cover rating meets pump flow, one blocked

We check that pools with three or more suction outlets can still handle the flow if one drain gets blocked.

Must be: The combined rating of all drain covers must meet or exceed the pump's maximum flow even with one drain fully blocked, unless the remaining unblockable drains alone can handle it.

If it fails: Have a pool professional verify combined drain cover ratings and upgrade covers if needed.

15A NCAC 18A .2539(d)(2)

(3) Documentation that drain sumps meet the dimensional requirements specified in the drain cover manufacturer's installation instructions.

What we inspect

Drain sumps documented to meet manufacturer's dimensional requirements

We check that documentation confirms the drain sumps are sized as the drain cover manufacturer requires.

Must be: Drain sump dimensions must be documented as matching the drain cover manufacturer's installation instructions.

If it fails: Obtain sump dimension documentation or have a professional verify and adjust the sump to spec.

15A NCAC 18A .2539(d)(3)

(e) Operators of all public swimming pools shall inspect pools daily to ensure the drain covers are not missing, broken, or cracked and are securely attached. The operator shall close the public swimming pool until missing, broken, or cracked suction fittings are replaced and loose suction fittings are resecured.

What we inspect

Daily inspection of drain covers for missing, broken, or loose condition

We check whether drain covers are being inspected daily for damage or looseness.

Must be: Someone must inspect the pool every day to confirm drain covers aren't missing, broken, cracked, or loose.

If it fails: Start a daily checklist that includes a visual inspection of all drain covers.

15A NCAC 18A .2539(e)

What we inspect

Pool closes until damaged drain covers replaced, loose ones resecured

We check that the pool stays closed if a drain cover is damaged or missing until it's fixed.

Must be: The pool must remain closed until any missing, broken, or cracked drain cover is replaced and any loose one is resecured.

If it fails: Close the pool immediately and replace or resecure the drain cover before reopening.

15A NCAC 18A .2539(e)

History Note: Authority G.S. 130A-282;
Temporary Adoption Eff. June 1, 1994 for a period of 180 days or until the permanent rule becomes effective,
whichever is sooner;
Eff. October 1, 1994;
Amended Eff. May 1, 2010; January 1, 2006; February 1, 2004; April 1, 1999;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019;
Amended Eff. November 1, 2024.
.2540

Reporting of Injury or Illness

The pool operator shall report any death, serious injury or complaint of illness attributed by a bather to use of a public swimming pool to the local health department within two working days of the incident or complaint. The report to the health department shall include the following:

What we inspect

Report death/serious injury/illness complaint within 2 working days

We check whether any deaths, serious injuries, or illness complaints tied to pool use were reported.

Must be: Any such incident must be reported to the local health department within 2 business days.

.2540-1

What we inspect

Injury/illness report must include specified information

We check that incident reports include all the required details.

Must be: A report must include the affected person's name and contact info, the date, a description of the injury or complaint, who provided first aid, any hospital, rescue squad, or physician involved, and witness contact information.

If it fails: Use a standard incident report form that captures all the required details.

.2540-2

(1) Name and telephone number or address of the person injured or making a complaint.
(2) Date of the incident or onset of illness.
(3) Description of the type of injury or complaint.
(4) Name and phone number of the person rendering assistance or first aid.
(5) The name of any known hospital, rescue squad or physician providing medical assistance.
(6) Names and phone numbers of available witnesses to the incident.
History Note: Authority G.S. 130A-282;
Eff. January 1, 1996;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2541

Flow Through Pools

Tanks or structures built prior to May 1, 1995 which hold a flowing natural water source for public swimming, diving, wading or recreational use without physical or chemical treatment shall not be required to comply with the rules of this Section.
History Note: Authority G.S. 130A-282;
Eff. January 1, 1996;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2542

In Pool Exercise Equipment

(a) Exercise equipment such as steps, weights, or floats used in a public swimming pool shall be designed and constructed so as not to pose a threat to water quality or bather safety and shall be removed from the pool after each use.

What we inspect

In-pool exercise equipment designed to not threaten water quality/safety

We check that any in-pool exercise gear, like steps, weights, or floats, is safe and won't harm water quality.

Must be: Exercise equipment used in the pool must be designed so it doesn't threaten water quality or swimmer safety.

.2542(a)-1

What we inspect

Portable in-pool exercise equipment removed after each use

We check whether portable exercise equipment like steps, weights, or floats is left in the pool after use.

Must be: Exercise equipment must be taken out of the pool after each use.

.2542(a)-2

(b) Where in-pool exercise equipment such as underwater treadmills remain in a swimming pool when not in use, the following conditions shall be met:
(1) The swimming pool shall be restricted to use only by adults or a lifeguard shall be on duty at all times when children are allowed in the pool.

What we inspect

Pool with fixed exercise equipment restricted to adults or lifeguarded

We check who is allowed to use the pool if fixed exercise equipment, like an underwater treadmill, stays in the water.

Must be: If exercise equipment remains in the pool, the pool must be adults-only or have a lifeguard on duty whenever children are swimming.

.2542(b)(1)

(2) Exercise equipment shall meet Underwriters' Laboratories Standard Number 1647 for exercise equipment as verified in writing by an independent third party testing laboratory.

What we inspect

Permanent in-pool exercise equipment must meet UL Standard 1647

We check whether permanently installed exercise equipment has been certified safe for pool use.

Must be: Permanent in-pool exercise equipment must meet Underwriters Laboratories Standard 1647, verified in writing by an independent testing lab.

If it fails: Get the equipment tested and certified by an accredited lab if documentation is missing.

.2542(b)(2)

(3) The position of underwater equipment shall be marked with colored floats attached by a 3/4 inch diameter rope or other movable barrier that surrounds the equipment with a visible perimeter designed so as not to entangle or otherwise threaten bather safety.

What we inspect

Underwater exercise equipment marked with a visible perimeter

We check that underwater exercise equipment is marked off so swimmers can see and avoid it.

Must be: The equipment's location must be outlined with colored floats on a 3/4 inch rope, or another barrier, that swimmers can see and won't get tangled in.

.2542(b)(3)

(4) Equipment shall be verified by the manufacturer to be designed for use in a public swimming pool and to be free of grease or oil that might negatively impact pool water quality.

What we inspect

In-pool exercise equipment manufacturer-verified and free of grease/oil

We check whether the equipment manufacturer has confirmed the gear is pool-safe and free of grease or oil.

Must be: The manufacturer must verify the equipment is designed for pool use and free of grease or oil that could harm water quality.

If it fails: Request manufacturer documentation, or clean and re-inspect the equipment for grease or oil.

.2542(b)(4)

(5) Any cords or hoses attached to underwater exercise equipment shall not pose a threat of bather entanglement. Cords or hoses which cross a pool deck shall be covered or shielded to prevent tripping. Covers that protrude more than one-half inch from the deck surface shall be sloped at an angle of no more than 30 from the horizontal deck surface.

What we inspect

Cords/hoses on exercise equipment must not create entanglement or trip hazard

We check any cords or hoses connected to underwater exercise equipment for entanglement or tripping hazards.

Must be: Cords or hoses must not risk entangling swimmers, and any that cross the deck must be covered or shielded to prevent tripping.

If it fails: Route cords away from swimmer areas and install a proper deck cover where they cross walking paths.

.2542(b)(5)a

What we inspect

Deck cord covers over 1/2 inch tall sloped at maximum 30 degrees

We check the slope of any raised cord or hose covers on the pool deck.

Must be: If a deck cover sticks up more than half an inch, it must be sloped no steeper than 30 degrees.

If it fails: Replace the cover with a lower-profile, properly beveled version.

.2542(b)(5)b

History Note: Authority G.S. 130A-282;
Eff. January 1, 1996;
Amended Eff. February 1, 2004;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2543

Water Recreation Attractions

(a) Upon written request and approval by the Department, water recreation attractions including water slides, wave pools, rapid rides, lazy rivers, artificial swimming lagoons, and other similar features may deviate from the requirements of this Section with respect to pool profile, depth, freeboard, flow dynamics and surface skimming systems. The Department shall approve the request upon a showing that such deviation performs in a manner equally to or more protective of public health than the requirements of this Section based upon design plans and technical specifications by the designing engineer or equipment manufacturer. Water recreation attractions shall meet all other requirements of this Section.

What we inspect

Design deviation from Section requires Department approval

We check whether unique features like water slides, wave pools, or lazy rivers have proper state approval for any design differences.

Must be: Any deviation from standard pool profile, depth, or flow rules for these attractions needs written approval from the health department showing it's just as safe.

.2543(a)

(b) Water slide landing pools with a capacity of less than 60,000 gallons shall have a circulation and filtration system capable of turning over the entire pool capacity every two hours. Where automatic chemical controllers are used the turnover time shall be no more than three hours. Landing pool dimensions shall be consistent with the slide manufacturer's recommendation.

What we inspect

Water slide landing pool turnover within 2 hours

We check the circulation and filter system serving the water slide's landing pool.

Must be: Landing pools under 60,000 gallons must be able to fully filter and recirculate their entire water volume every 2 hours.

If it fails: Upgrade the pump or filter to increase turnover capacity.

.2543(b)-1

What we inspect

Landing pool turnover within 3 hrs with chemical controllers

We check the turnover rate when an automatic chemical controller is used on the landing pool.

Must be: With an automatic chemical controller in place, the landing pool must fully turn over its water at least every 3 hours.

.2543(b)-2

What we inspect

Water slide landing pool dimensions per manufacturer recommendation

We check that the landing pool's size matches the water slide manufacturer's specifications.

Must be: Landing pool dimensions must match what the slide manufacturer recommends.

.2543(b)-3

(c) When waterfalls are incorporated in water recreation attractions, they shall be constructed with no handholds or footholds to a height of four feet to discourage climbing.

What we inspect

Waterfalls must discourage climbing to a height of 4 feet

We check waterfalls for handholds or footholds that could let someone climb them.

Must be: Waterfalls must be free of handholds or footholds for at least the first 4 feet to discourage climbing.

If it fails: Smooth or resurface the lower 4 feet of the waterfall to remove climbable ledges or grips.

.2543(c)

(d) Interactive play attractions shall be constructed and operated in accordance with the rules of this Section and shall comply with the following:
(1) The recirculation system shall contain a water capacity equal to at least three minutes of maximum flow of all feature pumps and filter circulation pumps combined and shall not be less than 1,000 gallons. Where the water capacity exceeds 10,000 gallons, the minimum capacity shall be based on the lesser of three minutes of maximum feature flow or 7.5 gallons per square foot of splash zone watershed drained to the surge container.

What we inspect

Interactive play attraction surge tank minimum capacity formula

We check the size of the surge tank that holds water for a splash pad or interactive play feature.

Must be: The surge tank must hold at least 3 minutes of the combined maximum pump flow, and never less than 1,000 gallons (with a different formula once capacity tops 10,000 gallons).

.2543(d)(1)

(2) Access shall be provided to the surge water container.

What we inspect

Access to surge water container provided

We check that the surge water container for splash pad features can be accessed for maintenance.

Must be: There must be a way to physically access the surge container.

If it fails: Add or clear an access hatch or panel to the surge tank.

.2543(d)(2)

(3) A filter circulation system shall be provided and shall be separate from the feature pump system except that both systems can draw water from a common drain pipe if the drain and pipe are sized to handle the flow of all pumps without exceeding the flow velocities specified in Rule .2518 of this Section.

What we inspect

Interactive play filter system separate from feature pump system

We check whether the splash feature's filter system is separate from the pumps powering the play features.

Must be: The filter circulation system must be separate from the feature pump system, unless both share a properly sized common drain.

.2543(d)(3)

(4) The filter circulation system shall draw water from the surge container through a variable height surface skimmer and a bottom drain located no more than 6 inches from the bottom of the container.

What we inspect

Interactive play filter draws from surge container via skimmer and bottom drain

We check how the filter draws water from the surge container.

Must be: Water must be drawn through both an adjustable surface skimmer and a bottom drain no more than 6 inches above the container floor.

.2543(d)(4)

(5) The filter circulation system shall filter and return the entire water capacity in no more than 30 minutes and shall operate 24 hours a day.

What we inspect

Interactive play filter turns over capacity in 30 min, continuous

We check the filter's turnover speed and whether it runs continuously.

Must be: The filter must fully cycle all the water within 30 minutes and run 24 hours a day.

If it fails: Increase pump or filter capacity, or fix the controls so the system runs continuously.

.2543(d)(5)

(6) Automatic chemical controllers shall be provided to monitor and adjust the disinfectant residual and pH of the water contained in the system.

What we inspect

Automatic chemical controllers required for interactive play disinfectant/pH

We check for an automatic controller that monitors and adjusts chlorine and pH.

Must be: An automatic chemical controller must be in place to monitor and adjust disinfectant and pH levels.

If it fails: Install an automatic chemical feeder and controller system.

.2543(d)(6)

(7) The disinfectant residual in interactive play attractions shall be maintained at a level of at least two parts per million of free chlorine. Chlorine feeders shall be capable of producing 12 parts per million of free chlorine in the filter circulation piping.

What we inspect

Interactive play attraction disinfectant residual minimum 2 ppm

We test the chlorine level in the splash pad or interactive play water.

Must be: Free chlorine must be at least 2 parts per million.

If it fails: Add chlorine or adjust the feeder until the reading reaches at least 2 ppm.

.2543(d)(7)a

What we inspect

Interactive play chlorine feeders capable of 12 ppm in filter circulation piping

We check the maximum output capacity of the chlorine feeder.

Must be: The chlorine feeder must be capable of dosing up to 12 parts per million in the filter piping.

.2543(d)(7)b

(8) Valves shall be provided to control water flow to the features in accordance with the manufacturers' specifications.

What we inspect

Interactive play feature flow valves per manufacturer specs

We check that valves controlling water flow to play features are set up as the manufacturer specifies.

Must be: Flow-control valves must be installed and adjusted according to the manufacturer's specifications.

.2543(d)(8)

(9) Splash zones shall be sloped to drains sized and located to remove all feature water to the surge tank without water accumulating on the surface.

What we inspect

Splash zones sloped to drains without water accumulation

We check whether the splash zone drains properly without water pooling.

Must be: The splash area must be sloped so all water runs off to drains and the surge tank, with no standing puddles.

If it fails: Regrade or re-slope the surface toward the drains.

.2543(d)(9)

(10) Deck or walkway space is not required outside the splash zone.
(11) Dressing and sanitary facilities shall not be required.
(12) Interactive play features shall not be required to have a fence except the wading pool fence requirements shall apply to interactive play features located inside a swimming pool enclosure.

What we inspect

Interactive play fence exemption inside a pool enclosure

We check whether a splash pad needs its own fence based on where it's located.

Must be: A standalone splash pad doesn't need a fence, but one built inside a pool's fenced area must meet the same fencing rules as a wading pool.

.2543(d)(12)

(13) The safety provisions of Rule .2530 of this Section shall not apply except a sign shall be posted prohibiting pets and glass containers.

What we inspect

Interactive play posts pets/glass sign in lieu of safety provisions

We check for a sign banning pets and glass containers at the splash pad.

Must be: A sign prohibiting pets and glass containers must be posted; the usual pool safety-equipment rules don't otherwise apply here.

.2543(d)(13)

(14) Interactive play attractions built prior to April 1, 2004, that do not comply with these design and construction requirements shall be permitted to operate as built if no water quality or safety violations occur under Rules .2535 and .2537 of this Section.
(e) Training pools shall meet the requirements for swimming pools with the following exceptions:
(1) Training pools shall be equipped with a filter circulation system that filters and returns the entire pool capacity in no more than two hours.

What we inspect

Training pool filter system turns over full capacity within 2 hours

We check the filter turnover rate for a training or teaching pool.

Must be: The filter must be able to fully cycle the pool's entire water volume in 2 hours or less.

.2543(e)(1)

(2) The free chlorine residual in training pools shall be maintained at no less than two parts per million.

What we inspect

Training pool free chlorine residual minimum 2 ppm

We test the chlorine level in the training pool.

Must be: Free chlorine must be at least 2 parts per million.

If it fails: Add chlorine or adjust the feeder to bring the level up to at least 2 ppm.

.2543(e)(2)

(f) Artificial swimming lagoons shall meet the requirements for public swimming pools except as specified in this Rule:

What we inspect

Lagoon non-swimming zone lighting exempt; swimming zones lit for night swimming

We check lighting in the lagoon's swimming zones if night swimming is offered.

Must be: Non-swimming zones don't need to be lit, but swimming zones must have proper lighting whenever night swimming is allowed.

.2543(f)(15)

What we inspect

Mechanical cleaners prohibited near open lagoon swimming zones

We check whether cleaning equipment is being used too close to an open swimming zone.

Must be: Submersible pumps or mechanical cleaners must stay at least 25 feet away from any swimming zone that's open to bathers.

.2543(f)(16)a

What we inspect

Mechanical cleaners in open non-swimming zones need RDP cert and sign

We check that any underwater cleaning equipment running while an area is open to swimmers has been certified safe and is marked with a warning sign.

Must be: A licensed design professional must certify the outlets are safe, and floating parts need a sign, letters at least 4 inches tall, warning people to stay back 25 feet.

If it fails: Add the required warning sign and have a licensed professional certify the suction outlets before running cleaning equipment while the pool is open.

.2543(f)(16)b

(1) Pool shells shall not be required. Liners shall meet the requirements of Rule .2514 of this Section.

What we inspect

Artificial lagoon shell not required; liner meets shell rule

We check the liner used in an artificial swimming lagoon.

Must be: A lagoon doesn't need a hard pool shell, but any liner used must meet the standard pool liner requirements.

.2543(f)(1)

(2) Underwater components of the artificial swimming lagoon or float lines with openings greater than one-half inch shall not be allowed in swimming zones.

What we inspect

Underwater openings over 1/2 in prohibited in swimming zones

We check underwater parts and float lines in the swimming zone for gaps or openings.

Must be: No underwater component or float line in a swimming zone may have an opening larger than half an inch.

If it fails: Replace or cover components with openings wider than half an inch.

.2543(f)(2)

(3) All swimming zone float rope components shall be a color contrasting with the pool liner. Artificial swimming lagoons are not required to meet the float rope location requirements of Rule .2523(e) of this Section regarding breakpoint and slope. A contrasting color band shall not be required on the liner under the rope.

What we inspect

Swimming zone float rope must contrast with liner color

We check that the float rope marking the swim zone stands out against the liner.

Must be: The float rope must be a color that clearly contrasts with the pool liner.

If it fails: Swap in a rope of a contrasting color.

.2543(f)(3)

(4) Each swimming zone and water feature shall meet water quality standards as required in Rule .2535 of this Section. If the water quality of a swimming zone or water feature does not meet the requirements of Rule .2535 of this Section, the operator shall close the swimming zone or water feature and post a sign at the entrance of the swimming zone with legible letters of at least four inches (10 cm) in height stating "ATTENTION: THE SWIMMING ZONE IS CLOSED. SWIMMING IN THIS AREA IS NOT PERMITTED AT THIS TIME." The swimming zone or water feature shall remain closed until the water quality in the swimming zone or water feature complies with the requirements of Rule .2535 of this Section.

What we inspect

Each lagoon swimming zone/water feature meets water quality standard

We test the water quality in every swimming zone and water feature of the lagoon.

Must be: Each zone and feature must independently meet the required water quality standards.

.2543(f)(4)a

What we inspect

Non-compliant lagoon zone closed and posted until water quality restored

We check what happens when a lagoon swim zone's water quality fails to meet standards.

Must be: A failing zone must be closed immediately, with a sign at least 4 inches tall posted announcing the closure, and it must stay closed until water quality is restored.

.2543(f)(4)b

(5) All non-swimming zones shall be maintained so the bottom of the lagoon is visible in all areas.

What we inspect

Lagoon non-swimming zone bottom must be visible everywhere

We check water clarity in the non-swimming areas of the lagoon.

Must be: The lagoon floor must be visible everywhere in the non-swimming zones.

If it fails: Improve filtration or reduce turbidity until the bottom is clearly visible.

.2543(f)(5)

(6) A sign shall be posted at all entrances to the artificial swimming lagoon with legible letters of at least four inches (10 cm) in height stating "NOTICE – NO SWIMMING ALLOWED OUTSIDE OF DESIGNATED SWIMMING ZONES."

What we inspect

Lagoon entrance sign restricting swimming to designated zones

We check for a sign at lagoon entrances restricting swimming to designated areas.

Must be: A sign with letters at least 4 inches tall must be posted at every entrance stating that swimming is only allowed in designated zones.

.2543(f)(6)

(7) Signage shall be posted indicating swimming zones.

What we inspect

Signage posted indicating swimming zones

We check for signage marking where the designated swimming zones are.

Must be: Signs must be posted showing the location of the swimming zones.

.2543(f)(7)

(8) Depth markings and no diving markers shall be provided on decks in swimming zones as required in Rule .2523 of this Section. Signs shall be posted at all entrances to swimming zones with legible letters of at least four inches (10cm) in height stating "NO DIVING" and stating the maximum depth of the swimming zone in Arabic numerals and shall include the word "feet" or the symbol "ft" to indicate the unit of measure.

What we inspect

Depth markings and NO DIVING signs at lagoon swimming zone entrances

We check for depth markers and no-diving signs at the entrances to each swimming zone.

Must be: Each swimming zone entrance needs depth markings on the deck plus a sign, in letters at least 4 inches tall, stating "NO DIVING" and the maximum depth in feet.

.2543(f)(8)

(9) Decks at zero entry areas located within swimming zones are not required to meet the minimum deck area requirements in Rule .2522 of this Section. Access to swimming zones shall be provided for emergency vehicles and personnel. No decks shall be required in non-swimming zones. The requirements of Rule .2515(g)(1) of this Section shall not apply to swimming zones and Rule .2515(g) of this Section shall not apply to non-swimming zones.

What we inspect

Lagoon swimming zones must have emergency vehicle/personnel access

We check whether emergency vehicles and personnel can reach the swimming zones.

Must be: There must be clear access to each swimming zone for emergency vehicles and responders.

If it fails: Clear or designate an access route wide enough for emergency vehicles.

.2543(f)(9)

(10) Swimming zones shall meet all safety provisions as set out in Rule .2530 of this Section. Where swimming zones are separated by more than 75 feet, each swimming zone shall separately meet all safety provisions. Non-swimming zones are exempt from the requirements in Rule .2530 of this Section.

What we inspect

Lagoon swimming zones over 75 ft apart each meet safety provisions

We check that each swimming zone in the lagoon meets full safety requirements on its own.

Must be: Every swimming zone must meet all standard pool safety requirements; if zones are more than 75 feet apart, each one must independently comply.

.2543(f)(10)

(11) A water treatment system that does not meet the requirements of Rules .2518 and .2519 of this Section shall be approved by the Environmental Health Section of the Department's Division of Public Health when the treatment system performs in a manner equal or superior to the systems described in Rules .2518 and .2519 of this Section in terms of water clarification, disinfection, and removal of debris, and results in a disinfectant residual and pH level as required in Subparagraph (f)(4) of this Rule.

What we inspect

Alternative lagoon treatment system needs equal/superior approval

We check whether the lagoon's water treatment system has state approval if it doesn't match the standard design.

Must be: A non-standard treatment system must be approved by the health department as performing equally or better at clarifying, disinfecting, and removing debris.

.2543(f)(11)

(12) The requirements of Rule .2529 of this Section and Rule .2526(e)–(h) of this Section shall not apply. Sanitary facility requirements shall comply with the 2018 North Carolina State Building Code: Plumbing Code, which is incorporated by reference, including any subsequent amendments or editions and available free of charge at: https://codes.iccsafe.org/content/NCPC2018.

What we inspect

Lagoon sanitary facilities comply with NC Plumbing Code instead

We check that the lagoon's restrooms and sanitary facilities follow the state plumbing code.

Must be: Sanitary facilities at an artificial swimming lagoon must comply with the North Carolina Plumbing Code rather than the standard pool facility rules.

.2543(f)(12)

(13) Bacteriological samples shall be collected by the operator in non-swimming zones and tested weekly. One sample shall be collected for every 250 feet of shoreline, with no more than 300 feet and no less than 25 feet between any two sampling locations. The samples shall be collected at least one foot below the surface, in at least three feet of water. The samples shall be analyzed by a laboratory accredited by the North Carolina Drinking Water Laboratory Certification Program, the North Carolina Wastewater/Groundwater Laboratory Certification Program, or the National Environmental Laboratory Accreditation Program. The test results shall be maintained as part of the records required in Rule .2535(11) of this Section.

What we inspect

Weekly bacteriological sampling in non-swimming zones per shoreline spacing

We check the lagoon's weekly water testing records for the non-swimming areas.

Must be: Samples must be taken weekly by an accredited lab, spaced roughly every 250 feet of shoreline (never more than 300 feet or less than 25 feet apart), collected at least one foot deep in at least three feet of water.

.2543(f)(13)

(14) When the result of any test required by Subparagraph (f)(13) of this Rule exceeds the standards in Rule .3402(a) of this Subchapter, the operator shall:

What we inspect

Lagoon exceedance: notify health dept and resample in 24 hrs

We check what happens after a failed bacteria test in the lagoon.

Must be: The operator must notify the local health department and retest the water within 24 hours of getting the failing lab result.

.2543(f)(14)a

What we inspect

Lagoon exceedance: close non-swimming zones, post closure sign

We check whether non-swimming zones are properly closed and posted after a failed bacteria test.

Must be: All non-swimming zones must be closed and a sign at least 4 inches tall posted at every entrance until a retest confirms safe bacteria levels.

.2543(f)(14)b

(A) notify the local health department that permitted the artificial swimming lagoon and resample the water within 24 hours of receipt of the result from the laboratory; and
(B) close all non-swimming zones and post a sign at all non-swimming zone entrances with legible letters of at least four inches (10 cm) in height stating "ATTENTION: ALL NON-SWIMMING ZONES ARE CLOSED. RECREATIONAL ACTIVITIES IN THIS AREA ARE NOT PERMITTED AT THIS TIME." This sign shall remain posted until resampling determines that bacterial levels do not exceed the standards in Rule .3402(a) of this Subchapter.
(15) Non-swimming zones shall not be required to comply with the lighting requirements of Rule .2524 of this Section. When night swimming is allowed, the operator shall provide lighting in swimming zones as required for public swimming pools.
(16) The requirements of Rule .2537(b)(16) of this Section shall not apply. Submersible pumps or mechanical pool cleaning equipment shall not be used in swimming zones or within 25 feet of swimming zones when a swimming zone is open to bathers. If submersible pumps or mechanical pool cleaning equipment are used in non-swimming zones when a non-swimming zone is open to users, the following conditions shall apply:
(A) A registered design professional shall provide design plans or technical specifications that demonstrate that any underwater suction outlets perform in a manner that is equally protective or more protective than the Pool and Hot Tub Alliance's ANSI/APSP/ICC-7 2013 Standard for Suction Entrapment Avoidance in Swimming Pools, which is incorporated by reference, including any subsequent amendments or editions, and available for a fee of one hundred sixty-five dollars ($165.00) at https://www.apsp.org/store1; and
(B) All floating components of submersible pumps or mechanical pool cleaning equipment shall be labeled with a sign above the water line with legible letters of at least four inches (10 cm) in a contrasting color stating: "DANGER: MECHANICAL EQUIPMENT IN USE. STAY BACK 25 FEET."
(17) The requirements of Rules .2521 and .2516(f)(1) of this Section shall not apply to non-swimming zones.
History Note: Authority G.S. 130A-280; 130A-282; S.L. 2011-39; S.L. 2019-88;
Eff. April 1, 1999;
Amended Eff. March 1, 2004;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019;
Temporary Amendment Eff. December 3, 2019;
Amended Eff. October 1, 2020.
.2544

Special Purpose and Therapy Pools

(a) Special purpose and therapy pools shall comply with the requirements for public swimming pools and spas except as specified in this Rule.
(b) Float tanks:
(1) The requirement in Rule .2522 of this Section for a deck or walkway continuous with the top of the pool wall does not apply to isolation float tanks where a clear floor space of at least eight feet by four feet is provided adjacent to the entrance to the tank.

What we inspect

Isolation float tank deck exemption if 8x4 ft clear floor space provided

We check whether an isolation float tank has enough open floor space at its entrance instead of a full surrounding deck.

Must be: A float tank doesn't need a deck around the pool wall if there's a clear floor area at least 8 feet by 4 feet in front of the entrance.

.2544(b)(1)

(2) The requirement in Rule .2532 of this Section for the minimum ceiling height of 7 ½ feet above the rim of the pool does not preclude use of a canopy of a lower height to enclose an isolation float tank provided the canopy can be opened to allow users a standing entry and exit from the float tank.

What we inspect

Float tank canopy ceiling exemption if it opens for standing exit

We check that a float tank's canopy can be opened to let someone stand up and exit safely.

Must be: A float tank's enclosure can be lower than the usual 7.5-foot ceiling height as long as the canopy opens for a standing entry and exit.

.2544(b)(2)

(3) The minimum lighting requirement in Rule .2524 of this Section does not apply to float tanks provided lighting is available for cleaning and is sufficient to provide visibility for entry and exit from the float tank.

What we inspect

Float tank lighting exemption if sufficient for cleaning and entry/exit

We check that a float tank has enough light for cleaning and for people to safely enter and exit.

Must be: Float tanks are exempt from the standard pool lighting rule as long as there's enough light to clean the tank and see well enough to get in and out safely.

.2544(b)(3)

(4) The requirements in Rule .2518 of this Section that recirculation pumps operate 24 hours per day do not preclude turning off the pump during float sessions when a sanitizing cycle is provided that filters and disinfects the entire capacity of the float tank system at least twice before every user enters the pool. When the float tank is not being used, the pump shall either operate continuously or intermittently to filter and disinfect the capacity of the pool twice every hour.

What we inspect

Float tank pump may stop between sessions if sanitizing cycle runs

We check how the float tank's pump is scheduled between float sessions.

Must be: The pump can shut off during a session only if a sanitizing cycle disinfects the water twice before each user enters; otherwise it must disinfect the water twice hourly.

If it fails: Set the sanitizing cycle to run at least twice before each session, or keep the pump filtering and disinfecting twice per hour when the tank isn't in use.

.2544(b)(4)

(5) The requirement in Rule .2518 of this Section that pool pumps three horsepower or smaller meet NSF/ANSI Standard 50 is not applicable when the mineral content of the brine in a float tank is incompatible with standard pool pumps. Pumps that do not meet NSF/ANSI standard 50 shall be approved by the Department when the viscosity of the mineral solution in the float tank requires a pump impeller or magnetic coupling designed to pump viscous liquids. Electrical safety of such pumps shall be verified by an independent third- party testing lab to meet applicable Underwriters Laboratories (UL) Standards.

What we inspect

Float tank pump NSF exemption needs approval and UL safety check

We check that any specialized float tank pump has proper approval and safety certification.

Must be: If the tank's mineral-rich water needs a specialized pump, it must be approved by the health department and independently tested for electrical safety to UL standards.

If it fails: Get the health department's written approval for the specialized pump and have its electrical safety verified by an independent testing lab.

.2544(b)(5)

(6) The requirement in Rule .2532 of this Section for a caution sign at spas with a water temperature above 90 degrees Fahrenheit is not applicable to float tanks that do not exceed an operating temperature of 95 degrees Fahrenheit. Float tanks that exceed an operating temperature of 95 degrees Fahrenheit shall have a posted sign with the same warnings required for hot spas except references to spas may be reworded to reference float tanks or float spas.

What we inspect

Float tank caution sign required above 95°F

We check the float tank's water temperature and whether a caution sign is posted if it runs hot.

Must be: Float tanks kept at 95°F or below don't need a hot-spa caution sign, but tanks above 95°F must post the same warning sign required for hot spas.

If it fails: Post a caution sign with the required hot-spa warnings, reworded for a float tank, if the water runs above 95°F.

.2544(b)(6)

(c) Swim Spas:
(1) Irrespective of Rule .2522(k) of this Section, swim spa training pools that use jetted water for training swimmer athletes under constant supervision of a swim coach may be located above deck level. Swim spa training pools located above deck level shall be in an enclosure secured against unauthorized access or use when a swim coach is not present.

What we inspect

Swim spa training pool above deck level must be secured, unmanned

We check that an elevated swim spa training pool is properly secured when no coach is present.

Must be: A jetted training pool used under a coach's constant supervision can sit above deck level, but it must be enclosed and locked against unauthorized access whenever a coach isn't there.

If it fails: Add a secure enclosure or lock so the training pool can't be accessed when unsupervised.

.2544(c)(1)

(2) The maximum operational water depth of four feet required for spas in Rule .2532 of this Section does not apply to swim spas.

What we inspect

Swim spas exempt from spa 4-foot maximum operational depth

We check the water depth of a swim spa.

Must be: Swim spas don't have to follow the usual 4-foot maximum depth rule that applies to regular spas.

.2544(c)(2)

(3) Ladders, steps or stairs required by Rule .2521 of this Section are not required for an above-ground swim spa where a handhold or handrail is provided to facilitate transfer over the pool wall.

What we inspect

Above-ground swim spa may substitute handrail for ladder/steps

We check that an above-ground swim spa has a safe way to get in and out.

Must be: An above-ground swim spa doesn't need a ladder or steps as long as it has a handhold or handrail to help users climb over the wall.

.2544(c)(3)

(d) Exercise Therapy and Treadmill Pools:
(1) The maximum operational water depth of four feet required for spas in Rule .2532 of this Section does not apply to exercise therapy and treadmill pools.

What we inspect

Exercise therapy/treadmill pools exempt from spa depth limit

We check the water depth of exercise therapy and treadmill pools.

Must be: Exercise therapy and treadmill pools don't have to follow the usual 4-foot maximum depth rule that applies to spas.

.2544(d)(1)

(2) The 30 minute turnover rate required for spa recirculation systems in Rule .2532 of this Section does not apply to exercise therapy or treadmill pools with a water capacity exceeding 1,000 gallons provided that the turnover time does not exceed two hours.

What we inspect

Large exercise therapy pools get 2-hr turnover, not 30 min

We check how quickly a large exercise therapy or treadmill pool's system filters the full volume of water.

Must be: Pools over 1,000 gallons can take up to 2 hours to fully turn over the water instead of the standard 30-minute spa requirement.

.2544(d)(2)

(e) Scuba Training Pools:
(1) The prohibition of underwater ledges in Rule .2516(b) of this Section does not preclude drop-off ledges to the deep-diving portion of pools designed and used for training swimmers to use self-contained underwater breathing apparatus.

What we inspect

Scuba training pools may have drop-off ledges to deep-diving portion

We check whether a scuba training pool's drop-off ledge into the deep-diving area is appropriate for its purpose.

Must be: Scuba training pools are allowed to have a drop-off ledge leading into the deep-diving section, even though underwater ledges are normally prohibited.

.2544(e)(1)

(2) Scuba pools shall comply with the requirements for swimming pools and are not required to meet the requirements for spas in Rule .2532 of this Section.

What we inspect

Scuba training pools follow pool rules, not spa requirements

We check that a scuba training pool is held to standard pool rules rather than spa rules.

Must be: Scuba training pools must meet the regular swimming pool requirements; they don't need to meet the separate spa requirements.

.2544(e)(2)

History Note: Authority G.S. 130A-282;
Eff. April 1, 2013;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. July 20, 2019.
.2545

Display Spa at a Temporary Event

A display spa at a temporary event (DSTE) shall not be required to comply with the Rules of this Section except as specified in this Rule.

What we inspect

DSTE requires hands/forearms-only sign, 2-inch letters

We check that the display spa has the required hands-and-forearms-only warning sign.

Must be: A sign reading "DISPLAY SPA – ONLY HANDS AND FOREARMS ALLOWED IN WATER" must be posted, with letters at least 2 inches tall.

.2545(4)

What we inspect

DSTE must be locked/covered when water quality fails or closed for day

We check that the display spa is covered and locked whenever the water isn't up to standard or the event has closed for the day.

Must be: If water quality fails or the spa is closed for the day, it must have a latched or locked cover that keeps the public from touching the water.

If it fails: Install a latching or locking cover and use it any time the spa is closed or the water isn't within standards.

.2545(5)a

What we inspect

DSTE closure requires posted 'SPA CLOSED' sign, 2-inch letters

We check that a "SPA CLOSED" sign is posted whenever the display spa isn't open.

Must be: A sign reading "SPA CLOSED," with letters at least 2 inches tall, must be posted anytime the spa is closed.

.2545(5)b

What we inspect

DSTE water quality records kept on site during event and 6 months after

We check how long the display spa's water quality records are being kept and where.

Must be: Records must stay on site during the event and be kept for at least 6 months afterward, available to the health department on request.

If it fails: Keep water quality logs on site during the event and store them for 6 months after it ends.

.2545(6)

What we inspect

DSTE chemicals stored in water-resistant covered container away from the public

We check how and where pool chemicals are stored at the temporary event.

Must be: All chemicals must be kept in a covered, water-resistant container in an area the public can't access.

If it fails: Move chemicals into a covered, water-resistant container in a locked or restricted area away from guests.

.2545(7)

What we inspect

DSTE closed and covered when applicant/designee unavailable to supervise

We check that the display spa is covered and locked whenever no one is available to supervise it.

Must be: Whenever the applicant or their designee isn't present to supervise, the spa must have a latched or locked cover that keeps the public from touching the water.

If it fails: Cover and lock the spa any time no one is on hand to supervise it.

.2545(8)

What we inspect

DSTE permit posted and visible to the public for event duration

We check that the display spa's permit is posted somewhere the public can see it.

Must be: The permit must stay posted in a visible location for the entire event.

.2545(9)

What we inspect

DSTE incident reporting follows the standard injury rule

We check that any death, serious injury, or illness complaint linked to the display spa was reported properly.

Must be: Any death, serious injury, or illness complaint tied to the display spa must be reported the same way as required for regular pools.

.2545(10)

(1) A DSTE shall not operate without a permit that has been issued by the local health department that serves the county in which the temporary event is located. The duration of a permit for a DSTE shall be no more than 21 consecutive calendar days. The applicant may apply for additional permits to operate a DSTE for multiple 21-day periods at the same temporary event.

What we inspect

DSTE requires local health department permit, maximum 21 days per permit

We check that a display spa at a temporary event has a valid permit and hasn't exceeded its allowed operating window.

Must be: A temporary event display spa must have a permit from the local health department. Each permit covers up to 21 consecutive days, though more can be requested for that event.

If it fails: Apply for a permit from the local health department, or renew with an additional 21-day permit before the current one expires.

.2545(1)

(2) One permit application shall be submitted for each DSTE. The applicant shall submit the application for a permit at least 15 calendar days before commencing operation of a DSTE. The application form shall be submitted to the local health department that serves the county in which the temporary event is located and shall include the following information:

What we inspect

DSTE permit application must be submitted at least 15 days before operation

We check when the display spa's permit application was submitted relative to the event start date.

Must be: The permit application must be turned in at least 15 days before the display spa starts operating.

If it fails: Submit the permit application at least 15 days before the planned opening date.

.2545(2)a

What we inspect

DSTE application must include applicant, event, and date information

We check that the display spa permit application includes all the required information.

Must be: The application must list the applicant's name, address, and phone number; the event's name and address; the planned operating dates; and the applicant's signature.

If it fails: Fill in any missing applicant, event, date, or signature information on the permit application.

.2545(2)b

(a) applicant's name, address, and phone number;

What we inspect

DSTE not required to have automatic chemical feeders

We check whether a display spa has automatic chemical feeders and whether that's actually required.

Must be: Display spas at temporary events don't have to have automatic chemical feeders, unlike permanent spas.

.2545(3)(a)

(b) name of the temporary event;

What we inspect

DSTE written records limited to disinfectant, pH, and chemicals added

We check what information is being logged in the display spa's water quality records.

Must be: Written records only need to track disinfectant level, pH, and the type and amount of chemicals added — nothing more is required.

.2545(3)(b)

(c) street address of the temporary event;

What we inspect

DSTE disinfectant residual measured before opening and every 4 hours

We check how often the display spa's disinfectant level is being tested during the event.

Must be: Disinfectant level must be measured every day before the spa opens to the public and at least every 4 hours after that until closing.

If it fails: Set a testing schedule that checks disinfectant level before opening and every 4 hours throughout the day.

.2545(3)(c)

(d) proposed operating dates; and

What we inspect

DSTE disinfectant minimum 3 ppm free chlorine

We test the free chlorine level in the display spa's water.

Must be: Free chlorine must stay at 3 parts per million or higher.

If it fails: Add chlorine or check the feed system if levels drop below 3 ppm.

.2545(3)(d)a

What we inspect

DSTE disinfectant minimum 4 ppm free bromine

We test the free bromine level in the display spa's water.

Must be: Free bromine must stay at 4 parts per million or higher.

If it fails: Add bromine or check the feed system if levels drop below 4 ppm.

.2545(3)(d)b

(e) signature of the applicant.

What we inspect

DSTE pH maintained between 7.0 and 7.8

We test the pH of the display spa's water.

Must be: pH must stay between 7.0 and 7.8.

If it fails: Adjust with pH increaser or decreaser to bring the water back into range.

.2545(3)(e)

(3) A DSTE shall meet the requirements of Rule .2535 of this Section, except as follows:
(a) automatic chemical feeders shall not be required;
(b) written records shall only be required to include disinfectant concentration, pH, and the type and amount of chemicals added to the DSTE;
(c) disinfectant residual shall be measured every day before opening the DSTE to the public and every four hours thereafter until the DSTE is closed for the day;
(d) disinfectant concentrations shall be maintained at or above 3 ppm free chlorine or 4 ppm free bromine; and
(e) pH shall be maintained between 7.0-7.8.
(4) A sign shall be posted on each permitted DSTE that states: "DISPLAY SPA – ONLY HANDS AND FOREARMS ALLOWED IN WATER." The text on the sign shall be at least 2 inches in height.
(5) When the water in a DSTE does not meet the water quality standards set out in Item (3) of this Rule or is closed for the day, the DSTE shall be kept closed with a latched or locked cover that prevents the public from coming into contact with the DSTE water. The applicant shall post a sign on the DSTE that states: "SPA CLOSED." The text on the sign shall be at least 2 inches in height.
(6) The applicant shall keep water quality records required under Sub-Item (3)(b) of this Rule on site during the temporary event and for six months after the completion of the temporary event. The applicant shall provide water quality records to the local health department that issued the DSTE permit and the Department upon request.
(7) All pool chemicals stored on-site at the temporary event shall be stored in a water resistant, covered container in an area that is not used by the public.
(8) When the applicant or applicant's designee is not available to supervise a DSTE, the DSTE shall be kept closed with a latched or locked cover that prevents the public from coming into contact with the DSTE water.
(9) The permit for each DSTE shall be posted for the duration of the temporary event in a location that is visible to the public.
(10) The applicant or the applicant's designee shall report any death, serious injury, or complaint of illness attributed to the applicant's DSTE in accordance with Rule .2540 of this Section.
History Note: Authority G.S. 130A-280; 130A-282;
Eff. July 1, 2022.

For general reference only — not legal advice. Always confirm the current rule with the issuing authority.